ASTM F2487-2006(2012) Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Corrugated High Density Polyethylene Pipelines《已安装高密度聚乙烯波纹管道渗入和渗出验收测试用标准实施.pdf

上传人:wealthynice100 文档编号:538830 上传时间:2018-12-07 格式:PDF 页数:2 大小:58.70KB
下载 相关 举报
ASTM F2487-2006(2012) Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Corrugated High Density Polyethylene Pipelines《已安装高密度聚乙烯波纹管道渗入和渗出验收测试用标准实施.pdf_第1页
第1页 / 共2页
ASTM F2487-2006(2012) Standard Practice for Infiltration and Exfiltration Acceptance Testing of Installed Corrugated High Density Polyethylene Pipelines《已安装高密度聚乙烯波纹管道渗入和渗出验收测试用标准实施.pdf_第2页
第2页 / 共2页
亲,该文档总共2页,全部预览完了,如果喜欢就下载吧!
资源描述

1、Designation: F2487 06 (Reapproved 2012) An American National StandardStandard Practice forInfiltration and Exfiltration Acceptance Testing of InstalledCorrugated High Density Polyethylene Pipelines1,2This standard is issued under the fixed designation F2487; the number immediately following the desi

2、gnation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by

3、 agencies of the Department of Defense.1. Scope1.1 This practice covers procedures for testing installednon-perforated, gasketed corrugated high-density polyethylene(HDPE) pipelines using either water infiltration or exfiltrationacceptance limits to demonstrate the integrity via the level ofleakage

4、of the installed materials, construction procedures andinstallation qualityvia the level of leakage. Pipe to be testedunder this practice shall include corrugated HDPE drainagepipe meeting the requirements of AASHTO M 252, AASHTOM 294 and Specification F2306/F2306M.NOTE 1The performance criteria spe

5、cified in this standard may beused for other plastic pipe products. The engineer, however, must assess ifthe testing procedures are adequate for the particular material andinstallation being considered.NOTE 2The user of this practice is advised that test criteria presentedin this practice are simila

6、r to those in general use. Pipe, 600-mm (24-in.)diameter or larger, may be accepted by visual inspection when testing forinfiltration.1.2 The values stated in SI units are to be regarded as thestandard. The values in parentheses are mathematical conver-sions to inch-pounds, which are provided for in

7、formationalpurposes only and are not considered standard.1.3 This test method shall be performed on lines after allconnections and service laterals have been plugged and bracedadequately to withstand the test pressures. The time betweencompletion of the backfill operations and testing shall bespecif

8、ied by the approving authority.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitatio

9、ns prior to use. The testingrequired under this standard necessitates operating in confinedspaces. The user must insure that all OSHA and local safetycodes are duly observed.2. Referenced Documents2.1 ASTM Standards:3D3212 Specification for Joints for Drain and Sewer PlasticPipes Using Flexible Elas

10、tomeric SealsF412 Terminology Relating to Plastic Piping SystemsF2306/F2306M Specification for 12 to 60 in. 300 to 1500mm Annular Corrugated Profile-Wall Polyethylene (PE)Pipe and Fittings for Gravity-Flow Storm Sewer andSubsurface Drainage Applications2.2 AASHTO Standards2M 252 Standard Specificati

11、on for Corrugated PolyethyleneDrainage Pipe 75 to 250-mm (3 to 10-inch) DiameterM 294 Standard Specification for Corrugated PolyethyleneDrainage Pipe 300 to 1500-mm (12 to 60-inch) Diameter3. Terminology3.1 DefinitionsFor definitions of terms relating to plasticpipe, see Terminology F412.4. Summary

12、of Practice4.1 Determine the groundwater conditions surrounding thesection of pipeline to be tested and select the type of test to beconducted.4.2 For the infiltration test, the amount of water leaking intothe pipeline is measured, and the rate of infiltration is deter-mined. If the rate is less tha

13、n or equal to the allowable limit, thesection of pipe tested is acceptable.4.3 For the exfiltration test, the pipeline is filled with waterto the specified test head and the rate of water loss isdetermined. If the rate is less than or equal to the allowablelimit, the section of pipe tested is accept

14、able.1This practice is under the jurisdiction of ASTM Committee F17 on PlasticPiping Systems and is the direct responsibility of Subcommittee F17.20 on Joining.Current edition approved Aug. 1, 2012. Published October 2012. Originallyapproved in 2006. Last previous edition approved in 2006 as F248706

15、. DOI:10.1520/F2487-06R12.2Available from American Association of State Highway and TransportationOfficials (AASHTO), 444 N. Capitol St., NW, Suite 249, Washington, DC 20001,http:/www.transportation.org.3For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Ser

16、vice at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States15. Significance and Use5.1 This is not a rou

17、tine test. The values recorded areapplicable only to the pipe being tested and at the time oftesting.6. Preparation of the Pipeline6.1 The pipe shall be free of debris prior to testing.6.2 The manholes, the ends of the branches, laterals, wyesand stubs to be included in the test shall be plugged. Al

18、l plugsshall be secured to prevent leakage blowout due to testingpressure.WarningThe test places extremely high forces onplugs used for sealing the pipeline for pressure testing. Plugsmust be properly blocked and braced against movement beforethe test begins.All confined space procedures shall be ob

19、servedduring preparation and conducting of this test. Under nocircumstances shall any persons be permitted inside the man-hole during pressure testing.7. Procedure7.1 Infiltration Testing:7.1.1 Conduct testing from manhole to manhole. The lengthof pipeline tested shall not exceed 213 m (700 ft).7.1.

20、2 Stop all dewatering operations and allow the ground-water to return to its normal level. Infiltration testing shall notbe used unless the groundwater level is at least 0.6 m (2 ft)above the crown of the pipe for the entire length of the testsection.7.1.3 Plug all pipe outlets discharging into the

21、upstreammanhole.7.1.4 Measure the groundwater elevation and determine theaverage head over the test section.7.1.5 Measure infiltration leakage at the outlet of the testsection. Because leakage allowances are small, measurementsare best made by either timing the filling of a small containerof known v

22、olume, or by directing flow into a container for aspecified time and measuring the content, or by using smallweirs.7.1.6 If the measured rate of leakage is less than or equal tothe allowable leakage in accordance with 8.1, the section ofpipeline tested is acceptable.7.1.7 If the test section fails,

23、the line shall be repaired andretested in accordance with this practice.7.2 Exfiltration Testing:7.2.1 Conduct testing from manhole to manhole. The lengthof pipeline tested shall not exceed 213 m (700 ft).7.2.2 Determine the groundwater elevation at both ends ofthe test section. If the groundwater l

24、evel is less than 0.6 m (2ft) above the crown of the pipe measured from the highestelevation of the pipeline, the exfiltration test shall be used.7.2.3 Plug all pipe outlets discharging into the upstreammanhole and the test section outlet. Fill the pipeline with water.7.2.4 At the upstream manhole t

25、he test head shall beestablished as minimum of 0.6 m (2 ft) above the crown of thepipe, or at least 0.6 m (2 ft) above existing groundwater,whichever is higher.7.2.5 Measure the leakage loss over a timed test period. Theminimum test period shall be 15 min and the maximum shallnot exceed 24 h.7.2.6 I

26、f the measured rate of leakage is less than or equal tothe allowable leakage, in accordance with 8.1, the section ofpipeline tested is acceptable.7.2.7 If the test section fails, the line shall be repaired andretested in accordance with this practice. The groundwaterelevation shall be redetermined p

27、rior to a second test and thetest head adjusted, if necessary, in accordance with 7.2.4.8. Leakage Criteria8.1 Leakage criteria for infiltration and exfiltration testingshall be determined by the owner based on their applicationand design requirements.NOTE 3If the hydrostatic head is expected to exc

28、eed the maximumpressure capacity of the joint, as specified in Specification D3212, thedesign engineer should review field conditions to determine if a specialjoint design is required to maintain the long-term integrity of the system.NOTE 4The current Environmental Protection Agencys (EPA) maxi-mum

29、leakage allowance specified for infiltration and exfiltration accep-tance for sanitary pipelines is 18.5 L/(mm of internal diameter) (km ofpipeline) (24 h) 200 gal/in/mi/day.9. Keywords9.1 corrugated HDPE pipe; exfiltration; infiltration; leakagetestingASTM International takes no position respecting

30、 the validity of any patent rights asserted in connection with any item mentionedin this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the riskof infringement of such rights, are entirely their own responsibility.This standar

31、d is subject to revision at any time by the responsible technical committee and must be reviewed every five years andif not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standardsand should be addressed to ASTM International

32、 Headquarters. Your comments will receive careful consideration at a meeting of theresponsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you shouldmake your views known to the ASTM Committee on Standards, at the address shown below.Thi

33、s standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the aboveaddress or at 610-832-9585 (phone), 610-832-9555 (fax), or serviceastm.org (e-mail); or through the ASTM website(www.astm.org). Permission rights to photocopy the standard may also be secured from the ASTM website (www.astm.org/COPYRIGHT/).F2487 06 (2012)2

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > ASTM

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1