1、Designation: F 1657 96 (Reapproved 2007)Standard Practice forEmergency Joining of Booms with IncompatibleConnectors1This standard is issued under the fixed designation F 1657; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the yea
2、r of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice provides a standard practice for the joiningof oil spill containment boom connectors in emergencie
3、s.1.2 The use of this connection method may adversely affectthe total tensile strength of the connected booms.1.3 These criteria are intended to define mating require-ments that will allow the emergency or occasional connectionof unlike connectors.1.4 This practice is not intended to replace Specifi
4、cationF 962.1.5 This practice does not address the compatibility of spillcontrol equipment with spill products. It is the users respon-sibility to ensure that any equipment selected is compatiblewith the anticipated spilled material.1.6 There is no guarantee that all of the connectors in usetoday ca
5、n accept the holes spaced as required without interfer-ing with existing bolt holes or other connector features.1.7 The values stated in SI units are to be regarded as thestandard. The values given in parentheses are for informationonly.1.8 This standard does not purport to address all of thesafety
6、concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. For a specificprecautionary statement, see 3.2.2. Referenced Documents2.1 AST
7、M Standards:2F 818 Terminology Relating to Spill Response BarriersF 962 Specification for Oil Spill Response Boom Connec-tion: Z-ConnectorF 1093 Test Methods for Tensile Strength Characteristics ofOil Spill Response BoomF 1523 Guide for Selection of Booms in Accordance WithWater Body Classifications
8、3. Significance and Use3.1 The use of this practice for the emergency joining ofbooms will not guarantee the effective performance of thejoined boom sections, since each boom design and the envi-ronmental conditions of each incident govern the overallperformance.3.2 Historically, different types of
9、end connectors have beenproduced. This practice addresses the operational need toconnect different types, during spill incidents. (WarningUseof this practice with similar or different sizes of boom maycause the transmission of unwanted loading such as, tensionloading and bending moments on certain b
10、oom parts resultingin possible premature failure of the containment system.)3.3 There are a wide range of boom connector configura-tions presently in use. These connectors were based upon someor all of the following design criteria:3.3.1 Connect and transfer tensile loads between boomsections,3.3.2
11、Minimize oil leakage between boom sections,3.3.3 Be easily connectable in the presence of dirt, oil or ice,or a combination thereof,3.3.4 Be quickly and easily connected and disconnected, inand out of the water,3.3.5 Maintain boom performance (freeboard, heave re-sponse, conformance, stability, and
12、so forth),3.3.6 Be unaffected by temperature extremes,3.3.7 Have no protruding parts that could snag, injure, orpuncture,3.3.8 Be light weight and buoyant,3.3.9 Be operatively symmetrical,3.3.10 Require no special tools for installation or removal,3.3.11 Require no loose parts for connection,3.3.12
13、Extend to the full height and draft of the boom,1This practice is under the jurisdiction of ASTM Committee F20 on HazardousSubstances and Oil Spill Response and is the direct responsibility of SubcommitteeF20.11 on Control.Current edition approved April 1, 2007. Published May 2007. Originallyapprove
14、d in 1996. Last previous edition approved in 2002 as F 1657 96 (2002).2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM
15、 website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.3.13 Resist distortion (that is, winding boom on a reel),and3.3.14 Be inherently safe to personnel.4. Design Criteria4.1 In order to comply with this practice for the emergen
16、cyjoining of boom with incompatible connectors, each boomconnector, regardless of design, will incorporate the require-ments described herein or use the adaption method in 5.3:4.1.1 A minimum of two holes sized to accommodate 13mm (12 in.) diameter 304 stainless steel bolts will be providedas shown
17、in Fig. 1. Using the boom design water line as areference point, the center of the first hole is to be 12 cm abovethe water line, the second hole will be 30 cm below the firsthole depending on the connector overall length. For largerconnectors additional holes will be placed at 30 cm incrementsfrom
18、the first two holes. Each hole is to be sealed to preventleakage when not in use.4.1.2 Use of this practice shall not significantly impact theoriginal design criteria in 3.4.4.1.3 Incorporation of this practice shall not reduce thetensile strength of the boom system below the values stated forthat c
19、lass of boom, (see Guide F 1523) when mated in itsnormal configuration.4.1.4 The manufacturer should establish the load carryingcapability of two of his connectors joined by this practice bytesting in accordance with Test Methods F 1093.5. Operational Consideration5.1 A suitable non-metallic gasket
20、sealing material may beinserted by the user between the surfaces to be joined. Thegasket material must be impervious to the products containedby the boom.5.2 The user must consider the transmission of tensileloading between the joined sections. This will include tensileloads on boom fabric, primary
21、and secondary tension members,FIG. 1 Side View of a Typical ConnectorF 1657 96 (2007)2and the orientation of the tension members (loads may be offsetat the joint depending on boom design).5.3 When the original connector design prevents the use ofthis practice, a suitable number of adapters should be
22、 providedto facilitate connection to this emergency joining practice.5.4 This practice will also allow for multiple boom connec-tions at one point.6. Keywords6.1 boom; boom connector; connector; incompatible boomconnector; oil spill responseASTM International takes no position respecting the validit
23、y of any patent rights asserted in connection with any item mentionedin this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the riskof infringement of such rights, are entirely their own responsibility.This standard is subject
24、 to revision at any time by the responsible technical committee and must be reviewed every five years andif not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standardsand should be addressed to ASTM International Headquarter
25、s. Your comments will receive careful consideration at a meeting of theresponsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you shouldmake your views known to the ASTM Committee on Standards, at the address shown below.This standard i
26、s copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the aboveaddress or at 610-832-9585 (phone), 610-832-9555 (fax), or serviceastm.org (e-mail); or through the ASTM website(www.astm.org).F 1657 96 (2007)3