1、Designation: E336 15E336 16Standard Test Method forMeasurement of Airborne Sound Attenuation betweenRooms in Buildings1This standard is issued under the fixed designation E336; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the ye
2、ar of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.INTRODUCTIONThis test method is part o
3、f a set of standards for evaluating the sound-insulating properties ofbuilding elements. It is designed to measure the sound isolation between two rooms or to estimatelower limits for sound transmission through a partition element installed as an interior part of abuilding. Others in the set cover t
4、he airborne sound transmission loss of an isolated partition elementin a controlled laboratory environment (Test Method E90), the laboratory measurement of impactsound transmission through floors (Test Method E492), the measurement of impact sound transmis-sion in buildings (Test Method E1007), the
5、measurement of sound transmission through buildingfacades and facade elements (Guide E966), the measurement of sound transmission through acommon plenum between two rooms (Test Method E1414/E1414M), and measurement of thenormalized insertion loss of doors (Test Method E2964).1. Scope1.1 The sound is
6、olation between two spaces in a building is determined by a combination of the direct transmission through thenominally separating building element (as normally measured in a laboratory) and any transmission along a number of indirectpaths, usually referred to as flanking paths. Fig. 1 illustrates t
7、he direct paths and some possible structural flanking paths.Additionalnon-structural flanking paths may include transmission through common air ducts between rooms, or doors to the corridor fromadjacent rooms.1.2 The main part of this test method defines procedures and metrics to assess the sound is
8、olation between two rooms or portionsthereof in a building separated by a common partition including both direct and flanking transmission paths or the apparent soundinsulation of the separating partition.Appropriate measures and their single number ratings are the noise reduction (NR) and noiseisol
9、ation class (NIC), the normalized noise reduction (NNR) and normalized noise isolation class (NNIC), and the apparenttransmission loss (ATL) and apparent sound transmission class (ASTC). With the exception of theATL andASTC under specifiedconditions, these procedures in the main part of the test met
10、hod are only applicable when both room volumes are less than 150m3.NOTE 1The word “partition” in this test method includes all types of walls, floors, or any other boundaries separating two spaces. The boundariesmay be permanent, operable, or movable.1.3 The NR and NIC between two locations may alwa
11、ys be measured and reported though conditions present will influence howmeasurements are made. Restrictions such as minimum room volume or dimensions or maximum room absorption are imposedfor all other measures and ratings in this standard. Thus, conditions may exist that will not allow NNR (NNIC),
12、ATL (ASTC) orFTL (FSTC) to be measured. Where a partition between rooms is composed of parts that are constructed differently, or containsan element such as a door, it is not possible to measure the ATL and ASTC of the individual elements or portions of the partition.To evaluate the field performanc
13、e of a door less than 6 m2 in area, use Test Method E2964.1.4 Annex A1 provides methods to assess the sound transmission through a partition or partition element with the influence offlanking transmission reduced. These methods may be used when it must be demonstrated that a partition has achieved a
14、 specifiedminimum sound attenuation. The results are the field transmission loss (FTL) and field sound transmission class (FSTC).1 This test method is under the jurisdiction of ASTM Committee E33 on Building and Environmental Acoustics and is the direct responsibility of Subcommittee E33.03on Sound
15、Transmission.Current edition approved Sept. 1, 2015Jan. 1, 2016. Published December 2015January 2016. Originally approved in 1971. Last previous edition approved in 20142015as E336 14.E336 15. DOI: 10.1520/E0336-1510.1520/E0336-16.This document is not an ASTM standard and is intended only to provide
16、 the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the sta
17、ndard as published by ASTM is to be considered the official document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States11.5 Annex A2 provides methods to measure the sound isolation between portions of two rooms in a building separated by
18、 acommon partition including both direct and flanking paths when at least one of the rooms has a volume of 150 m3 or more. Theresults are the noise reduction (NR) and noise isolation class (NIC).1.6 The values stated in SI units are to be regarded as standard. No other units of measurement are inclu
19、ded in this standard.1.7 The text of this test method references notes and footnotes which provide explanatory material. These notes and footnotes(excluding those in tables and figures) shall not be considered as requirements of the standard.1.8 This standard may involve hazardous materials, operati
20、ons, and equipment. This standard does not purport to address allof the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriatesafety and health practices and determine the applicability of regulatory limitations prior to use.2
21、. Referenced Documents2.1 ASTM Standards:2C634 Terminology Relating to Building and Environmental AcousticsE90 Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and ElementsE413 Classification for Rating Sound InsulationE492 Test Method for Laboratory
22、Measurement of Impact Sound Transmission Through Floor-Ceiling Assemblies Using theTapping MachineE966 Guide for Field Measurements of Airborne Sound Attenuation of Building Facades and Facade ElementsE1007 Test Method for Field Measurement of Tapping Machine Impact Sound Transmission Through Floor-
23、CeilingAssembliesand Associated Support StructuresE1414/E1414M Test Method for Airborne Sound Attenuation Between Rooms Sharing a Common Ceiling PlenumE2235 Test Method for Determination of Decay Rates for Use in Sound Insulation Test MethodsE2964 Test Method for Measurement of the Normalized Insert
24、ion Loss of Doors2.2 ANSI Standards:3S1.10 Pressure Calibration of Laboratory Standard Pressure MicrophonesS1.11 Specification for Octave-Band and Fractional-Octave-Band Analog and Digital FiltersS1.40 Specification and Verification Procedures for Sound CalibratorsS1.43 Specifications for Integratin
25、g-Averaging Sound Level Meters2.3 IEC Standard:4IEC 60942 ElectroacousticsSound CalibratorsIEC 61672 ElectroacousticsSound Level Meters2.4 ISO Standard:5ISO 16283-1:2014 Acoustics - Field measurement of sound insulation in buildings and of building elements - Part 1:Airbornesound insulation2 For ref
26、erencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standards Document Summary page on the ASTM website.3 Available from American National Standards Institute (ANSI), 25 W. 4
27、3rd St., 4th Floor, New York, NY 10036, http:/www.ansi.orghttp:/www.ansi.org.4 Available from International Electrotechnical Commission (IEC), 3 rue de Varemb, Case postale 131, CH-1211, Geneva 20, Switzerland, http:/www.iec.ch.5 Available from International Organization for Standardization (ISO), 1
28、, ch. de la Voie-Creuse, CP 56, CH-1211 Geneva 20, Switzerland, http:/www.iso.org.FIG. 1 Direct (D) and Some Indirect or Flanking Paths (F and Dotted) in a BuildingE336 1623. Terminology3.1 The following terms used in this test method have specific meanings that are defined in Terminology C634:3.1.1
29、 airborne sound; background noise; decay rate; decibel; diffuse sound field; field sound transmission class, FSTC; fieldtransmission loss, FTL; flanking transmission; pink noise; receiving room; self-noise; sound absorption; sound attenuation; soundinsulation; sound isolation; sound pressure level;
30、sound transmission loss, TL; source roomNOTE 2The unqualified term average sound pressure level in this document means that sound pressure levels were averaged over the measurementregion for specified periods of time.3.2 Definitions of Terms Specific to This Standard:3.2.1 apparent transmission loss
31、, ATL (dB), nof a partition installed in a building, in a specified frequency band isoperationally defined as:ATL5LH12LH2110logS SA2D (1)where:S = the area of the partition common to both source and receiving rooms, m2A2 = the sound absorption in the receiving room, m2L1 = the source room average so
32、und pressure level, dB andL2 = the receiving room average sound pressure level resulting from the combined effect of direct and flanking transmission,dB.3.2.1.1 DiscussionThroughout this test method, log is taken to mean log10, unless otherwise indicated.3.2.1.2 DiscussionThis definition attributes
33、all the power transmitted into the receiving room, by direct and flanking paths, to the area of the partitioncommon to both rooms. If flanking transmission is significant, the ATL will be less than the TL for the partition. Apparenttransmission loss (ATL) is equivalent in meaning to apparent sound r
34、eduction index (ASRI) used by ISO 16283-1:2014.3.2.2 apparent sound transmission class, ASTC, na single number rating obtained by applying the classification procedure ofClassification E413 to apparent transmission loss data.3.2.3 coupled space, na secondary space that is adjacent to and partially o
35、pen to the primary space on the same side of theseparating partition and which meets spatial and sound level distribution requirements sufficient to allow the secondary space tobe included as part of the measurement space with the primary space.3.2.3.1 DiscussionFig. 2 and Fig. 3 illustrate conditio
36、ns that may be coupled spaces.FIG. 2 Coupled Spaces Adjacent to a Primary SpaceE336 1633.2.3.2 DiscussionTo qualify as a coupled space in this standard the space must meet requirements specified in 9.4.1.3.2.4 direct transmission, nsound that travels between a source and a receiving room only throug
37、h the common (separating)building element.3.2.5 noise reduction, NR, (dB), nin a specified frequency band, the difference between the sound pressure levels at twowell-defined locations.3.2.6 noise isolation class, NIC, na single-number rating calculated in accordance with Classification E413 using m
38、easuredvalues of noise reduction.3.2.7 normalized noise reduction, NNR, (dB), nbetween two rooms of less than 150 cubic meters, in a specified frequencyband, the value that the noise reduction, NR, in a given field test would have if the reverberation time in the receiving room were0.5 s. NNR is cal
39、culated as follows:NNR5NR110logS T0.5D (2)where:NR = noise reduction, dB, andT = reverberation time in receiving room, s.3.2.7.1 DiscussionThe normalized noise reduction is intended to approximate the noise reduction that would exist between two ordinarily furnishedrooms.3.2.8 normalized noise isola
40、tion class, NNIC (dB), na single-number rating for noise isolation between two rooms both lessthan 150 cubic meters calculated in accordance with Classification E413 using measured values of normalized noise reduction.(See normalized noise reduction.)4. Summary of Test Method4.1 The source and recei
41、ving rooms are selected, the measurement spaces and volumes in each room are defined and the metricsto be measured are identified based on information given in Section 5 within the restrictions given in 11.3 and Annex A2.4.2 The number and location of sound sources are chosen, sound is produced in t
42、he source room and sound pressure levels aresampled spatially in the measurement spaces in both the source and receiving rooms.4.3 Sound decay rates are measured as necessary depending on the result to be reported.4.4 If a value for noise reduction is to be measured between rooms immediately adjacen
43、t to a common partition where eitheris 150 m3 in volume or greater, the requirements and procedures of Annex A2 must be satisfied.4.5 If values of NNR are to be reported, the requirements of 9.3 must be satisfied. If values of ATL are to be reported, therequirements of 9.4.1 must be satisfied and if
44、ATL is to be reported for a partition between spaces where either is 150 cubic metersin volume or greater, the requirement of 9.4.1.2 must be satisfied.FIG. 3 Receiving Spaces Adjacent to a Coupled Source SpaceE336 1644.6 If a value for the field transmission loss (FTL) is to be measured, the requir
45、ements and procedures of Annex A1 must besatisfied.4.7 Results and single number ratings are calculated and reported.5. Significance and Use5.1 The main part of this standard uses procedures originally developed for laboratory measurements of the transmission lossof partitions. These procedures assu
46、me that the rooms in which the measurements are made have a sound field that reasonablyapproximates a diffuse field. Sound pressure levels in such rooms are reasonably uniform throughout the room and average levelsvary inversely with the logarithm of the room sound absorption. Not all rooms will sat
47、isfy these conditions. Practical experienceand controlled studies (1)6 have shown that the test method is applicable to smaller spaces normally used for work or living, suchas rooms in multi-family dwellings, hotel guest rooms, meeting rooms, and offices with volumes less than 150 cubic meters. Them
48、easures appropriate for such spaces are NR, NNR, andATL. The corresponding single number ratings are NIC, NNIC andASTC.TheATL andASTC may be measured between larger spaces that meet a limitation on absorption in the spaces to provide uniformsound distribution.5.2 Annex A2 was developed for use in sp
49、aces that are very large (volume of 150 m3 or greater). Sound pressure levels duringtesting can vary markedly across large rooms so that the degree of isolation can vary strongly with distance from the common(separating) partition. This procedure evaluates the isolation observed near the partition. The appropriate measure is NR, and theappropriate single number rating is NIC.5.3 It is sometimes necessary to demonstrate that the sound insulation of a partition meets or exceeds a specific criterion. AnnexA1 provides additional requirements, and descri