ASTM D3487-2008 Standard Specification for Mineral Insulating Oil Used in Electrical Apparatus.pdf

上传人:towelfact221 文档编号:514865 上传时间:2018-12-02 格式:PDF 页数:5 大小:87.17KB
下载 相关 举报
ASTM D3487-2008 Standard Specification for Mineral Insulating Oil Used in Electrical Apparatus.pdf_第1页
第1页 / 共5页
ASTM D3487-2008 Standard Specification for Mineral Insulating Oil Used in Electrical Apparatus.pdf_第2页
第2页 / 共5页
ASTM D3487-2008 Standard Specification for Mineral Insulating Oil Used in Electrical Apparatus.pdf_第3页
第3页 / 共5页
ASTM D3487-2008 Standard Specification for Mineral Insulating Oil Used in Electrical Apparatus.pdf_第4页
第4页 / 共5页
ASTM D3487-2008 Standard Specification for Mineral Insulating Oil Used in Electrical Apparatus.pdf_第5页
第5页 / 共5页
亲,该文档总共5页,全部预览完了,如果喜欢就下载吧!
资源描述

1、Designation: D 3487 08Standard Specification forMineral Insulating Oil Used in Electrical Apparatus1This standard is issued under the fixed designation D 3487; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revisi

2、on. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This specification covers new mineral insulating

3、 oil ofpetroleum origin for use as an insulating and cooling mediumin new and existing power and distribution electrical apparatus,such as transformers, regulators, reactors, circuit breakers,switchgear, and attendant equipment.1.2 This specification is intended to define a mineral insu-lating oil t

4、hat is functionally interchangeable and miscible withexisting oils, is compatible with existing apparatus and withappropriate field maintenance,2and will satisfactorily main-tain its functional characteristics in its application in electricalequipment. This specification applies only to new insulati

5、ng oilas received prior to any processing.2. Referenced Documents2.1 ASTM Standards:3D88 Test Method for Saybolt ViscosityD92 Test Method for Flash and Fire Points by ClevelandOpen Cup TesterD97 Test Method for Pour Point of Petroleum ProductsD 445 Test Method for Kinematic Viscosity of Transparenta

6、nd Opaque Liquids (and Calculation of Dynamic Viscos-ity)D611 Test Methods for Aniline Point and Mixed AnilinePoint of Petroleum Products and Hydrocarbon SolventsD 877 Test Method for Dielectric Breakdown Voltage ofInsulating Liquids Using Disk ElectrodesD 923 Practices for Sampling Electrical Insul

7、ating LiquidsD 924 Test Method for Dissipation Factor (or Power Factor)and Relative Permittivity (Dielectric Constant) of Electri-cal Insulating LiquidsD 971 Test Method for Interfacial Tension of Oil AgainstWater by the Ring MethodD 974 Test Method for Acid and Base Number by Color-Indicator Titrat

8、ionD 1275 Test Method for Corrosive Sulfur in ElectricalInsulating OilsD 1298 Test Method for Density, Relative Density (SpecificGravity), or API Gravity of Crude Petroleum and LiquidPetroleum Products by Hydrometer MethodD 1500 Test Method for ASTM Color of Petroleum Prod-ucts (ASTM Color Scale)D 1

9、524 Test Method for Visual Examination of Used Elec-trical Insulating Oils of Petroleum Origin in the FieldD 1533 Test Method for Water in Insulating Liquids byCoulometric Karl Fischer TitrationD 1816 Test Method for Dielectric Breakdown Voltage ofInsulating Oils of Petroleum Origin Using VDE Electr

10、odesD 1903 Test Method for Coefficient of Thermal Expansionof Electrical Insulating Liquids of Petroleum Origin, andAskarelsD2112 Test Method for Oxidation Stability of InhibitedMineral Insulating Oil by Pressure VesselD 2300 Test Method for Gassing of Electrical InsulatingLiquids Under Electrical S

11、tress and Ionization (ModifiedPirelli Method)D 2440 Test Method for Oxidation Stability of MineralInsulating OilD 2668 Test Method for 2,6-di-tert-Butyl- p-Cresol and2,6-di-tert-Butyl Phenol in Electrical Insulating Oil byInfrared AbsorptionD 2717 Test Method for Thermal Conductivity of LiquidsD 276

12、6 Test Method for Specific Heat of Liquids and Solids1This specification is under the jurisdiction of ASTM Committee D27 onElectrical Insulating Liquids and Gases and is the direct responsibility of Subcom-mittee D27.01 on Mineral.Current edition approved Nov. 1, 2008. Published December 2008. Origi

13、nallyapproved in 1976. Last previous edition approved in 2006 as D3487 00(2006).2Refer to American National Standard C 57.106. Guide for Acceptance andMaintenance of Insulating Oil in Equipment (IEEE Standard 64). Available fromAmerican National Standards Institute (ANSI), 25 W. 43rd St., 4th Floor,

14、 NewYork,NY 10036, http:/www.ansi.org.3For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM Interna

15、tional, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.D 3300 Test Method for Dielectric Breakdown Voltage ofInsulating Oils of Petroleum Origin Under Impulse Con-ditionsD 4059 Test Method forAnalysis of Polychlorinated Biphe-nyls in Insulating Liquids by Gas Chr

16、omatographyD 4768 Test Method for Analysis of 2,6-Ditertiary-ButylPara-Cresol and 2,6-Ditertiary-Butyl Phenol in InsulatingLiquids by Gas ChromatographyD 5837 Test Method for Furanic Compounds in ElectricalInsulating Liquids by High-Performance Liquid Chroma-tography (HPLC)3. Terminology Definitions

17、3.1 Type I Mineral Oilan oil for apparatus where normaloxidation resistance is required. Some oils may require theaddition of a suitable oxidation inhibitor to achieve this.3.2 Type II Mineral Oilan oil for apparatus where greateroxidation resistance is required. This is usually achieved withthe add

18、ition of a suitable oxidation inhibitor.NOTE 1During processing of inhibited mineral oil under vacuum andelevated temperatures, partial loss of inhibitor and volatile portions ofmineral oil may occur. The common inhibitors, 2,6-ditertiary-butylpara-cresol (DBPC/BHT) and 2,6-ditertiary-butyl phenol (

19、DPB), are morevolatile than transformer oil. If processing conditions are too severe,oxidation stability of the oil may be decreased due to loss of inhibitor. Theselectivity for removal of moisture and air in preference to loss of inhibitorand oil is improved by use of a low processing temperature.C

20、onditions that have been found satisfactory for most inhibited mineraloil processing are:Minimum PressureTemperature, C Pa Torr, Approximate40 5 0.0450 10 0.07560 20 0.1570 40 0.380 100 0.7590 400 3.0100 1000 7.5If temperatures higher than those recommended for the operatingpressure are used, the oi

21、l should be tested for inhibitor content andinhibitor added as necessary to return inhibitor content to its initial value.Attempts to dry apparatus containing appreciable amounts of free watermay result in a significant loss of inhibitor even at the conditionsrecommended above.3.3 additiveschemical

22、substances that are added to min-eral insulating oil to achieve required functional properties.3.4 propertiesthose properties of the mineral insulatingoil which are required for the design, manufacture, andoperation of the apparatus. These properties are listed inSection 5.4. Sampling and Testing4.1

23、 Take all oil samples in accordance with Test MethodsD 923.4.2 Make each test in accordance with the latest revision ofthe ASTM test method specified in Section 5.4.3 The oil shall meet the requirements of Section 5 at theunloading point.NOTE 2Because of the different needs of the various users, ite

24、msrelating to packaging, labeling, and inspection are considered to be subjectto buyer-seller agreement.NOTE 3In addition to all other tests listed herein, it is soundengineering practice for the apparatus manufacturer to perform anevaluation of new types of insulating oils in insulation systems, pr

25、ototypestructures, or full-scale apparatus, or any combination thereof, to assuresuitable service life.4.4 Make known to the user the generic type and amount ofany additive used, for assessing any potential detrimentalreaction with other materials in contact with the oil.5. Property Requirements5.1

26、Mineral insulating oil conforming to this specificationshall meet the property limits given inTable 1.The significanceof these properties is discussed in Appendix X2.D 3487 082TABLE 1 Property RequirementsPropertyLimit ASTM TestMethodType I Type IIPhysical:Aniline point, C, min 63A63AD611Color, max

27、0.5 0.5 D 1500Flash point, min, C 145 145 D 92Interfacial tension at 25C, min, dynes/cm 40 40 D 971Pour point, max, C 40B40BD97Relative Density (Specific gravity), 15C/15C max 0.91 0.91 D 1298Viscosity, max, cSt (SUS) at:100C 3.0 (36) 3.0 (36) D 445 or D 8840C 12.0 (66) 12.0 (66)0C 76.0 (350) 76.0 (

28、350)Visual examination clear and bright clear and bright D 1524Electrical:Dielectric breakdown voltage at 60 Hz:Disk electrodes, min, kV 30 30 D 877VDE electrodes, min, kV 0.040-in. (1.02-mm) gap0.080-in. (2.03-mm) gap20C35C20C35CD 1816Dielectric breakdown voltage, impulse conditions D 330025C, min,

29、 kV, needle negative to sphere grounded,1-in. (25.4-mm) gap145D145DGassing tendency, max, L/min +30 +30 D 2300Dissipation factor (or power factor), at 60 Hz max, %: D 92425C100C0.050.300.050.30Chemical:EOxidation stability (acid-sludge test) D 244072 h:% sludge, max, by massTotal acid number, max, m

30、g KOH/g0.150.50.10.3164 h:% sludge, max, by massTotal acid number, max, mg KOH/g0.30.60.20.4Oxidation stability (rotating bomb test), min, minutes 195 D 2112Oxidation inhibitor content, max, % by mass 0.08 0.3 D 4768 or D 2668FCorrosive sulfur noncorrosive D 1275BWater, max, ppm 35 35 D 1533Neutrali

31、zation number, total acid number, max, mgKOH/g0.03 0.03 D 974PCB content, ppm not detectable not detectable D 4059AThe value shown represents current knowledge.BIt is common practice to specify a lower or higher pour point, depending upon climatic conditions.CThese limits by Test Method D 1816 are a

32、pplicable only to as received new oil (see Appendix X2.2.1.2). A new processed oil should have minimum breakdownstrengths of 28 kV and 56 kV for a 0.04 in. (1.02 mm) or 0.08 in. (2.03 mm) gap respectively.DCurrently available oils vary in impulse strength. Some users prefer oil of a 145 kV minimum f

33、or certain applications, while others accept oil with impulse strength aslow as 130 kV for other applications.EFuranic compounds, as determined by Test Method D 5837, are useful for assessing the level of cellulose degradation that has occurred in oil impregnated papersystems. Specifying maximum all

34、owable furan levels in new oils for this purpose should be by agreement between user and supplier.FBoth 2,6-ditertiary-butyl para-cresol (DBPC/BHT) and 2,6-ditertiary butylphenol (DBP) have been found to be suitable oxidation inhibitors for use in oils meeting thisspecification.Preliminary studies i

35、ndicate both Test Methods D 2668 and D 4768 are suitable for determining concentration of either inhibitor or their mixture.D 3487 083APPENDIXES(Nonmandatory Information)X1. SUPPLEMENTARY DESIGN INFORMATIONX1.1 The following values are typical for presently usedmineral insulating oils. For oils deri

36、ved from paraffinic ormixed-base crudes, the apparatus designer needs to know thatthese properties have not changed.Property Typical ValuesASTM TestMethodCoefficient of expansion,/ Cfrom 25 to 100C0.0007 to 0.0008 D 1903Property Typical ValuesASTM TestMethodDielectric constant, 25C 2.2 to 2.3 D 924S

37、pecific heat, cal/g, 20C 0.44 D 2766Thermal conductivity, cal/cmsC, from 20 to 100C(0.30 to 0.40) 3 103D 2717X2. SIGNIFICANCE OF PROPERTIES OF MINERAL INSULATING OILX2.1 Physical PropertiesX2.1.1 Aniline PointThe aniline point of a mineral insu-lating oil indicates the solvency of the oil for materi

38、als that arein contact with the oil. It may relate to the impulse and gassingcharacteristics of the oil.X2.1.2 ColorA low color number is an essential require-ment for inspection of assembled apparatus in the tank. Anincrease in the color number during service is an indicator ofdeterioration of the

39、mineral insulating oil.X2.1.3 Flash PointThe safe operation of the apparatusrequires an adequately high flash point.X2.1.4 Interfacial TensionA high value for new mineralinsulating oil indicates the absence of undesirable polar con-taminants. This test is frequently applied to service-aged oils asan

40、 indicator of the degree of deterioration.X2.1.5 Pour PointThe pour point of mineral insulatingoil is the lowest temperature at which the oil will just flow andmany of the factors cited under viscosity apply. The pour pointof 40C may be obtained by the use of suitable distillates,refining processes,

41、 the use of appropriate long life additives, orany combination thereof. If a pour point additive is used, it isnecessary to make known the amount and chemical composi-tion.X2.1.6 Relative Density (Specific Gravity)The specificgravity of a mineral insulating oil influences the heat transferrates and

42、may be pertinent in determining suitability for use inspecific applications. In extremely cold climates, specificgravity has been used to determine whether ice, resulting fromfreezing of water in oil-filled apparatus, will float on the oil andpossibly result in flashover of conductors extending abov

43、e theoil level. See, for example, “The Significance of the Density ofTransformer Oils.”4X2.1.7 ViscosityViscosity influences the heat transferand, consequently, the temperature rise of apparatus. At lowtemperatures, the resulting higher viscosity influences thespeed of moving parts, such as those in

44、 power circuit breakers,switchgear, load tapchanger mechanisms, pumps, and regula-tors. Viscosity controls mineral insulating oil processing con-ditions, such as dehydration, degassification and filtration, andoil impregnation rates. High viscosity may adversely affect thestarting up of apparatus in

45、 cold climates (for example, sparetransformers and replacements).X2.1.8 Visual ExaminationA simple visual inspection ofmineral insulating oil may indicate the absence or presence ofundesirable contaminants. If such contaminants are present,more definitive testing is recommended to assess their effec

46、t onother functional properties.X2.2 Electrical PropertiesX2.2.1 Dielectric Breakdown Voltage, 60 HzThe dielec-tric breakdown voltage of a mineral insulating oil indicates itsability to resist electrical breakdown at power frequencies inelectrical apparatus.X2.2.1.1 Dielectric BreakdownDisk Electrod

47、esThe testutilizing disk electrodes is useful in assessing the quality of themineral insulating oil as received in tank cars, tank trucks, ordrums. It is not sensitive enough to determine if an oil meetsthe minimum acceptable breakdown strength needed for pro-cessed oil used in some equipment.X2.2.1

48、.2 Dielectric BreakdownVDE ElectrodesTheVDE method (Test Method D 1816) is sensitive to contami-nants, such as water, dissolved gases, cellulose fibers, andconductive particles in oil. Processing involves filtering, dehy-dration, and degassing, which generally improve the break-down strength of the

49、oil. As a general guide, the moisture anddissolved gas content by volume in processed oils should beless 15 ppm and 0.5 % respectively. The minimum breakdownstrength for as received oils is typically lower than that ofprocessed oils because of higher levels of contaminants.X2.2.2 Dielectric Breakdown VoltageImpulseThe im-pulse strength of oil is critical in electrical apparatus. Theimpulse breakdown voltage of an oil indicates its ability toresist electrical breakdown under transient voltage stresses(lightning and switching surg

展开阅读全文