ASTM D2300-2000 Standard Test Method for Gassing of Insulating Liquids Under Electrical Stress and Ionization (Modified Pirelli Method)《在电应力和电离作用下绝缘液体放气的标准试验方法(改进的皮勒里法)》.pdf

上传人:吴艺期 文档编号:511415 上传时间:2018-12-01 格式:PDF 页数:5 大小:49.91KB
下载 相关 举报
ASTM D2300-2000 Standard Test Method for Gassing of Insulating Liquids Under Electrical Stress and Ionization (Modified Pirelli Method)《在电应力和电离作用下绝缘液体放气的标准试验方法(改进的皮勒里法)》.pdf_第1页
第1页 / 共5页
ASTM D2300-2000 Standard Test Method for Gassing of Insulating Liquids Under Electrical Stress and Ionization (Modified Pirelli Method)《在电应力和电离作用下绝缘液体放气的标准试验方法(改进的皮勒里法)》.pdf_第2页
第2页 / 共5页
ASTM D2300-2000 Standard Test Method for Gassing of Insulating Liquids Under Electrical Stress and Ionization (Modified Pirelli Method)《在电应力和电离作用下绝缘液体放气的标准试验方法(改进的皮勒里法)》.pdf_第3页
第3页 / 共5页
ASTM D2300-2000 Standard Test Method for Gassing of Insulating Liquids Under Electrical Stress and Ionization (Modified Pirelli Method)《在电应力和电离作用下绝缘液体放气的标准试验方法(改进的皮勒里法)》.pdf_第4页
第4页 / 共5页
ASTM D2300-2000 Standard Test Method for Gassing of Insulating Liquids Under Electrical Stress and Ionization (Modified Pirelli Method)《在电应力和电离作用下绝缘液体放气的标准试验方法(改进的皮勒里法)》.pdf_第5页
第5页 / 共5页
亲,该文档总共5页,全部预览完了,如果喜欢就下载吧!
资源描述

1、Designation: D 2300 00Standard Test Method forGassing of Electrical Insulating Liquids Under ElectricalStress and Ionization (Modified Pirelli Method)1This standard is issued under the fixed designation D 2300; the number immediately following the designation indicates the year oforiginal adoption o

2、r, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method measures the rate at which gas isevolved or absorbed by insu

3、lating liquids when subjected toelectrical stress of sufficient intensity to cause ionization incells having specific geometries.1.2 This test method is not concerned with bubbles arisingfrom supersaturation of the insulating liquid.1.3 This standard does not purport to address all of thesafety conc

4、erns, if any, associated with its use. It is theresponsibility of whoever uses this standard to consult andestablish appropriate safety and health practices and deter-mine the applicability of regulatory limitations prior to use.For specific precautions see 5.1.4 and 8.4.2. Referenced Documents2.1 A

5、STM Standards:D 924 Test Method for Dissipation Factor (or Power Factor)and Relative Permittivity (Dielectric Constant) of Electri-cal Insulating Liquids23. Summary of Test Method33.1 After being saturated with a gas (usually hydrogen), theinsulating liquid is subjected to a radial electrical stress

6、. Thegas space above the insulating liquid film is ionized due to theelectrical stresses and therefore the insulating liquid surface atthe insulating liquid-gas interface is subjected to ionic bom-bardment. The evolving or absorbing of gas is calculated involume per unit of time from changes in pres

7、sure with timefrom two specimens run on the same sample.3.2 This test method indicates whether insulating liquids aregas absorbing or gas evolving under the test conditions.4. Significance and Use4.1 For certain applications when insulating liquid isstressed at high voltage gradients, it is desirabl

8、e to be able todetermine the rate of gas evolution or gas absorption underspecified test conditions. At present time correlation of suchtest results with equipment performance is limited.4.2 In this test method, hydrogen (along with low molecularweight hydrocarbons) is generated by ionic bombardment

9、 ofsome insulating liquid molecules and absorbed by chemicalreaction with other insulating liquid molecules. The valuereported is the net effect of these two competing reactions. Thearomatic molecules or unsaturated portions of moleculespresent in insulating liquids are largely responsible for thehy

10、drogen-absorbing reactions. Both molecule type, as well asconcentration, affects the gassing tendency result. Saturatedmolecules tend to be gas evolving. The relation betweenaromaticity and quantity of unsaturates of the insulating liquidand gassing tendency is an indirect one and cannot be used for

11、a quantitative assessment of either in the insulating liquid.4.3 This test method measures the tendency of insulatingliquids to absorb or evolve gas under conditions of electricalstress and ionization based on the reaction with hydrogen, thepredominant gas in the partial discharge. For the test cond

12、i-tions, the activating gas hydrogen, in contrast to other gases,for example, nitrogen, enhances the discrimination of differ-ences in the absorption-evolution patterns exhibited by theinsulating liquids. Insulating liquids shown to have gas-absorbing (H2) characteristics in the test have been used

13、toadvantage in reducing equipment failures, particularly cablesand capacitors. However, the advantage of such insulatingliquids in transformers is not well defined and there has beenno quantitative relationship established between the gassingtendency as indicated by this test method and the operatin

14、g1This test method is under the jurisdiction of ASTM Committee D27 onElectrical Insulating Liquids and Gasesand is the direct responsibility of Subcom-mittee D27.05on Electrical Test.Current edition approved Oct. 10, 2000. Published December 2000. Originallypublished as D 2300 68 T. Last previous ed

15、ition D 2300 98.2Annual Book of ASTM Standards, Vol 10.03.3The original Pirelli method is described by Guiseppe Palandri and UgoPellagatti in the paper. “Gli Oli Isolanti per Cavi Elettrici” (Insulating Oils forElectric Cables), Elettrotecnica (Milan) Jan. 8, 1955. Translation of this paper iscontai

16、ned in “Minutes of the Meeting of the Insulated Conductors Committee of theAmerican Institute of Electrical Engineers,” Nov. 15 and 16, 1955.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.performance of the equipment. This test meth

17、od is not con-cerned with bubble evolution, which may arise from physicalprocesses associated with super-saturation of gases in oil orwater vapor bubbles evolving from wet insulation.5. Apparatus45.1 The apparatus for making gassing tests where theinsulating liquid is saturated in the same cell that

18、 is usedthereafter to electrically stress the insulating liquid is shown inFig. 1. The apparatus consists of the following:5.1.1 Gassing Cell and Buret Assembly, as shown in Fig. 1,with dimensions as given in Fig. 2. The gassing cell consists ofthe following two components:5.1.1.1 Cell made of boros

19、ilicate glass with the part understress constructed of 16 mm inside diameter and 18 mm outsidediameter truebore tubing. This cell has an outer (ground)electrode of painted or plated silver with a vertical slit forobserving the insulating liquid level, and a metal conductorband for ground connection.

20、5.1.1.2 Hollow High-Voltage Electrode made of 10 60.1-mm outside diameter center-less-ground and polished No.304 stainless steel seamless tubing and containing an 18-gagestainless steel capillary tubing as a gas passage. The electrodeshall be supported and centered by a precision-machined 24/40reces

21、sed TFE-fluorocarbon plug. A18-in. needle valve (E) withgas inlet is on top of the electrode.5.1.2 Gas Buret (Fig. 1) made of 7-mm outside diameterborosilicate glass tubing with an etched scale, tapered glassjoint (G) for connecting to the gassing cell, a bypass stopcock(D), and three glass bulbs, (

22、A, B, and C).5.1.3 Oil Bath with thermostatic control to maintain thebath at test temperature 60.5C. The bath shall be equippedwith a stirrer, a heating arrangement capable of maintaining thenecessary temperature control, a suitable support for thegassing test cell assembly, and a thermometer gradua

23、ted in0.1C divisions. As the test is temperature sensitive, it isimportant that the calibration is traceable to a standard, such asNIST.5.1.4 Transparent Safety Shield to protect the operator fromcontact with high voltage.5.1.5 High-Voltage Transformer, providing a test voltagehaving a frequency in

24、the range of 45 to 65 Hz. Thetransformer and its controlling equipment shall be of such sizeand design that with the test specimen in the circuit, the voltagewave shape shall approximate a sinoid with both half cyclesclosely alike. The ratio of peak-to-rms values should be equalto the square root of

25、 two within 65 % while maintaining 10RV 62%.6. Reagents and Materials6.1 Hydrogen, oxygen-free. See Note 1.6.2 Dibutyl Phthalate, reagent grade.6.3 2-Propanol, reagent grade.6.4 Low vapor pressure grease, such as high vacuumsilicone grease.6.5 Unless otherwise indicated, it is intended that all re-a

26、gents shall conform to the Committee on Analytical Reagentsof the American Chemical Society.NOTE 1Hydrogen normally is the saturating gas but other gases, suchas nitrogen, carbon dioxide, argon, or air may be used.7. Preparation of Apparatus7.1 Clean the glass cell by first rinsing it inside and out

27、sidewith a suitable hydrocarbon solvent such as heptane or othersolvent suitable for the dielectric liquid test tested. Then fill thecell with the hydrocarbon solvent and scrub to remove waxydeposits from previous tests. Clean the tapered joint, takingcare that none of the grease enters the cell. Ag

28、ain rinse withhydrocarbon solvent and blow dry with clean compressed air.Check the silver electrode and repair if necessary.7.2 Clean the hollow electrode by blowing a suitable hy-drocarbon solvent through the capillary tube with compressed4Suitable equipment is available from Doble Engineering Comp

29、any, 85 WalnutSt., Watertown, MA 02472.FIG. 1 Schematic Diagram of Cell and Manometer AssemblyFIG. 2 Detailed Dimensions of the Glass Cell and the Inner (High-Voltage) ElectrodeD 2300 002air, rinsing the insulating liquid off the entire electrode with asuitable hydrocarbon solvent, such as heptane,

30、and wiping offany waxy deposit with tissue paper. Polish the surface with a2-propanol soaked towel. If there are visible marks on thestainless steel shaft of the electrode, they should be polishedwith a suitable device, such as a buffing wheel, wiping off thebuffing compound carefully with tissue pa

31、per moistened with asuitable hydrocarbon solvent such as heptane.7.3 Apply a light coat of low vapor pressure silicone greaseto the stopcock (D) and the standard-taper joint (G) andassemble the glass cell and buret, but do not insert the electrodeinto the glass cell.7.3.1 Caution: Do not allow silic

32、one grease to contaminatethe inside of the buret, gassing cell, electrode, or oil.7.4 Fill the buret to the half-full mark with dibutyl phthalate.8. Procedure8.1 Introduce 5 6 0.1 mL of the insulating liquid sampleinto the glass cell by means of a hypodermic syringe.8.2 Lightly coat the TFE-fluoroca

33、rbon plug of the electrodewith the test insulating liquid or low vapor pressure siliconegrease and insert the electrode into the glass cell.NOTE 2It has been found helpful to place a few drops of the testinsulating liquid on top of the TFE-fluorocarbon plug to act as a gas-seal.If there is a leak, u

34、se of the oil may help detect it through the appearanceof gas bubbles at the top of the Teflon plug.8.3 Bring the oil bath up to 80C (for some applications itmay be desirable to use 60C; in either case, report testtemperature as indicated in 10.1.1). Suspend the gassing celland buret assembly in the

35、 oil bath at the level indicated in Fig.1, and connect the lead from the outside electrode to ground.8.4 Attach the gas inlet and outlet connections. When usinghydrogen, the gas outlet should lead outside the building, eitherdirectly or through a fume hood.8.5 Close the stopcock (D) and open the val

36、ve (E) to allowthe saturating gas to bubble through the test insulating liquidand the buret liquid at a steady rate (about 3 bubbles/s) for 10min.8.6 Open the stopcock (D) and continue bubbling thesaturating gas through the test insulating liquid for an addi-tional 5 min.8.7 After a total of 15 min

37、of gas bubbling, close the firstvalve (E) and then the stopcock (D), making certain the liquidlevels in the two legs of the buret are equal.8.8 Connect the high-voltage lead to the center electrode.8.9 Place the transparent safety shield in position and takethe buret reading after checking the bath

38、temperature.NOTE 3To facilitate reading the buret, it has been found helpful toilluminate the buret scale and to use a magnifying glass or a small opticalmagnifying device.8.10 Turn on the high voltage and adjust to 10 kV. Recordthe time and voltage, as well as the buret level, and check theobservat

39、ion slit on the outer electrode for onset of the gassingreaction.8.11 After 10 min, record the buret level, voltage, and bathtemperature.8.12 After an additional 50 min, again record the buretlevel, voltage, and bath temperature, and turn off the voltage.8.13 To ensure the equipment is operating cor

40、rectly it isrecommended that the buret level be read every 10 min untilthe test is terminated. A plot of the readings versus time shouldgive a reasonably straight line. If the data are widely scattered,the equipment should be checked and the test rerun.8.14 For oils with very low gassing tendencies,

41、 it may benecessary to stop the test to vent the manometer. The total gasabsorbed is the sum of the gas absorbed before and afterventing.8.15 Repeat the procedure on a fresh test specimen, 8.1-8.13.9. Calculation9.1 Calculate the gassing tendency as follows:G 5 B602 B10!K/Twhere:G = gassing tendency

42、, L/min,B60= buret reading, mm, at 60 min of test,B10= buret reading, mm, at 10 min of test,K = buret constant = L/mm buret reading, (see Appen-dix X2) andT = test time of computed gassing rate,min = 60 10 = 50 min.NOTE 4This will result in an answer which will be positive ( + ) if gasis evolved, an

43、d negative () if gas is absorbed.9.2 Take the average of the two values of G. If the averagevalues are different by more than 0.3 + 0.26 |X|, then the testshould be repeated. Where |X| is the absolute value of duplicatedeterminations in microliters per minute. Duplicate analysesare performed because

44、 it is difficult to detect when a problemoccurs during a test. The equation to determine when duplicateanalysis are acceptable is based on general experiences and isnot derived from a round-robin program for this test method.9.3 See Appendix X1 to determine the electrical stress forthe electrode sys

45、tem and dielectric liquids.10. Report10.1 Report the following:10.1.1 Test temperature,10.1.2 Test voltage and frequency,10.1.3 Saturating gas,10.1.4 Test period, and10.1.5 Average gassing rate in microlitres per minute.11. Precision and Bias11.1 Precision.11.1.1 ReapeatabilityData is being collecte

46、d for repeat-ability values based on data from one laboratory.11.1.2 ReproducibilityThe difference between two singleand independent results obtained by different operators work-ing in different laboratories on identical test material has notbeen determined because there are insufficient laboratorie

47、s toperform the analysis.11.2 No justifiable statement can be made on the bias of theprocedure in the test method since there is no accepted materialsuitable for reference in determining gassing tendency.D 2300 00312. Keywords12.1 gas absorbing; gas evolving; gassing; insulating liq-uids; insulating

48、 oils; ionization; Pirelli methodAPPENDIXES(Nonmandatory Information)X1. CALCULATION OF ELECTRICAL STRESSX1.1 The electrical stress on the insulating liquid in the cellcan be calculated as follows:Gx51XK1Vln d2/d1K11ln d3/d2K2where:Gx= stress, kV/cm, at distance X in cm from axis of innerelectrode,V

49、 = applied voltage, in kV,K1= dielectric constant of insulating liquid,K2= dielectric constant of glass cylinder,d1= diameter of the inner electrode,d2= inner diameter of the outer glass cylinder, andd3= diameter of the outer glass cylinder.X1.1.1 K1can be measured as outlined in Test MethodD 924. For most insulating mineral oils, the dielectric constantis approximately 2.2. For other insulating liquids, the dielectricconstant may be different and characteristic values should beused.X1.1.2 K2can best be determined on samples of the glasstubing by requesting such sa