1、Designation: D1524 15Standard Test Method forVisual Examination of Used Electrical Insulating Liquids inthe Field1This standard is issued under the fixed designation D1524; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year o

2、f last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method for visual examination is applicable toelectrical insulating liquids that have been used intransfor

3、mers, oil circuit breakers, or other electrical apparatusas insulating or cooling media, or both.1.2 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health

4、practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D1500 Test Method for ASTM Color of Petroleum Products(ASTM Color Scale)D2129 Test Method for Color of Clear ElectricalInsulatingLiquids (Platinum-Cobalt Scale)3. Summary of T

5、est Method3.1 The condition of the test specimen is estimated byobservation of cloudiness, foreign particles, or suspendedmatter in the sample by reflected light.4. Significance and Use4.1 By use of this test method and Test Methods D1500 orD2129 the color and condition of a test specimen of electri

6、calinsulating liquid may be estimated during a field inspection,thus assisting in the decision as to whether or not the sampleshould be sent to a central laboratory for full evaluation.Cloudiness, particles of insulation, products of metal corrosion,or other undesirable suspended materials, as well

7、as anyunusual change in color may be detected.5. Apparatus5.1 Sample ContainerThe sample vessel from a colorcomparitor, or a container in which light can be projected fromthe bottom into the sample.5.2 LightA light source such as a pen light with a No. 222bulb.5.3 ClothPhotographers focusing cloth.6

8、. Procedure6.1 Tyndall Beam ExaminationProject a narrow focusedlight beam from the pen light upward through the samplecontainer, using the photographic focusing cloth to excludeextraneous light. Carefully examine the test specimen bymeans of this light. A test specimen of good insulating liquidwill

9、appear clean and bright. Haziness or cloudiness usuallydenotes moisture in suspension or sludge. If the dielectricstrength is satisfactory, the cloudiness may be caused byoxidation products, in which case the neutralization numberwill probably be high and the interfacial tension low. Particlesof met

10、als, insulation, carbon, and other matter will show upvery markedly by reflected light. Report the electrical insulat-ing liquid as failing the test if the appearance of any conditionother than clear and bright is observed.7. Report7.1 Report the following information:7.1.1 Type of insulating liquid

11、,7.1.2 Pass or fail, and the description of any deviation fromperfectly clear and bright,7.1.3 Evidence of sediment or free water,7.1.4 Approximate temperature of the liquid at the time thetest specimen was taken, and7.1.5 Approximate temperature of the liquid at time ofobservation, if other than at

12、 room temperature.8. Precision and Bias8.1 It is not practical to specify the precision and bias of thistest method because this is a rapid field examination to screentest specimens for further testing.1This test method is under the jurisdiction of ASTM Committee D27 onElectrical Insulating Liquids

13、and Gases and is the direct responsibility of Subcom-mittee D27.07 on Physical Tests.Current edition approved Oct. 1, 2015. Published October 2015. Originallyapproved in 1968. Last previous edition approved in 2010 as D1524 94 (2010).DOI: 10.1520/D1524-15.2For referenced ASTM standards, visit the AS

14、TM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. Unite

15、d States18.2 An interlaboratory investigation was conducted in 1968to support this test method. The results of this investigationwere first reported in January 1969.39. Keywords9.1 Tyndell beam effect; visual examinationASTM International takes no position respecting the validity of any patent right

16、s asserted in connection with any item mentionedin this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the riskof infringement of such rights, are entirely their own responsibility.This standard is subject to revision at any t

17、ime by the responsible technical committee and must be reviewed every five years andif not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standardsand should be addressed to ASTM International Headquarters. Your comments will

18、 receive careful consideration at a meeting of theresponsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you shouldmake your views known to the ASTM Committee on Standards, at the address shown below.This standard is copyrighted by ASTM

19、 International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the aboveaddress or at 610-832-9585 (phone), 610-832-9555 (fax), or serviceastm.org (e-mail); or

20、through the ASTM website(www.astm.org). Permission rights to photocopy the standard may also be secured from the Copyright Clearance Center, 222Rosewood Drive, Danvers, MA 01923, Tel: (978) 646-2600; http:/ data have been filed at ASTM International Headquarters and maybe obtained by requesting Research Report RR:D27-1008.D1524 152