ASTM D7815-2012 3125 Standard Practice for Handling Transportation and Storage of Halon 1211 Bromochlorodifluoromethane (CF2BrCl)《哈龙1211 一溴三氟甲烷 (CF2BrC1) 的装卸 运输和存储的标准实施规程》.pdf

上传人:eastlab115 文档编号:526357 上传时间:2018-12-04 格式:PDF 页数:3 大小:104.08KB
下载 相关 举报
ASTM D7815-2012 3125 Standard Practice for Handling Transportation and Storage of Halon 1211 Bromochlorodifluoromethane (CF2BrCl)《哈龙1211 一溴三氟甲烷 (CF2BrC1) 的装卸 运输和存储的标准实施规程》.pdf_第1页
第1页 / 共3页
ASTM D7815-2012 3125 Standard Practice for Handling Transportation and Storage of Halon 1211 Bromochlorodifluoromethane (CF2BrCl)《哈龙1211 一溴三氟甲烷 (CF2BrC1) 的装卸 运输和存储的标准实施规程》.pdf_第2页
第2页 / 共3页
ASTM D7815-2012 3125 Standard Practice for Handling Transportation and Storage of Halon 1211 Bromochlorodifluoromethane (CF2BrCl)《哈龙1211 一溴三氟甲烷 (CF2BrC1) 的装卸 运输和存储的标准实施规程》.pdf_第3页
第3页 / 共3页
亲,该文档总共3页,全部预览完了,如果喜欢就下载吧!
资源描述

1、Designation: D7815 12Standard Practice forHandling, Transportation, and Storage of Halon 1211,Bromochlorodifluoromethane (CF2BrCl)1This standard is issued under the fixed designation D7815; the number immediately following the designation indicates the year oforiginal adoption or, in the case of rev

2、ision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers guidance and direction to suppliers,recyclers, reclaimers, purchasers, and use

3、rs in the handling,transportation, and storage of Halon 1211.1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.3 This standard does n

4、ot purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standar

5、ds:2D7673 Specification for Halon 1211, Bromochlorodifluo-romethane (CF2BrCl)2.2 CGA Standards:3C-6 Standards for Visual Inspection of Steel CompressedGas CylindersC-7 Guide to Preparation of Precautionary Labeling andMarking of Compressed Gas ContainersP-1 Safe Handling of Compressed Gases in Conta

6、inersSB-1 Hazards of Refilling Compressed Refrigerant (Haloge-nated Hydrocarbon) Gas CylindersSB-5 Hazards of Reusing Disposable Refrigerant (Haloge-nated Hydrocarbon) Gas CylindersSB-18 Use of Refrigerant (Halogenated Hydrocarbon) Re-covery Cylinders2.3 U.S. Government Standards:4CFR Title 40, Part

7、 82.106 Environmental ProtectionAgency,Warning Statement RequirementsCFR Title 49, Part 172 U.S. DOT, Hazardous MaterialsTable, Special Provisions, Hazardous MaterialsCommunications, Emergency Response Information, andTraining RequirementsCFR Title 49, Part 172.101 U.S. DOT, Tables of HazardousMater

8、ials and Special ProvisionsCFR Title 49, Part 173 U.S. DOT, Shippers-General Re-quirements for Shipping and PackagingsCFR Title 49, Part 178 U.S. DOT Specifications for Pack-agingsCFR Title 49, Part 180 U.S. DOT, Continuing Qualificationand Maintenance of Packagings3. Terminology3.1 Definitions of T

9、erms Specific to This Standard:3.1.1 containersstorage vessel for Halon 1211.3.1.2 cylinderscontainers of Halon 1211.3.1.3 Halon 1211bromochlorodifluoromethane; a com-pound used to suppress a fire.3.1.4 insulatedplaced in an isolated situation to protectand prevent the transfer of damage.4. Signific

10、ance and Use4.1 This practice provides requirements for the handling,transportation, and storage of Halon 1211 encountered indistribution through both commercial and military channels. Itis intended to ensure that Halon 1211 is handled, transported,and stored in such a way that its physical property

11、 values arenot degraded. Transport may be by various means, such as, butnot limited to, highway, rail, water, and air.5. Practice5.1 To ensure safe handling, loading, storing, and transport-ing of material, personnel shall be trained in the CGA1This practice is under the jurisdiction of ASTM Committ

12、ee D26 on Haloge-nated Organic Solvents and Fire Extinguishing Agents and is the direct responsi-bility of Subcommittee D26.09 on Fire Extinguishing Agents.Current edition approved Sept. 1, 2012. Published October 2012. DOI: 10.1520/D7815-12.2For referenced ASTM standards, visit the ASTM website, ww

13、w.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from the Compressed Gas Association.4Available from Superintendent of Documents, U.S. Government PrintingOff

14、ice, Washington, DC 20036.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1publications, CFR regulations, and other documents, as listedin Sections 2.2 and 2.3, respectively.5.2 Handling:5.2.1 Handling shall be in accordance with CGA P

15、ublica-tion P-1 Safe Handling of Compressed Gases in Containers.5.2.1.1 Personnel who handle or store, or both, cylinders ofHalon 1211 shall be trained properly to recognize and identifythe characteristics of the product and the proper methods ofsafely handling full, partly full, and empty cylinders

16、.5.2.2 All Halon transfers between storage containers andrecycling processes shall be performed by personnel trained inhandling procedures.5.2.3 Halon 1211 recycling and transfer processes shall bein conjunction with the equipment requirements specified bythe manufacturer.5.2.4 Halon 1211 handling s

17、hall be in nonsmoking, heater-free, ventilated areas to preclude product accumulation. Provi-sions shall be made to ensure that service areas limit Halon1211 concentrations to not exceed1%byvolume for 1 minand 0.01 % by volume for a time weighted exposure of 8 h.5.2.5 Cylinders shall not be over fil

18、led. The liquid portion ofthe liquefied gas shall not completely fill the containersinternal volume and the pressure shall not exceed five fourthsthe service pressure of the container at any temperature up toand including 130F (54C). The maximum permitted fillingdensity for Type I product in accorda

19、nce with SpecificationD7673 shall be 100 lb/ft3 (1602 kg/m3). Filling densityrequirements are specified in CFR Title 49, Part 173.304 andCFR Title 49, Part 173.305.5.2.6 Handling of materials should be done in a manner thatprevents contamination or commingling of materials other thanHalon 1211.5.2.7

20、 Cylinders shall be free of dirt and contamination thatwould contribute to or would cause deterioration of the productduring shipment or storage. Precautions should be taken toprevent the entry of oil, water, or any other foreign matter intothe container. Unique coatings or preservatives applied pri

21、or toshipment to protect the containers are not considered contami-nation.5.3 Transportation:5.3.1 Transportation shall be as specified in accordance withDOT regulations of CFR Title 49 .5.3.1.1 Shipment of materials between distributors,collectors, recyclers, and reclaimers should be within approve

22、dDOT guidelines for Class 2.2, regulated materials. Any furtherprovisions for special transportation or packaging should beagreed upon between the collectors, recyclers, and reclaimers.5.3.1.2 The minimum design pressure requirements shall beas stated in CFR Title 49, Part 173.304. The pressure insi

23、de thecontainer at 70F (21C) shall not exceed the service pressurefor which the container is marked. The pressure inside thecontainer at 130F (54C) shall not exceed five fourths theservice pressure for which the container is marked. Fig. 1illustrates the effect of temperature on cylinders filled wit

24、hmixtures of Halon 1211 and nitrogen.5.3.2 Where possible, transportation shall be by suitablevehicles to preclude cylinder damage by excessive mechanicalFIG. 1 Vapor Pressure of Halon 1211 versus TemperatureD7815 122vibration, shock, freezing, or deleterious high temperaturesthroughout the entire t

25、ransport route.5.3.2.1 If cylinders are likely to be subject to unacceptabletransport conditions, the cylinders should be placed underinsulated conditions.5.3.3 Compressed gas cylinder permanent marking require-ments shall be in accordance with CFR Title 49, Part 178 andmust be maintained in legible

26、 condition as required by CFRTitle 49, Part 173. Warning labels shall be affixed to thecylinders conforming to the requirements of CFR Title 40, Part82.106.5.3.4 Containers used for shipping of Halon 1211 conform-ing to Specification D7673 shall be marked in accordance withCFR Title 49, Part 172 Sub

27、part D “Marking.” The propershipping name for Specification D7673 Type II (pure) Halon1211 is “Chlorodifluorobromomethane or Refrigerant GasR12B1 (do not list both),” UN 1974, Hazard Class 2.2(nonflammable gas). The proper shipping name for nitrogensuperpressurized Halon 1211 is “Liquefied Gas, nonf

28、lammablecharged with nitrogen,” UN1058, Hazard Class 2.2 (nonflam-mable gas).5.4 Storage:5.4.1 Storage shall be in accordance with CGA PublicationP-1 Safe Handling of Compressed Gases in Containers,inqualified cylinders in accordance with CFR Title 49, Parts 173and 178.5.4.2 Cylinders should be stor

29、ed in areas that will protectvessels from physical and environmental damage, and tamper-ing from unauthorized personnel.5.4.2.1 Facilities should be constructed and oriented so thatsafety requirements are fulfilled for storage of pressurizedcylinders.5.4.3 Storage containers shall be fitted with pre

30、ssure-releasemechanisms to limit vessel pressure to not more than theminimum required test pressure of the cylinder. Safety reliefvalves shall be set at no less than 75 %, nor more than 100 %,of the minimum required test pressure of the cylinder. Safetyrelief valves shall be in contact with the vapo

31、r space of thecylinder.5.4.3.1 Periodic hydrostatic testing and re-inspection ofcylinders used for Halon 1121 shall comply with CFR Title 49,Part 173.34.5.4.4 Containers used for storage of Halon 1211 conformingto Specification D7673 shall be clearly marked and labeled toidentify whether the Halon 1

32、211 contained conforms to eitherType I or Type II of Specification D7673. The proper storagename for Specification D7673 Type II (pure) Halon 1211 is“Chlorodifluorobromomethane or Refrigerant Gas R12B1 (donot list both),” UN 1974, Hazard Class 2.2 (nonflammablegas). The proper storage name for nitro

33、gen superpressurizedHalon 1211 is “Liquefied Gas, nonflammable charged withnitrogen,” UN1058, Hazard Class 2.2 (nonflammable gas).5.4.5 Insulation shall be placed on pallets or shoring andprovisions should be made to prevent excessive shock orthermal fluctuations to cylinders.5.4.6 Cylinders shall b

34、e stored in a manner that will preventcontamination from external sources.5.4.6.1 If Halon 1211 in accordance with SpecificationD7673 is stored in the same area as material not in accordancewith Specification D7673, storage shall be segregated orclearly identifiable as not being similar.5.5 Extreme

35、Elevated Temperature ConsiderationsWhenType I or Type II mixtures of Halon 1211 may be exposed toconstant temperatures at or greater than 131F (55C) duringtransportation or storage, higher container pressures will beencountered that require alternative fill in the container to thatspecified in 5.2.5

36、. A maximum non-condensable gas content of1.5 % is recommended for long-term storage of Type II Halon1211. The vapor pressure diagram for Type II Halon 1211 isshown in Fig. 1.6. Inspection6.1 Halon 1211 that has been reclaimed or recycled usingapproved reclamation systems may be released for reissue

37、,provided test examination to validate the material to specifi-cation is fulfilled.6.1.1 Reclaimed or recycled Halon 1211 that cannot beproven to comply with Specification D7673 shall not bereissued. The material shall be processed by environmentallysafe methods until conformance to the product stan

38、dard isachieved.7. Keywords7.1 bromochlorodifluoromethane; chlorodifluorobro-momethane; Refrigerant Gas R 12B1; CF2BrCl; compressedgas; compressed liquefied gas; cylinders; explosion suppres-sant; fire suppressant; Halon 1211; handling; reclamation;recovery; recycling; storage; transportASTM Interna

39、tional takes no position respecting the validity of any patent rights asserted in connection with any item mentionedin this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the riskof infringement of such rights, are entirely th

40、eir own responsibility.This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years andif not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standardsand should

41、 be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of theresponsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you shouldmake your views known to the ASTM Committee on Standa

42、rds, at the address shown below.This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the aboveaddress or at 610-832-9585 (phone), 610-832-9555 (fax), or serviceastm.org (e-mail); or through the ASTM website(www.astm.org). Permission rights to photocopy the standard may also be secured from the ASTM website (www.astm.org/COPYRIGHT/).D7815 123

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > ASTM

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1