ASTM E662-2013 0053 Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials《固体材料产生的烟雾比光密度的标准试验方法》.pdf

上传人:visitstep340 文档编号:533254 上传时间:2018-12-06 格式:PDF 页数:24 大小:466.46KB
下载 相关 举报
ASTM E662-2013 0053 Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials《固体材料产生的烟雾比光密度的标准试验方法》.pdf_第1页
第1页 / 共24页
ASTM E662-2013 0053 Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials《固体材料产生的烟雾比光密度的标准试验方法》.pdf_第2页
第2页 / 共24页
ASTM E662-2013 0053 Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials《固体材料产生的烟雾比光密度的标准试验方法》.pdf_第3页
第3页 / 共24页
ASTM E662-2013 0053 Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials《固体材料产生的烟雾比光密度的标准试验方法》.pdf_第4页
第4页 / 共24页
ASTM E662-2013 0053 Standard Test Method for Specific Optical Density of Smoke Generated by Solid Materials《固体材料产生的烟雾比光密度的标准试验方法》.pdf_第5页
第5页 / 共24页
亲,该文档总共24页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

1、Designation: E662 13 An American National StandardStandard Test Method forSpecific Optical Density of Smoke Generated by SolidMaterials1This standard is issued under the fixed designation E662; the number immediately following the designation indicates the year oforiginal adoption or, in the case of

2、 revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This fire-test

3、-response standard covers determination ofthe specific optical density of smoke generated by solidmaterials and assemblies mounted in the vertical position inthicknesses up to and including 1 in. (25.4 mm).1.2 Measurement is made of the attenuation of a light beamby smoke (suspended solid or liquid

4、particles) accumulatingwithin a closed chamber due to nonflaming pyrolytic decom-position and flaming combustion.1.3 Results are expressed in terms of specific optical densitywhich is derived from a geometrical factor and the measuredoptical density, a measurement characteristic of the concentra-tio

5、n of smoke.1.4 This test method is intended for use in research anddevelopment and not as a basis for ratings for regulatorypurposes.1.5 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for

6、information onlyand are not considered standard.1.6 This standard measures and describes the response ofmaterials, products, or assemblies to heat and flame undercontrolled conditions, but does not by itself incorporate allfactors required for fire hazard or fire risk assessment of thematerials, pro

7、ducts or assemblies under actual fire conditions.1.7 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of re

8、gulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D2843 Test Method for Density of Smoke from the Burningor Decomposition of PlasticsE176 Terminology of Fire Standards3. Terminology3.1 DefinitionsFor definitions of terms found in this testmethod refer to Terminology E176.4

9、. Summary of Test Method4.1 This test method employs an electrically heated radiant-energy source mounted within an insulated ceramic tube andpositioned so as to produce an irradiance level of 2.2 Btu/sft2(2.5 W/cm2) averaged over the central 1.5-in. (38.1-mm)diameter area of a vertically mounted sp

10、ecimen facing theradiant heater. The nominal 3 by 3-in. (76.2 by 76.2-mm)specimen is mounted within a holder which exposes an areameasuring 2916 by 2916 in. (65.1 by 65.1 mm). The holder isable to accommodate specimens up to 1 in. (25.4 mm) thick.This exposure provides the nonflaming condition of th

11、e test.4.2 For the flaming condition, a six-tube burner is used toapply a row of equidistant flamelets across the lower edge ofthe exposed specimen area and into the specimen holdertrough. This application of flame in addition to the specifiedirradiance level from the heating element constitutes the

12、flaming combustion exposure.1This test method is under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsibility of Subcommittee E05.21 on Smoke andCombustion Products.Current edition approved Jan. 1, 2013. Published January 2013. Originallyapproved in 1979. Last previ

13、ous edition approved in 2012 as E662 12a. DOI:10.1520/E0662-13.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM websit

14、e.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States14.3 The test specimens are exposed to the flaming andnonflaming conditions within a closed chamber. A photometricsystem with a vertical light path is used to measure the varyinglight t

15、ransmission as smoke accumulates. The light transmit-tance measurements are used to calculate specific opticaldensity of the smoke generated during the time period to reachthe maximum value.35. Significance and Use5.1 This test method provides a means for determining thespecific optical density of t

16、he smoke generated by specimens ofmaterials and assemblies under the specified exposure condi-tions. Values determined by this test are specific to thespecimen or assembly in the form and thickness tested and arenot to be considered inherent fundamental properties of thematerial tested. Thus, it is

17、likely that closely repeatable orreproducible experimental results are not to be expected fromtests of a given material when specimen thickness, density, orother variables are involved.5.2 The photometric scale used to measure smoke by thistest method is similar to the optical density scale for huma

18、nvision. However, physiological aspects associated with visionare not measured by this test method. Correlation with mea-surements by other test methods has not been established.45.3 At the present time no basis is provided for predictingthe density of smoke generated by the materials upon exposuret

19、o heat and flame under other fire conditions.5.4 The test method is of a complex nature and the dataobtained are sensitive to variations which in other test methodsmight be considered to be insignificant (see Section 6). Aprecision statement based on the results of a roundrobin test bya prior draft

20、version of this test method is given in 14.15.5 In this procedure, the specimens are subjected to one ormore specific sets of laboratory test conditions. If different testconditions are substituted or the end-use conditions arechanged, it is not always possible by or from this test methodto predict

21、changes in the fire-test-response characteristicsmeasured. Therefore, the results are valid only for the fire testexposure conditions described in this procedure.6. Limitations6.1 If during the test of one or more of the three replicatesamples there occurs such unusual behavior as (1) the speci-men

22、falling out of the holder, (2) melted material overflowingthe sample holder trough, (3) self-ignition in the pyrolysismode, (4) extinguishment of the flame tiplets (even for a shortperiod of time), or (5) a specimen being displaced from thezone of controlled irradiance, then an additional three samp

23、lesof the identical preconditioned materials shall be tested in thetest mode in which the unusual behavior occurred. Dataobtained from the improper tests noted above shall not beincorporated in the averaged data but the occurrence shall bereported. The test method is not suitable if more than three

24、ofthe six replicates tested show these characteristics.6.2 The test method has proven sensitive to small variationsin sample geometry, surface orientation, thickness (eitheroverall or individual layer), weight, and composition. It is,therefore, critical that the replicate samples be cut, sawed, orbl

25、anked to identical sample areas, 3 by 3, +0, 0.03 in. (76.2by 76.2, +0, 0.8 mm), and that records be kept of therespective weights with the individual test data. It is feasiblethat evaluation of the obtained data together with the individualweights will assist in assessing the reasons for any observ

26、edvariability in measurements. Preselection of samples withidentical thickness or weight, or both, are potential methods toreduce the variability but are likely to not be truly indicative ofthe actual variability to be expected from the material asnormally supplied.6.3 The results of the test apply

27、only to the thickness of thespecimen as tested. There is no common mathematical formulato calculate the specific optical density of one thickness of amaterial when the specific optical density of another thicknessof the same material is known.6.4 The test method is sensitive to small variations of t

28、heposition of the specimen and radiometer relative to the radiantheat source.6.5 It is critical to clean the test chamber, and to removeaccumulated residues from the walls when changing from onetest material to another, to ensure that chemical or physicalrecombination with the effluents or residues

29、produced does notaffect the data obtained. Even when testing the same material,excessive accumulations of residue shall not be permitted tobuild up since ruggedness tests have indicated that suchaccumulations serve as additional insulators tending to reducenormally expected condensation of the aeros

30、ol, thereby raisingthe measured specific optical density.6.6 With resilient samples, take extreme care to ensure thateach replicate sample in its aluminum foil wrapper is installedso that each protrudes identically through the front sampleholder opening. Unequal protrusion will subject the samples t

31、odifferent effective irradiances and to slightly different ignitionexposures. Excessive protrusion of specimens has the potentialto cause drips or for the specimen to sag onto the burner,clogging the flame jets and thereby invalidating the test.6.7 The measurements obtained have also proven sensitiv

32、eto small differences in conditioning (see Section 9). Manymaterials such as carpeting and thick sections of wood,plastics, or plywood require long periods to attain equilibrium(constant weight) even in a forced-draft humidification cham-ber.7. Apparatus7.1 Fig. 1 shows examples of the test apparatu

33、s, with adetailed description contained in the remainder of Section 7and in Annex A2. The apparatus shall include the following:3Additional parameters, such as the maximum rate of smoke accumulation, timeto a fixed optical density level, or a smoke obscuration index provide potentiallyuseful informa

34、tion. See Appendix X1.4Other test methods for measuring smoke available at the time of the publica-tions referenced have been reviewed and summarized in “The Control of Smoke inBuilding FiresAState of theArt Review.” Materials Research and Standards,Vol42, April 1971, pp. 1623 and “A Report on Smoke

35、 Test Methods,” ASTMStandardization News, August 1976, pp. 1826.E662 1327.1.1 Test ChamberAs shown in Fig. 1, the test chambershall be fabricated from laminated panels5to provide insidedimensions of 36 by 24 by 36 618 in. (914 by 610 by 914 63 mm) for width, depth, and height, respectively. The inte

36、riorsurfaces shall consist of porcelain enameled metal, or othercoated metal, which shall be resistant to chemical attack andcorrosion, and suitable for periodic cleaning. Sealed windowsshall be provided to accommodate a vertical photometricsystem. All other chamber penetrations shall be sealed. Whe

37、nall openings are closed, the chamber shall be capable of5Commercially available panels of porcelain-enameled steel (interior surface)permanently laminated to an asbestos-magnesia core and backed with galvanizedsteel (exterior surface), total thickness316 in. (9.6 mm), have been found suitable.APhot

38、omultiplier tube housing NFlowmeter shutoff valvesBChamber OSample mover knobCBlow-out panel (in floor of chamber) PLight source switchDHinged door with window QLight source voltage jacksEExhaust vent control RLine switchFRadiometer output jacks SBase cabinetGTemperature (wall) indicator TIndicating

39、 lampsHAutotransformer UMicrophotometer (photomultiplier)IFurnace switch VOptical system rodsJVoltmeter (furnace) WOptical system floor windowKFuse holder (furnace) XExhaust vent damperLRadiometer air flowmeter YInlet vent damperMGas and air (burner) flowmeter ZAccess portsFIG. 1 Smoke Density Chamb

40、er AssemblyE662 133developing and maintaining positive pressure during testperiods, in accordance with 11.11.7.1.1.1 If the interior wall surfaces become corroded or thecoating starts to peel off, users shall repair the damaged areausing any suitable coating material, installed to the coatingmanufac

41、turers instructions.NOTE 1Some high temperature paints have been found satisfactoryfor this purpose.7.1.1.2 Fit the chamber with a safety blow-out panel,consisting of a sheet of aluminum foil of thickness not greaterthan 1.63 103in. (0.04 mm) and having a minimum area of125 in.2(80 600 mm2), fastene

42、d in such a way as to provide anairtight seal.7.1.2 Radiant Heat FurnaceAs shown in Fig. 2,anelectric furnace with a 3-in. (76.2-mm) diameter opening shallbe used to provide a constant irradiance on the specimensurface. The furnace shall be located along the centerlineequidistant between the front a

43、nd back of the chamber, with theopening facing toward and about 12 in. (305 mm) from theright wall. The centerline of the furnace shall be about 734 in.(195 mm) above the chamber floor. The furnace control systemshall maintain the required irradiance level, under steady-stateconditions with the cham

44、ber door closed, of 2.20 6 0.04Btu/ft2s (2.50 6 0.05 W/cm2) for 20 min. The control systemshall consist of an autotransformer or alternative controldevice, and a voltmeter or other means for monitoring theelectrical input. Where line voltage fluctuations exceed 62.5 ,a constant voltage transformer i

45、s required to maintain theprescribed irradiance level.7.1.3 Specimen HolderSpecimen holders shall conform inshape and dimension to that shown in Fig. 3 and be fabricatedto expose a 2916 by 2916-in. (65.1 by 65.1-mm) specimen area.Also shown in Fig. 3 are the spring and rods for retaining thespecimen

46、 within the holders.AStainless steel tube GStainless steel spacersBFront insulating ring HStainless steel reflectors (3)CCeramic tube JCenter insulating diskDHeater/plate 525 W KInsulating spacer ringEStainless steel mounting screw LRear insulating diskFInsulating gasket MSheet metal screw (2)PHeate

47、r leads/porcelain beadsFIG. 2 Furnace SectionE662 1347.1.4 Framework for Support of Furnace and SpecimenHolderThe furnace and specimen supporting frameworkshall be constructed essentially in accordance with Fig. 4.7.1.5 Photometric SystemThe photometric system shallconsist of a light source and phot

48、odetector, oriented verticallyto reduce measurement variations resulting from stratificationof the smoke generated by materials under test. The systemshall be as shown in Figs. 5 and 6 and include the following:7.1.5.1 The light source shall be an incandescent lampoperated at a fixed voltage in a ci

49、rcuit powered by a constant-voltage transformer. The light source shall be mounted in asealed and light-tight box. This box shall contain the necessaryoptics to provide a collimated light beam passing verticallythrough the chamber. The light source shall be maintained at anoperating voltage required to provide a brightness temperatureof 2200 6 100K.FIG. 3 Details of Specimen Holder and Pilot BurnerE662 1357.1.5.2 The photodetector shall be a photomultiplier tube,with an S-4 spectral sensitivity response and a dar

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > ASTM

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1