ASTM E2816-2017 Standard Test Methods for Fire Resistive Metallic HVAC Duct Systems《防火金属采暖通风与空调管道系统的标准试验方法》.pdf

上传人:explodesoak291 文档编号:531941 上传时间:2018-12-05 格式:PDF 页数:24 大小:2.43MB
下载 相关 举报
ASTM E2816-2017 Standard Test Methods for Fire Resistive Metallic HVAC Duct Systems《防火金属采暖通风与空调管道系统的标准试验方法》.pdf_第1页
第1页 / 共24页
ASTM E2816-2017 Standard Test Methods for Fire Resistive Metallic HVAC Duct Systems《防火金属采暖通风与空调管道系统的标准试验方法》.pdf_第2页
第2页 / 共24页
ASTM E2816-2017 Standard Test Methods for Fire Resistive Metallic HVAC Duct Systems《防火金属采暖通风与空调管道系统的标准试验方法》.pdf_第3页
第3页 / 共24页
ASTM E2816-2017 Standard Test Methods for Fire Resistive Metallic HVAC Duct Systems《防火金属采暖通风与空调管道系统的标准试验方法》.pdf_第4页
第4页 / 共24页
ASTM E2816-2017 Standard Test Methods for Fire Resistive Metallic HVAC Duct Systems《防火金属采暖通风与空调管道系统的标准试验方法》.pdf_第5页
第5页 / 共24页
亲,该文档总共24页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

1、Designation: E2816 15aE2816 17 An American National StandardStandard Test Methods forFire Resistive Metallic HVAC Duct Systems1This standard is issued under the fixed designation E2816; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revisio

2、n, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.INTRODUCTIONHeating, Ventilation, Air Conditioning (HVAC) duct systems may be subjected to fire- exposureconditions

3、. ISO 6944 is a standard test method used to evaluate ventilation ducts. However, ISO 6944does not address all of the fire resistive attributes deemed necessary by some authorities havingjurisdiction, for example, (1) the fire-resistive, combustibility, flame spread and smoke generation, anddurabili

4、ty properties of the fire-resistive materials protecting the HVAC duct, (2) the transition fromthe horizontal to a vertical HVAC duct, (3) the attachment of the HVAC ducts supports to thefire-separating elements, (4) the termination of an HVAC duct system and the protection of its ends,(5) the effec

5、ts of rapid cooling and erosion upon the HVAC duct system, (6) the use of fire dampersand (7) the effect of the HVAC duct system on its supporting construction. Many types of fire-resistivematerials are used to protect HVAC ducts. These fire-resistive materials are either applied to HVACducts in the

6、 field or are fabricated as an integral part of the HVAC duct system when shipped from thefactory. Evaluating fire-resistive materials used to protect a HVAC duct from fire is an aid forpredicting their fire performance and helps to establish uniformity in requirements of variousauthorities. To do t

7、his it is necessary that the fire-resistance properties of HVAC ducts protected withfire-resistive materials be measured and specified according to a common standard expressed in termsthat are applicable alike to a wide variety of materials, situations, and conditions of exposure.1. Scope Scope*NOTE

8、 1Use of the standard designation ISO 6944 refers to both ISO 6944:1985 and ISO 6944-1:2008.1.1 These test methods evaluate the fire-resistive materials and the HVAC duct systems surface burning characteristics,non-combustibility, fire resistance, durability, and fire-engulfment with horizontal and

9、vertical through-penetration firestops.NOTE 2The intent of these test methods is to provide authorities having jurisdiction a means to evaluate the fire performance of HVAC duct systemsto enable their application and use.1.2 These test methods evaluate the fire performance of HVAC ducts, including b

10、oth supply (pressurized: Condition A Horizontal and Condition B Vertical) and return (exhaust: Condition C Horizontal and Condition D Vertical).1.3 These test methods evaluate the ability of a HVAC duct system to resist the spread of fire from one compartment to othercompartments separated by a fire

11、 resistance rated construction when the HVAC duct system is exposed to fire under one or moreof the following conditions:1.3.1 Condition AFire exposure from the outside of the horizontal HVAC duct system without openings,1.3.2 Condition BFire exposure from the outside of the vertical HVAC duct syste

12、m without openings,1.3.3 Condition CFire exposure from the outside with hot gases entering the inside of the horizontal HVAC duct system withunprotected openings, andNOTE 3Unprotected openings are openings that are not protected by fire dampers.1.3.4 Condition DFire exposure from the outside with ho

13、t gases entering the inside of the vertical HVAC duct system withunprotected openings.1.4 These test methods provide a means for determining the fire-resistance of vertical and horizontal HVAC duct systems, whensubjected to the standard time-temperature curve of Test Methods E119.1 These test method

14、s are under the jurisdiction of ASTM Committee E05 on Fire Standards and are the direct responsibility of Subcommittee E05.11 on Fire Resistance.Current edition approved Oct. 1, 2015July 1, 2017. Published November 2015August 2017. Originally approved in 2011. Last previous edition approved in 2015

15、asE2816-15.-15a. DOI: 10.1520/E2816-15A.10.1520/E2816-17.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes

16、 accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr H

17、arbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States11.4.1 Condition AThese test methods provide a means for evaluating a horizontal HVAC duct system, without openingsexposed to fire, passing through a vertical fire-separating element.1.4.2 Condition BThese test methods provide

18、a means for evaluating a vertical HVAC duct system, without openings exposedto fire and outfitted with a horizontal connection, passing through a horizontal fire-separating element.1.4.3 Condition CThese test methods provide a means for evaluating a horizontal HVAC duct system, with unprotectedopeni

19、ngs exposed to fire, passing through a vertical fire-separating element.1.4.4 Condition DThese test methods provide a means for evaluating a vertical HVAC duct system with a horizontalconnection, and with unprotected openings exposed to fire, passing through a horizontal fire-separating element.1.5

20、These test methods prescribe a standardized fire exposure for comparing the test results of the fire resistive materials andHVAC duct systems. The results of these tests are one factor in assessing predicted fire performance of HVAC duct systems. Usingthese test results to predict the performance of

21、 actual HVAC duct systems requires the evaluation of test conditions.1.6 The values stated in inch-pound units are to be regarded as the standard. The SI values given in parentheses are forinformation only, unless the SI units are used consistently to perform all of the test methods referenced herei

22、n. In this case, theSI units will be regarded as the standard and will be used in Section 17, Report.1.7 The text of these test methods references notes and footnotes which provide explanatory material and (excluding those intables and figures) shall not be considered as requirements of the fire-tes

23、t-response standard.1.8 This document specifically excludes evaluating ducts that carry combustibles, flammable vapors, combustible gases, andcommercial kitchen ventilation systems commonly called grease ducts or hazardous exhaust ducts, which are tested in compliancewith Test Methods E2336.1.9 This

24、 standard is used to measure and describe the response of materials, products, or assemblies to heat and flame undercontrolled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials,products, or assemblies under actual fire condit

25、ions.1.10 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatorylimitations prior to use.1.11 Fire t

26、esting is inherently hazardous.Adequate safeguards for personnel and property shall be employed in conducting thesetests.1.12 This international standard was developed in accordance with internationally recognized principles on standardizationestablished in the Decision on Principles for the Develop

27、ment of International Standards, Guides and Recommendations issuedby the World Trade Organization Technical Barriers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM Standards:2C411 Test Method for Hot-Surface Performance of High-Temperature Thermal InsulationC518 Test Method for Steady-Stat

28、e Thermal Transmission Properties by Means of the Heat Flow Meter ApparatusE84 Test Method for Surface Burning Characteristics of Building MaterialsE119 Test Methods for Fire Tests of Building Construction and MaterialsE136 Test Method for Behavior of Materials in a Vertical Tube Furnace at 750CE176

29、 Terminology of Fire StandardsE631 Terminology of Building ConstructionsE814 Test Method for Fire Tests of Penetration Firestop SystemsE2226 Practice for Application of Hose StreamE2307 Test Method for Determining Fire Resistance of Perimeter Fire Barriers Using Intermediate-Scale, Multi-story TestA

30、pparatusE2336 Test Methods for Fire Resistive Grease Duct Enclosure Systems2.2 Other Standards:UL 385 Standard for Play Pipes for Water Supply Testing in Fire-Protection Service3ISO 6944:1985 Fire Resistance Tests Ventilation Ducts 4ISO 6944-1:2008 Fire Containment Elements of Building Construction

31、Part 1: Ventilation ducts4SMACNA HVAC Duct Construction Standards52 For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standards Document Summary page on the ASTM web

32、site.3 Available from Underwriters Laboratories (UL), 2600 N.W. Lake Rd., Camas, WA 98607-8542, http:/.4 Available from International Organization for Standardization (ISO), ISO Central Secretariat, BIBC II, Chemin de Blandonnet 8, CP 401, 1214 Vernier, Geneva,Switzerland, http:/www.iso.org.5 Availa

33、ble from Sheet Metal and Air Conditioning Contractors National Association, 4201 Lafayette Center Drive Chantilly, Virginia 20151-1219, www.smacna.org.E2816 172DW/144 Specification for Sheet Metal Ductwork63. Terminology3.1 For definitions of terms used in these test methods and associated with fire

34、 issues, refer to the definitions contained inTerminology E176.3.2 For definitions of terms used in these test methods and associated with building issues, refer to the definitions contained inTerminology E631.3.3 When there is a conflict between Terminology E176 and Terminology E631 definitions, Te

35、rminology E176 definitions shallapply.3.4 Definitions of Terms Specific to This Standard:3.4.1 fire resistive material, nthe product applied to or a part of the HVAC duct to provide fire resistance.3.4.2 fire-separating element, nfloors, walls, and partitions having a period of fire resistance deter

36、mined in accordance withfire resistance test methods such as Test Methods E119.3.4.3 fire side, adjthe surface of the test assembly or test specimen exposed to the heat or flame, or both, of the test apparatus.3.4.4 integrity, nthe absence of cracks, holes or openings that appear outside the furnace

37、 on the fire-resistive material orfirestop, or both, or through which flames or hot gases pass as determined by the cotton pad test.3.4.5 orifice, nthe continuous hollow area or opening within the HVAC duct.3.4.6 stability, nthe ability of the HVAC duct, support and fastening system to fulfill their

38、 intended function.3.4.7 supporting construction, nthe arrangement of building sections forming the fire-separating elements into which theHVAC duct system is installed.3.4.8 support system, nthe vertical or horizontal devices used to sustain the HVAC duct and its fire-resistive materials andtheir f

39、astening means.3.4.9 test assembly, nthe complete construction composed of a test specimen(s) together with its supporting construction.3.4.10 test specimen, na material, product, or assemblage of a specific design, composition, density, and dimension, forexample, a HVAC duct protected with a fire-r

40、esistive material(s) that is secured by fastening system, which is suspended by asupport system, and protected by a firestop(s).3.4.10.1 DiscussionThe fire-resistive material or the HVAC duct system are examples of test specimens.3.4.11 unexposed side, nthe surface not directly exposed to the heat o

41、r flame, or both, of the test apparatus.3.4.12 unexposed surface thermocouple, ntemperature-measuring device placed on the unexposed surface.3.4.13 HVAC duct, na tube or conduit utilized for conveying air without combustible materials, flammable vapors, andcombustible gases.3.4.14 HVAC duct system,

42、nconsists of the HVAC duct, a fire-resistive material(s), a support system, the through-penetrationfirestop(s) and fastening system(s).4. Summary of Test Method4.1 Representative test specimens of the fire-resistive material or the HVAC duct system are subjected to the selected tests forthe purposes

43、 of assisting the authority having jurisdiction in qualifying an HVAC duct system to a an explicit set of theirrequirements. These test methods describe the following test sequence and procedures:4.1.1 A combustion characteristics of building materials test, Test Method E136, demonstrates the measur

44、e of fire-resistivematerials combustibility at a standardized temperature and duration.4.1.2 A durability test intended to simulate the effects of long-term exposure of typical in-service conditions, only when theservice temperature exceeds 125F, on the thermal transmission qualities of the fire-res

45、istive materials when subjected to amodified version of Test Method C518.NOTE 4The service temperature refers to the temperature inside the HVAC duct system or the ambient temperature surrounding the HVAC ductsystem.4.1.3 A fire-engulfment test uses a standardized fire exposure to simulate a fire oc

46、curring on the outside of the HVAC ductsystem in Conditions A and B, or a fire occurring on the inside and outside of the HVAC duct system in Conditions C and D, anddemonstrates the ability of the HVAC duct system to remain intact without a through opening appearing in supporting construction6 Avail

47、able from BESA, Building Engineering Services Association, .E2816 173or the HVAC duct system outside the furnace or raising the temperature on its unexposed surface above the limitations of thesetest methods or conveying hot gases into other compartments. The fire-engulfment test also tests the fast

48、ening methods used tosecure the fire-resistive material to the HVAC duct and the support system. The fire-engulfment test also provides a means to testa through-penetration firestop to determine its compatibility with the HVAC duct when mounted in a horizontal or verticalfire-separating element. A h

49、ose stream test is also performed on the test assembly in accordance with the provisions in PracticeE2226.4.1.4 Surface burning test, Test Method E84, provides a means to evaluate the flame spread and smoke developed of thefire-resistive material.4.1.5 A hot-surface performance test, Test Method C411, provides a means of evaluating the coverings and linings ability toresist flaming, glowing, smoldering or smoking while in service.5. Significance and Use5.1 These test methods are intended to evaluate