ASTM E1374-2006(2011) Standard Guide for Open Office Acoustics and Applicable ASTM Standards《开放式办公室声学及其适用的ASTM标准的标准指南》.pdf

上传人:孙刚 文档编号:528572 上传时间:2018-12-05 格式:PDF 页数:5 大小:80.68KB
下载 相关 举报
ASTM E1374-2006(2011) Standard Guide for Open Office Acoustics and Applicable ASTM Standards《开放式办公室声学及其适用的ASTM标准的标准指南》.pdf_第1页
第1页 / 共5页
ASTM E1374-2006(2011) Standard Guide for Open Office Acoustics and Applicable ASTM Standards《开放式办公室声学及其适用的ASTM标准的标准指南》.pdf_第2页
第2页 / 共5页
ASTM E1374-2006(2011) Standard Guide for Open Office Acoustics and Applicable ASTM Standards《开放式办公室声学及其适用的ASTM标准的标准指南》.pdf_第3页
第3页 / 共5页
ASTM E1374-2006(2011) Standard Guide for Open Office Acoustics and Applicable ASTM Standards《开放式办公室声学及其适用的ASTM标准的标准指南》.pdf_第4页
第4页 / 共5页
ASTM E1374-2006(2011) Standard Guide for Open Office Acoustics and Applicable ASTM Standards《开放式办公室声学及其适用的ASTM标准的标准指南》.pdf_第5页
第5页 / 共5页
亲,该文档总共5页,全部预览完了,如果喜欢就下载吧!
资源描述

1、Designation: E1374 06 (Reapproved 2011)Standard Guide forOpen Office Acoustics and Applicable ASTM Standards1This standard is issued under the fixed designation E1374; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of las

2、t revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.INTRODUCTIONThere are no full height partitions in an open-plan office to block sound transmission betweenadjacent work stations. Ins

3、tead, partial height barriers, a sound absorbing ceiling and absorption onvertical surfaces are used to provide sound attenuation between individuals. These, in combinationwith work station layout and appropriate levels of broad band masking sound are used to obtainacceptable degrees of acoustical p

4、rivacy.1. Scope1.1 This guide discusses the acoustical principles and inter-actions that affect the acoustical environment and acousticalprivacy in the open office. In this context, it describes theapplication and use of the series of ASTM standards that applyto the open office.1.2 The values stated

5、 in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use.

6、It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2E1110 Classification for Determination of ArticulationClassE1111 Test Method f

7、or Measuring the InterzoneAttenuationof Open Office ComponentsE1130 Test Method for Objective Measurement of SpeechPrivacy in Open Plan Spaces Using Articulation IndexE1179 Specification for Sound Sources Used for TestingOpen Office Components and SystemsE1414 Test Method for Airborne Sound Attenuat

8、ion Be-tween Rooms Sharing a Common Ceiling PlenumE1573 Test Method for Evaluating Masking Sound in OpenOffices Using A-Weighted and One-Third Octave BandSound Pressure Levels3. Summary of Guide3.1 Acoustical PrivacyThe attenuation of sound betweenneighboring work stations in an open-plan office is

9、typicallymuch less than that potentially available between closed-planoffices. Nevertheless, a degree of acoustical privacy can beachieved if component selection and interaction are under-stood. A successful open plan office is the result of carefulcoordination of the several components, ceiling, wa

10、ll treat-ments, furniture and furnishings, heating, ventilating andair-conditioning system, and masking sound system. (SeeSection 7.)3.1.1 This guide delineates the role and interaction of theseveral components and the application of the relevant ASTMStandards.4. Significance and Use4.1 This guide i

11、s intended for the use of architects, engi-neers, office managers, and others interested in designing,specifying, or operating open offices.4.2 It is not intended to be applied to other than officeenvironments, for example, open plan schools.4.3 While this guide attempts to clarify the many interact

12、ingvariables that influence office privacy, it is not intended tosupplant the experience and judgment of experts in the field ofacoustics. Competent technical advice should be sought for1This guide is under the jurisdiction of ASTM Committee E33 on Building andEnvironmentalAcoustics and is the direc

13、t responsibility of Subcommittee E33.02 onOpen Plan Spaces.Current edition approved Nov. 1, 2011. Published December 2011. Originallyapproved in 1990. Last previous edition approved in 2006 as E1374 06. DOI:10.1520/E1374-06R11.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orc

14、ontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.success in the desi

15、gn of open offices, including comparisons oftest results carried out according to ASTM standards.5. General Open Office Acoustical Considerations5.1 IntroductionAttenuation with DistanceIn almostany enclosed space, there is some reduction of sound level withdistance. In many typical spaces, this dec

16、rease of sound levelwith distance is affected by sound reflections from the ceiling,the walls, and floor. In the open plan office the goal is tomaximize this loss with distance in order to improve acousticalprivacy. This requires a highly absorbent ceiling, some absorp-tion on the floor, and careful

17、 treatment of nearby verticalsurfaces. The ideal is to approach the conditions of theoutdoors, where there are no reflecting surfaces.5.2 Attaining acoustical privacy between work stations,open or closed plan, is determined by the degree to which theintruding sounds from adjacent work stations excee

18、d theambient sound levels at the listeners ear.5.3 The sound pressure levels arriving at the listeners earfrom sources in adjacent work stations depend on the follow-ing:5.3.1 The sound source amplitude, directivity, and orienta-tion.5.3.2 The total attenuation of the sound due to a combina-tion of

19、distance and shielding by intervening barriers.5.3.3 The reinforcement of the direct sound due to reflec-tions from office surfaces such as the ceiling, furniture panels,light fixtures, walls, and windows.5.3.4 The level of ambient sound at the listeners ear. Thiswill often be generated and controll

20、ed by a sound maskingsound system, but in certain positions and frequency ranges,heating, ventilating, and air conditioning equipment (HVAC)may contribute significantly to the ambient sound level.5.4 The attributes in 5.3.1 through 5.3.4 apply regardless ofthe source of the intruding sound. In the o

21、pen plan, both officeequipment and speech are the dominant intruding sources. Inmany cases, the provision for acceptable speech privacy is themajor concern.5.5 Office layout should be designed to avoid obvious noiseintrusion possibilities. Individual work stations should bepositioned relative to col

22、umns, walls, and each other to avoiduninterrupted sound paths between contiguous work stations.Occupant orientation is also important, because there is asignificant difference between the sound level when a talkerfaces a listener versus the talker facing away from the listener,of the order of 9 dB.5

23、.6 Loud Noises Distractions caused by raised voices orloud office equipment usually cannot be controlled by normalopen office constructions. It is recommended that some closedplan spaces be provided to contain such loud equipment orenclose noise sensitive spaces such as conference rooms.5.7 Problem

24、Noise SourcesComputers, business ma-chines, copiers, typewriters, and other noise generating devicesshould be located in isolated (enclosed) rooms or areas tominimize their noise intrusion into the work station. Where thisis impractical, care should be exercised in eliminating orminimizing the noise

25、 generation aspects. Telephones and“speaker phones” are a frequent problem. The former should beequipped with flashing lights, rather than ringers (audibleannunciators). Large typing pools or word processing centerscan generate A-weighted sound levels up to 80 dB. Theseactivities should be contained

26、 in special work areas affordingadequate noise isolation from the surrounding open planspaces.5.8 Undivided WorkspacesAcoustical comfort may beimproved in undivided workspaces such as “bull-pen” offices,drafting rooms, and typing pools by the addition of acousticalabsorption to horizontal and vertic

27、al surfaces, but no suchtreatment alone will provide speech privacy.5.9 ASTM test methods exist for testing components andsystems for open plan offices. These include measuring theattenuation between work stations by the ceiling path , theeffect of barriers such as furniture panels, the effect of fl

28、ankingor reflections from vertical surfaces (see Test Method E1111),measurement of masking sound in the open office (see TestMethod E1573), and the determination of the articulation class(see Classification E1110), that is a single number rating ofsystem component performance. Articulation class doe

29、s notaccount for the effect of masking sound.5.10 Objective Determination of Speech PrivacyTestMethod E1130 describes a method of objectively measuringthe speech privacy in open plan offices. It is based on adetermination of the articulation index.5.10.1 Articulation IndexThe articulation index (AI)

30、 is acomputational method for predicting the intelligibility ofspeech for groups of talkers and listeners. The AI is a weightedfraction representing, for a given speech frequency band andnoise condition, the effective proportion of the standard speechsignal that is available at the listeners ear for

31、 conveyingspeech intelligibility.5.10.1.1 The articulation index ranges from 0.00 to 1.00,with 0.00 representing zero intelligibility and 1.00 completeintelligibility.5.10.1.2 Speech privacy may be described as confidentialwhen speech may be detected but not understood.5.10.1.3 Speech privacy may be

32、 described as normal ornon-intrusive when effort is required to understand the intrud-ing speech. Normal speech privacy may also be described asthe absence of distraction.5.10.1.4 Confidential speech privacy occurs at an AI of 0.05or less. Speech becomes more readily understood with AIvalues greater

33、 than 0.20; at values greater than 0.40 there isessentially no privacy.NOTE 1Additional research is needed to verify the relation betweenthe AI and the subjective judgement of normal privacy in the open plan.(See the appendix of Test Method E1130.)6. Components of the Open Plan Acoustical Environmen

34、t6.1 Ceilings:6.1.1 The sound absorbing characteristics required of theceiling plane for open plan systems are different than those forprivate offices or conference rooms. In open plan spaces, soundfrom the source not controlled by part-height space dividerstravels toward the ceiling plane, where pa

35、rt can be reflectedback into the adjacent work space. To minimize the reflectedsound, the ceiling must absorb most of it. In private offices orconference rooms, some lesser absorption or greater reflectionmay be desirable.E1374 06 (2011)26.1.2 The sound barrier characteristics of the ceiling planehe

36、lps provide spatially uniform masking sound from loud-speakers located in the ceiling plenum. If the sound barrierperformance is low or variable, it may lead to the perceptionsof “hot spots” in the masking sound. Some masking systemdesigns may compensate for these deficiencies or variations.NOTE 2Th

37、ere is currently no accepted objective method of specifyingsingle-pass sound barrier performance of ceiling materials.6.1.3 Lighting fixtures mounted in the ceiling must bechosen with care. Flat, lensed fixtures tend to reflect soundspecularly and should be avoided. Parabolic cell fixtures, areprefe

38、rred because they tend to scatter incident sound. Thesound barrier characteristics of the fixtures should also besimilar to that of the ceiling, to avoid masking sound “hotspots” underneath them.6.1.4 Other ceiling elements, such as return air grilles orfixtures, must also be selected with care, to

39、avoid leakage ofsound from the masking system or surface reflections ofincident sounds.6.1.5 In closed plan spaces frequently associated with openplan areas, the absorption characteristics of the ceiling are ofless importance than its sound barrier characteristics. Anaccepted method of specifying th

40、is performance is by thetwo-room method, in Test Method E1414, that evaluates thesound passing through one ceiling into the plenum and thenback down through the ceiling into the adjacent space. Whereopen and closed plan spaces are adjacent, masking sound isfrequently useful for providing speech priv

41、acy in both spaces.The barrier and absorption characteristics of the ceiling systemshould be optimized where open and closed spaces will bemixed.6.1.6 Test Method E1111 is the preferred method of deter-mining the ceiling absorption characteristics. It is a componenttest and is restricted to measurem

42、ent with a fixed-height spacedivider, fixed sound source height, and microphone positions.A single number rating, convenient for ranking the perfor-mance of the ceiling, is obtained using Classification E1110.Specification E1179 specifies the directional characteristics ofloudspeakers used in this a

43、nd similar tests.NOTE 3Articulation class is the preferred measure of the absorptionproperties necessary for acceptable open plan ceiling performance; soundabsorption ratings derived from reverberation room measurements shouldnot be used.6.2 Sound Barriers and Vertical Surfaces:6.2.1 Sound generated

44、 within the work station and poten-tially intruding into adjacent work spaces is of major concern.This potentially intrusive sound is reduced in the following twoways: ( 1) using barriers that are properly absorptive andappropriately impervious to sound penetration, and (2) reduc-ing the tendency of

45、 sound to “flank” or diffract around theperimeters of such barriers.6.2.2 Sound Reflectors All vertical surfaces are possiblesound reflectors if not specifically treated. Hard, flat, smoothsurfaces represent the worst condition. To reduce or eliminatethese reflections, such surfaces should be highly

46、 absorptive tosound in the frequency range of concern.Aparticularly difficultarea to treat in this regard is the glass in the typical exteriorwall of the office area. Note that materials used to achievesound absorption usually are not effective sound barriers. Theinterzone attenuation provided by a

47、vertical surface can bedetermined in accordance with Test Method E1111. The singlenumber classification for a vertical surface is the ArticulationClass (AC) determined in accordance with ClassificationE1110.6.2.3 Sound Barriers Reduction of sound transmissionthrough barriers separating adjacent work

48、 spaces is normallyachieved by adding an impermeable septum to the center of thebarrier. Care must be exercised in eliminating any possible“through holes” offering unencumbered passageways for soundto “leak” through to adjacent work spaces. The interzoneattenuation provided by a barrier can be deter

49、mined in accor-dance with Test Method E1111. The single number classifica-tion for barriers is the Articulation Class (AC) determined inaccordance with Classification E1110. Severe conditions, forexample, people being located in close proximity to each otheror high source levels, need to be assessed for unwanted soundtransmission paths (“flanking”) or higher barrier performance.6.2.3.1 Flanking TransmissionFlanking can be controlledby proper consideration of the height and length of the barrier,the horizontal distance between adjacent barriers, and thesound absorpt

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > ASTM

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1