1、Designation: E2307 15b An American National StandardStandard Test Method forDetermining Fire Resistance of Perimeter Fire BarriersUsing Intermediate-Scale, Multi-story Test Apparatus1This standard is issued under the fixed designation E2307; the number immediately following the designation indicates
2、 the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.INTRODUCTIONA perimeter fire barrier is the perimeter joint
3、 protection that provides fire resistance to preventpassage of fire from floor to floor within the building at the opening between the exterior wallassembly and the floor assembly. A perimeter fire barrier is a unique building construction detail notaddressed by other fire test methods.Among its oth
4、er functions, a perimeter fire barrier impedes the vertical spread of fire from the floorof origin to the floor(s) above, at the buildings exterior perimeter and accommodates variousmovements such as those induced by thermal differentials, seismicity, and wind loads.This test method describes criter
5、ia and test methods used to determine the fire resistance ofperimeter fire barriers when subjected to standard fire exposure conditions using the intermediate-scale, multistory test apparatus (ISMA). The use of the multi-story test apparatus and this test methodare intended to simulate a possible fi
6、re exposure on a perimeter fire barrier.1. Scope1.1 This test method measures the performance of theperimeter fire barrier and its ability to maintain a seal toprevent fire spread during the deflection and deformation of theexterior wall assembly and floor assembly during the fire test,while resisti
7、ng fire exposure from an interior compartment fireas well as from the flame plume emitted from the windowburner below. The end point of the fire-resistance test is theperiod of time elapsing before the first condition of complianceis reached as the perimeter fire barrier is subjected to atime-temper
8、ature fire exposure.1.2 The fire exposure conditions used are those specified bythis test method for the first 30 min of exposure and thenconform to the Test Methods E119 time-temperature curve forthe remainder of the test in the test room.1.3 This test method specifies the heating conditions, meth-
9、ods of test, and criteria for evaluation of the ability of aperimeter fire barrier to maintain the fire resistance where afloor and exterior wall assembly are juxtaposed to a perimeterjoint.1.4 Test results establish the performance of perimeter firebarriers during the fire-exposure period and shall
10、 not beconstrued as having determined the suitability of perimeter firebarriers for use after that exposure.1.5 This test method does not provide quantitative informa-tion about the perimeter fire barrier relative to the rate ofleakage of smoke or gases or both. While it requires that suchphenomena
11、be noted and reported when describing the generalbehavior of perimeter fire barrier during the fire-resistance test,such phenomena are not part of the conditions of compliance.1.6 Potentially important factors and fire characteristics notaddressed by this test method include, but are not limited to:
12、1.6.1 The performance of the perimeter fire barrier con-structed with components other than those tested, and1.6.2 The cyclic movement capabilities of perimeter firebarriers other than the cycling conditions tested.1.7 This test method is used to measure and describe theresponse of materials, produc
13、ts or assemblies to heat and flameunder controlled conditions but does not by itself incorporateall factors required for the fire-hazard or fire-risk assessment ofthe materials, products, or assemblies under actual fire condi-tions.1.8 The values stated in inch-pound units are to be regardedas stand
14、ard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1This test method is under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsibility of Subcommittee E05.11 on FireResista
15、nce.Current edition approved Oct. 1, 2015. Published November 2015. Originallyapproved in 2004. Last previous edition approved in 2015 as E2307-15a. DOI:10.1520/E2307-15B.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States11.9 The text of
16、 this test method references notes andfootnotes which provide explanatory material. These notes andfootnotes (excluding those in tables and figures) shall not beconsidered as requirements of the standard.1.10 This standard does not purport to address all of thesafety concerns, if any, associated wit
17、h its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2E84 Test Method for Surface Burning Characteristics ofBuilding Mate
18、rialsE108 Test Methods for Fire Tests of Roof CoveringsE119 Test Methods for Fire Tests of Building Constructionand MaterialsE176 Terminology of Fire StandardsE511 Test Method for Measuring Heat Flux Using a Copper-Constantan Circular Foil, Heat-Flux TransducerE631 Terminology of Building Constructi
19、onsE1529 Test Methods for Determining Effects of Large Hy-drocarbon Pool Fires on Structural Members and Assem-bliesE1966 Test Method for Fire-Resistive Joint Systems2.2 Other Documents:Uniform Building Code Standard No. 26-9 Method of Testfor the Evaluation of Flammability Characteristics ofExterio
20、r, Non-Loadbearing Wall Assemblies ContainingCombustible Components Using the Intermediate-ScaleMultistory Test Apparatus3NFPA 285 Standard Method of Test for the Evaluation ofFlammability Characteristics of Exterior Non-Load-Bearing Wall Assemblies Containing Combustible Com-ponents Using the Inter
21、mediate-Scale, Multistory TestApparatus4The 14th Edition of the Gypsum Associations Fire Resis-tance Design Manual (GA 600 94)53. Terminology3.1 Terms defined in Terminology E176 and E631 shallprevail for fire standard and building terms not defined in thisdocument.3.2 Definitions:3.2.1 blockout, na
22、 recess formed in the floor assembly toaccommodate the installation of the perimeter joint protection,flush with the wearing surface of the floor assembly.3.2.2 curtain wall assembly, neither a rated or non-rated,nonbearing exterior wall assembly secured to and supported bythe structural members of
23、the building.3.2.3 exterior wall assembly, na curtain wall or a load-bearing exterior wall that is either fire resistance rated or onethat is not.3.2.4 floor assembly, na fire resistance rated loadbearinghorizontal separating element adjacent to and separate from thefloor of the observation room.3.2
24、.4.1 DiscussionFloor assemblies tested in accordancewith Test Methods E119 are required to be loadbearing.3.2.5 integrity, nthe ability of a perimeter fire barrier,when exposed to fire from two sides, to prevent the passage offlame and hot gases through it and the occurrence of flames onits unexpose
25、d sides as determined by using a cotton pad.3.2.6 maximum joint width, nthe widest opening of theperimeter joint as defined by the test sponsor.3.2.7 minimum joint width, nthe narrowest opening of theperimeter joint as defined by the test sponsor.3.2.8 movement cycle, nthe change between the minimum
26、and the maximum joint widths.3.2.9 nominal joint width, nthe specified opening of theperimeter joint as defined by the test sponsor that is selected fortest purposes.3.2.10 observation room, nthe second-story room of theISMA.3.2.11 perimeter fire barrier, nthe perimeter joint protec-tion that provid
27、es fire resistance to prevent the passage of firefrom floor to floor within the building at the opening betweenthe exterior wall assembly and the floor assembly. The bound-aries are the edge of the floor assembly and the interior face ofthe exterior wall assembly in contact with the perimeter jointp
28、rotection.3.2.11.1 DiscussionFor the purpose of this standard, aknee wall is not to be considered as part of the exterior wall.3.2.12 perimeter joint, nthe linear void located between ajuxtaposed exterior wall assembly and floor assembly toaccommodate various movements induced by thermaldifferential
29、s, seismicity, wind loads, and misalignments of thefloor and wall during construction.3.2.13 perimeter joint protection, na fire-resistive jointsystem located between the exterior wall assembly and thefloor assembly that fills the perimeter joint.3.2.13.1 DiscussionFire-resistive joint system is def
30、inedin Test Method E1966.3.2.14 separating element, na floor assembly or exteriorwall assembly.3.2.15 splice, nthe connection or junction within thelength of a perimeter joint protection.3.2.15.1 DiscussionA splice is a result of the device ormethod used to connect or join multiple lengths of theper
31、imeter joint protection.3.2.16 supporting construction, nthe arrangement of sepa-rating elements forming the intersection into which the perim-eter joint protection is installed.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org.
32、For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3International Conference of Building Officials Inc., 5360 Workman Mill Rd.,Whittier, CA 90601.4National Fire Protection Association, 1 Batterymarch Park, Quincy, MA02269-9101.5Gypsum
33、 Association, 810 First Street NE #510, Washington, DC 20002.E2307 15b23.2.17 test assembly, nthe complete assembly of the testspecimen together with the test apparatus.3.2.18 test room, nthe first-story room of the ISMA.3.2.19 test specimen, nthe specific test details of theperimeter fire barrier.4
34、. Summary of Test Method4.1 This test method describes the following test sequenceand procedure:4.1.1 When the maximum joint width does not equal theminimum joint width, the perimeter fire barrier is movementcycled before being fire tested.4.1.2 A perimeter joint protection and its supporting con-st
35、ruction are conditioned and fire tested.4.1.3 During the fire test, the integrity of the perimeter jointprotection and its supporting construction is determined by useof a cotton pad.5. Significance and Use5.1 This test method provides for the following measure-ments and evaluations:5.1.1 Movement c
36、apacity of the perimeter fire barrier.5.1.2 Loadbearing capacity of the perimeter joint protectionis optional.5.1.3 Ability of the perimeter fire barrier to resist thepassage of flames and hot gases.5.1.4 Transmission of heat through the perimeter fire barrier.5.2 This test method does not provide t
37、he following:5.2.1 Evaluation of the degree to which the perimeter firebarrier contributes to the fire hazard by generation of smoke,toxic gases, or other products of combustion,5.2.2 Measurement of the degree of control or limitation ofthe passage of smoke or products of combustion through theperim
38、eter fire barrier,NOTE 1This test method does not measure the quantity of smoke orhot gases through the floor assembly, the wall assembly, or the perimeterjoint protection.5.2.3 Measurement of flame spread over the surface of theperimeter fire barrier,NOTE 2The information in 5.2.1 through 5.2.3 are
39、 determined byother suitable fire test methods. For example, Test Method E84 is used todetermine 5.2.3.5.2.4 Durability of the test specimen under actual serviceconditions, including the effects of cycled temperature,5.2.5 Effects of a load on the movement cycling of theperimeter fire barrier establ
40、ished by this test method,5.2.6 Rotational, vertical, and horizontal shear capabilitiesof the test specimen,FIG. 1 Plan View of Test Room Burner Positioned in Test Room (See 6.3.2 for Dimensions)E2307 15b35.2.7 Any other attributes of the test specimen, such as wearresistance, chemical resistance, a
41、ir infiltration, water-tightness,and so forth, and5.2.8 A measurement of the capability of the test specimento resist:5.2.8.1 Flame propagation over the exterior faces of the testspecimen,5.2.8.2 Spread of flame within the combustible core com-ponent of the exterior wall assembly from one story to t
42、he next,NOTE 3Some exterior wall assemblies are made from sandwichpanels, which use EPS foam or other similar materials that are combus-tible.5.2.8.3 Spread of flame over the interior surface (room side)of the test specimen from one story to the next, andNOTE 4While it is a failure to have fire on t
43、he interior surface of theobservation room, this test method does not provide a measurement of thatflame spread.5.2.8.4 Lateral spread of flame from the compartment of fireorigin to adjacent spaces.NOTE 5The exterior wall assembly, floor assembly, and perimeterjoint protection are individual compone
44、nts. The capabilities of individualcomponents are not part of this specific test methods Conditions ofCompliance.(1) Window Burner (see 6.3.3)(2) Slot in Burner (see 6.3.3.2)(3) Gas Supply Line (see 6.3.3.3)(4) Perimeter Joint Protection (see 3.2.13)(5) Window (see 7.3.9)(6) Test Room in Test Appara
45、tus (see 3.2.18)(7) Observation Room in Test Apparatus (see 3.2.10)(8) Horizontal Centerline of Burner (see 6.3.3.5)(9) Vertical Centerline of Burner (see 6.3.3.5)(10) Window Burner Location During Test (see 6.3.3.5)(11) Exterior Wall Assembly or Calibration Wall (see 7.3 and 9.2)(12) Test Apparatus
46、 (ISMA) (see 6.2)(13) Floor Assembly (see 7.4)(14) Floor of Observation Room (see 6.2.4.2)(15) Roof Slab (see 6.2.2)(16) Floor of Test Room (see 6.2.2)(17) Window Sill Height (see 7.3.9.2)FIG. 2 Plan View of Window Burner and Side Elevation View of Window Burner LocationE2307 15b45.3 In this test me
47、thod, the test specimens are subjected toone or more specific test conditions. When different testconditions are substituted or the end-use conditions arechanged, it is not always possible by, or from, this test methodto predict changes to the characteristics measured.FIG. 3 Example of an Exterior W
48、all Assembly with Window Opening in a Test Frame (See 7.3.1)E2307 15b5FIG. 4 Typical Copper Thermocouple Disc and Insulating Pipe (See 6.6 and 6.7)FIG. 5 Typical Cotton Wool Pad Holder (See 6.8.2)E2307 15b65.4 This test method is not intended to be used as the onlytest method in the selection of a p
49、erimeter fire barrier. It is notintended as a specification for all attributes required by aFIG. 6 T-Shaped Sensor (See 6.10.1.1)FIG. 7 Tube Sensor (See 6.10.1.2)E2307 15b7FIG. 8 Exposed Thermocouple Layout on Underside of Observation Room Floor in Test Room (See 8.1)FIG. 9 Exposed Thermocouple Layout in Test Room (See 8.2)E2307 15b8perimeter fire barrier, or any of its individual components, inorder for a perimeter fire barrier to be used in a particularapplication.6. Apparatus6.1 The test apparatus described in 6.2 shall be locatedinside a