1、Designation: E2816 18 An American National StandardStandard Test Methods forFire Resistive Metallic HVAC Duct Systems1This standard is issued under the fixed designation E2816; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the ye
2、ar of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.INTRODUCTIONHeating, Ventilation, Air Conditioning (HVAC) duct systems may be subjected to fire- exposureconditions. ISO 694
3、4 is a standard test method used to evaluate ventilation ducts. However, ISO 6944does not address all of the fire resistive attributes deemed necessary by some authorities havingjurisdiction, for example, (1) the fire-resistive, combustibility, flame spread and smoke generation, anddurability proper
4、ties of the fire-resistive materials protecting the HVAC duct, (2) the transition fromthe horizontal to a vertical HVAC duct, (3) the attachment of the HVAC ducts supports to thefire-separating elements, (4) the termination of an HVAC duct system and the protection of its ends,(5) the effects of rap
5、id cooling and erosion upon the HVAC duct system, (6) the use of fire dampersand (7) the effect of the HVAC duct system on its supporting construction. Many types of fire-resistivematerials are used to protect HVAC ducts. These fire-resistive materials are either applied to HVACducts in the field or
6、 are fabricated as an integral part of the HVAC duct system when shipped from thefactory. Evaluating fire-resistive materials used to protect a HVAC duct from fire is an aid forpredicting their fire performance and helps to establish uniformity in requirements of variousauthorities. To do this it is
7、 necessary that the fire-resistance properties of HVAC ducts protected withfire-resistive materials be measured and specified according to a common standard expressed in termsthat are applicable alike to a wide variety of materials, situations, and conditions of exposure.1. Scope*NOTE 1Use of the st
8、andard designation ISO 6944 refers to both ISO6944:1985 and ISO 6944-1:2008.1.1 These test methods evaluate the fire-resistive materialsand the HVAC duct systems surface burning characteristics,non-combustibility, fire resistance, durability, and fire-engulfment with horizontal and vertical through-
9、penetrationfirestops.NOTE 2The intent of these test methods is to provide authoritieshaving jurisdiction a means to evaluate the fire performance of HVACduct systems to enable their application and use.1.2 These test methods evaluate the fire performance ofHVAC ducts, including both supply (pressuri
10、zed: Condition A Horizontal and Condition B Vertical) and return (exhaust:Condition C Horizontal and Condition D Vertical).1.3 These test methods evaluate the ability of a HVAC ductsystem to resist the spread of fire from one compartment toother compartments separated by a fire resistance rated con-
11、struction when the HVAC duct system is exposed to fire underone or more of the following conditions:1.3.1 Condition AFire exposure from the outside of thehorizontal HVAC duct system without openings,1.3.2 Condition BFire exposure from the outside of thevertical HVAC duct system without openings,1.3.
12、3 Condition CFire exposure from the outside with hotgases entering the inside of the horizontal HVAC duct systemwith unprotected openings, andNOTE 3Unprotected openings are openings that are not protected byfire dampers.1.3.4 Condition DFire exposure from the outside with hotgases entering the insid
13、e of the vertical HVAC duct systemwith unprotected openings.1.4 These test methods provide a means for determining thefire-resistance of vertical and horizontal HVAC duct systems,when subjected to the standard time-temperature curve of TestMethods E119.1.4.1 Condition AThese test methods provide a m
14、eans forevaluating a horizontal HVAC duct system, without openingsexposed to fire, passing through a vertical fire-separatingelement.1.4.2 Condition BThese test methods provide a means forevaluating a vertical HVAC duct system, without openings1These test methods are under the jurisdiction of ASTM C
15、ommittee E05 on FireStandards and are the direct responsibility of Subcommittee E05.11 on FireResistance.Current edition approved Feb. 1, 2018. Published March 2018. Originallyapproved in 2011. Last previous edition approved in 2017 as E2816-17. DOI:10.1520/E2816-18.*A Summary of Changes section app
16、ears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Princi
17、ples for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.1exposed to fire and outfitted with a horizontal connection,passing through a horizontal fire-separating element.1.4.3 Condition CThese te
18、st methods provide a means forevaluating a horizontal HVAC duct system, with unprotectedopenings exposed to fire, passing through a vertical fire-separating element.1.4.4 Condition DThese test methods provide a means forevaluating a vertical HVAC duct system with a horizontalconnection, and with unp
19、rotected openings exposed to fire,passing through a horizontal fire-separating element.1.5 These test methods prescribe a standardized fire expo-sure for comparing the test results of the fire resistive materialsand HVAC duct systems. The results of these tests are onefactor in assessing predicted f
20、ire performance of HVAC ductsystems. Using these test results to predict the performance ofactual HVAC duct systems requires the evaluation of testconditions.1.6 The values stated in inch-pound units are to be regardedas the standard. The SI values given in parentheses are forinformation only, unles
21、s the SI units are used consistently toperform all of the test methods referenced herein. In this case,the SI units will be regarded as the standard and will be usedin Section 17, Report.1.7 The text of these test methods references notes andfootnotes which provide explanatory material and (excludin
22、gthose in tables and figures) shall not be considered as require-ments of the fire-test-response standard.1.8 This document specifically excludes evaluating ductsthat carry combustibles, flammable vapors, combustible gases,and commercial kitchen ventilation systems commonly calledgrease ducts or haz
23、ardous exhaust ducts, which are tested incompliance with Test Methods E2336.1.9 This standard is used to measure and describe theresponse of materials, products, or assemblies to heat and flameunder controlled conditions, but does not by itself incorporateall factors required for fire hazard or fire
24、 risk assessment of thematerials, products, or assemblies under actual fire conditions.1.10 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety, health, and environ
25、mental practices and deter-mine the applicability of regulatory limitations prior to use.1.11 Fire testing is inherently hazardous. Adequate safe-guards for personnel and property shall be employed inconducting these tests.1.12 This international standard was developed in accor-dance with internatio
26、nally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM Standards:2C411 Test
27、Method for Hot-Surface Performance of High-Temperature Thermal InsulationC518 Test Method for Steady-State Thermal TransmissionProperties by Means of the Heat Flow Meter ApparatusE84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE119 Test Methods for Fire Tests of Building Cons
28、tructionand MaterialsE136 Test Method for Behavior of Materials in a VerticalTube Furnace at 750CE176 Terminology of Fire StandardsE631 Terminology of Building ConstructionsE814 Test Method for Fire Tests of Penetration FirestopSystemsE2226 Practice for Application of Hose StreamE2307 Test Method fo
29、r Determining Fire Resistance ofPerimeter Fire Barriers Using Intermediate-Scale, Multi-story Test ApparatusE2336 Test Methods for Fire Resistive Grease Duct Enclo-sure Systems2.2 Other Standards:UL 385 Standard for Play Pipes for Water Supply Testing inFire-Protection Service3ISO 6944:1985 Fire Res
30、istance Tests Ventilation Ducts4ISO 6944-1:2008 Fire Containment Elements of BuildingConstruction Part 1: Ventilation ducts4SMACNA HVAC Duct Construction Standards5DW/144 Specification for Sheet Metal Ductwork63. Terminology3.1 For definitions of terms used in these test methods andassociated with f
31、ire issues, refer to the definitions contained inTerminology E176.3.2 For definitions of terms used in these test methods andassociated with building issues, refer to the definitions con-tained in Terminology E631.3.3 When there is a conflict between Terminology E176 andTerminology E631 definitions,
32、 Terminology E176 definitionsshall apply.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from Unde
33、rwriters Laboratories (UL), 2600 N.W. Lake Rd., Camas,WA 98607-8542, http:/.4Available from International Organization for Standardization (ISO), ISOCentral Secretariat, BIBC II, Chemin de Blandonnet 8, CP 401, 1214 Vernier,Geneva, Switzerland, http:/www.iso.org.5Available from Sheet Metal and Air C
34、onditioning Contractors NationalAssociation, 4201 Lafayette Center Drive Chantilly, Virginia 20151-1219, www.s-macna.org.6Available from BESA, Building Engineering Services Association, www.besa-.E2816 1823.4 Definitions of Terms Specific to This Standard:3.4.1 fire resistive material, nthe product
35、applied to or apart of the HVAC duct to provide fire resistance.3.4.2 fire-separating element, nfloors, walls, and parti-tions having a period of fire resistance determined in accor-dance with fire resistance test methods such as Test MethodsE119.3.4.3 fire side, adjthe surface of the test assembly
36、or testspecimen exposed to the heat or flame, or both, of the testapparatus.3.4.4 integrity, nthe absence of cracks, holes or openingsthat appear outside the furnace on the fire-resistive material orfirestop, or both, or through which flames or hot gases pass asdetermined by the cotton pad test.3.4.
37、5 orifice, nthe continuous hollow area or openingwithin the HVAC duct.3.4.6 stability, nthe ability of the HVAC duct, support andfastening system to fulfill their intended function.3.4.7 supporting construction, nthe arrangement of build-ing sections forming the fire-separating elements into whichth
38、e HVAC duct system is installed.3.4.8 support system, nthe vertical or horizontal devicesused to sustain the HVAC duct and its fire-resistive materialsand their fastening means.3.4.9 test assembly, nthe complete construction composedof a test specimen(s) together with its supporting construction.3.4
39、.10 test specimen, na material, product, or assemblageof a specific design, composition, density, and dimension, forexample, a HVAC duct protected with a fire-resistive materi-al(s) that is secured by fastening system, which is suspended bya support system, and protected by a firestop(s).3.4.10.1 Di
40、scussionThe fire-resistive material or theHVAC duct system are examples of test specimens.3.4.11 unexposed side, nthe surface not directly exposedto the heat or flame, or both, of the test apparatus.3.4.12 unexposed surface thermocouple, ntemperature-measuring device placed on the unexposed surface.
41、3.4.13 HVAC duct, na tube or conduit utilized for convey-ing air without combustible materials, flammable vapors, andcombustible gases.3.4.14 HVAC duct system, nconsists of the HVAC duct, afire-resistive material(s), a support system, the through-penetration firestop(s) and fastening system(s).4. Su
42、mmary of Test Method4.1 Representative test specimens of the fire-resistive mate-rial or the HVAC duct system are subjected to the selected testsfor the purposes of assisting the authority having jurisdiction inqualifying an HVAC duct system to a an explicit set of theirrequirements. These test meth
43、ods describe the following testsequence and procedures:4.1.1 A combustion characteristics of building materialstest, Test Method E136, demonstrates the measure of fire-resistive materials combustibility at a standardized tempera-ture and duration.4.1.2 A durability test intended to simulate the effe
44、cts oflong-term exposure of typical in-service conditions, only whenthe service temperature exceeds 125F, on the thermal trans-mission qualities of the fire-resistive materials when subjectedto a modified version of Test Method C518.NOTE 4The service temperature refers to the temperature inside theH
45、VAC duct system or the ambient temperature surrounding the HVACduct system.4.1.3 A fire-engulfment test uses a standardized fire expo-sure to simulate a fire occurring on the outside of the HVACduct system in Conditions A and B, or a fire occurring on theinside and outside of the HVAC duct system in
46、 Conditions Cand D, and demonstrates the ability of the HVAC duct systemto remain intact without a through opening appearing insupporting construction or the HVAC duct system outside thefurnace or raising the temperature on its unexposed surfaceabove the limitations of these test methods or conveyin
47、g hotgases into other compartments. The fire-engulfment test alsotests the fastening methods used to secure the fire-resistivematerial to the HVAC duct and the support system. Thefire-engulfment test also provides a means to test a through-penetration firestop to determine its compatibility with the
48、HVAC duct when mounted in a horizontal or vertical fire-separating element. A hose stream test is also performed on thetest assembly in accordance with the provisions in PracticeE2226.4.1.4 Surface burning test, Test Method E84, provides ameans to evaluate the flame spread and smoke developed of the
49、fire-resistive material.4.1.5 A hot-surface performance test, Test Method C411,provides a means of evaluating the coverings and liningsability to resist flaming, glowing, smoldering or smoking whilein service.5. Significance and Use5.1 These test methods are intended to evaluate the abilityof the HVAC duct system and its supporting construction to dothe following:5.1.1 Resist the effects of a standardized fire exposure, and5.1.2 Retain its integrity.5.2 These test methods provide for the following measure-ments