1、BS EN 1736:2008ICS 27.080;27.200NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBRITISH STANDARDRefrigerating systemsand heat pumps Flexible pipe elements,vibration isolators,expansion joints andnon-metallic tubes Requirements, designand installationLicensed Copy: Wang Bin, ISO
2、/EXCHANGE CHINA STANDARDS, 03/06/2009 08:04, Uncontrolled Copy, (c) BSIThis British Standardwas published under theauthority of the StandardsPolicy and StrategyCommittee on 28 February2009 BSI 2009ISBN 978 0 580 61493 4Amendments/corrigenda issued since publicationDate CommentsBS EN 1736:2008Nationa
3、l forewordThis British Standard is the UK implementation of EN 1736:2008. Itsupersedes BS EN 1736:2000 which is withdrawn.The UK participation in its preparation was entrusted to TechnicalCommittee RHE/18, Refrigeration safety.A list of organizations represented on this committee can be obtained onr
4、equest to its secretary.This publication does not purport to include all the necessary provisionsof a contract. Users are responsible for its correct application.Compliance with a British Standard cannot confer immunityfrom legal obligations.Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 03/
5、06/2009 08:04, Uncontrolled Copy, (c) BSIBS EN 1736:2008EUROPEAN STANDARDNORME EUROPENNEEUROPISCHE NORMEN 1736November 2008ICS 27.080; 27.200 Supersedes EN 1736:2000 English VersionRefrigerating systems and heat pumps - Flexible pipe elements,vibration isolators, expansion joints and non-metallic tu
6、bes -Requirements, design and installationSystmes de rfrigration et pompes chaleur - Elmentsflexibles de tuyauterie, isolateurs de vibration, joints dedilatation et tubes non mtalliques - Exigences, conceptionet installationKlteanlagen und Wrmepumpen - FlexibleRohrleitungsteile, Schwingungsabsorber,
7、 Kompensatorenund Nichtmetall-Schluche - Anforderungen, Konstruktionund EinbauThis European Standard was approved by CEN on 5 October 2008.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a nationa
8、l standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the CEN Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any o
9、ther language made by translationunder the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as theofficial versions.CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia,
10、 Finland,France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMIT EUROPEN DE NORMALISATIONEUROPISCHES K
11、OMITEE FR NORMUNGManagement Centre: rue de Stassart, 36 B-1050 Brussels 2008 CEN All rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 1736:2008: ELicensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 03/06/2009 08:04, Uncontrolled Copy, (c)
12、BSIBS EN 1736:2008EN 1736:2008 (E) 2 Contents Page Foreword3 Introduction .4 1 Scope 5 2 Normative references 5 3 Terms and definitions .5 4 Applications .7 5 Materials .10 6 Pressure and pulsation requirements .10 7 Permeability of non-metallic flexible tubes.11 8 Internal cleaness, internal humidi
13、ty and permeability of water vapour.13 9 End connections13 10 Pre-charged flexible pipe elements .13 11 Marking .13 12 Documentation.14 Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 03/06/2009 08:04, Uncontrolled Copy, (c) BSIBS EN 1736:2008EN 1736:2008 (E) 3 Foreword This document (EN 1736
14、:2008) has been prepared by Technical Committee CEN/TC 182 “Refrigerating systems, safety and environmental requirements”, the secretariat of which is held by DIN. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, a
15、t the latest by May 2009, and conflicting national standards shall be withdrawn at the latest by May 2009. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all
16、 such patent rights. This document supersedes EN 1736:2000. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
17、 France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 03/06/2009 08:04, Uncontroll
18、ed Copy, (c) BSIBS EN 1736:2008EN 1736:2008 (E) 4 Introduction The use of flexible pipe elements is required where impermissible stresses are to be eliminated from refrigerating circuits and pipe expansion or relative movements of components are to be absorbed. The use of flexible pipe elements shou
19、ld not be specified unless it is necessary in the design of refrigerant circuits. If necessary, they should be designed and installed in accordance with this standard. Flexible pipe elements are often the weakest part of a refrigerating system and the part most likely to suffer from fatigue or stres
20、s corrosion cracking. Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 03/06/2009 08:04, Uncontrolled Copy, (c) BSIBS EN 1736:2008EN 1736:2008 (E) 5 1 Scope This document describes requirements, design and installation of flexible pipe elements (e. g. metallic flexible pipe, metallic flexible
21、tube, vibration isolator, expansion joint) and non-metallic tube used in the refrigerant circuits of refrigerating systems and heat pumps. It also describes the requirements to qualify the tightness of non-metallic tubes (e.g. plastic) used in evaporating and/or condensing sides of refrigerating sys
22、tems and heat pumps. It does not apply to flexible pipes that are only occasionally stressed beyond the elastic limit, e. g. during repair work, or to joints which are free to rotate or hinge. 2 Normative references The following referenced documents are indispensable for the application of this doc
23、ument. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 378-1:2008, Refrigerating systems and heat pumps Safety and environmental requirements Part 1: Basic requirements, definitions, cl
24、assification and selection criteria EN 378-2:2008, Refrigerating systems and heat pumps Safety and environmental requirements Part 2: Design, construction, testing, marking and documentation EN ISO 175, Plastics - Methods of test for the determination of the effects of immersion in liquid chemicals
25、(ISO 175:1999) ISO 6605:2002, Hydraulic fluid power Hoses and hose assemblies Test methods 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 378-1:2008 and the following apply. 3.1 flexible pipe element any form of pipe or tube connecting two points whi
26、ch may move relative to each other NOTE 1 This generic term includes all types, as defined in 3.2 to 3.6. NOTE 2 Flexible pipe elements may include a plastic barrier in the construction, either as a liner on the inner surface or as a sandwich in the pipe wall. The main purpose of such a barrier is t
27、o reduce the permeation of refrigerant gas. 3.2 metallic flexible pipe readily flexible, small bore pipe, e. g. capillary tube which is capable of movement within its elastic limit during operation of the refrigerating system (see Figure 1) NOTE This type of pipe is flexible by virtue of the shape i
28、nto which the tube is bent, e. g. coiled capillary tube. 3.3 metallic flexible tube tubular flexible element designed to bend within defined limits and containing a corrugated metal bellows, the corrugations of which may be annular or spiral (see Figure 1) Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA
29、 STANDARDS, 03/06/2009 08:04, Uncontrolled Copy, (c) BSIBS EN 1736:2008EN 1736:2008 (E) 6 NOTE 1 Metallic flexible tubes may be reinforced by metallic braiding which may be covered by rubber or plastic but the whole element should be designed so that, when bent within pre-determined limits, it is no
30、t stressed beyond the elastic limit. NOTE 2 This type of pipe is flexible by virtue of its design and construction, e. g. bellows. 3.4 non-metallic flexible tube tubular flexible element designed to bend within defined limits (see Figure 1) NOTE 1 Non-metallic flexible tubes may have smooth bore or
31、corrugated bore and they may be reinforced to withstand pressure, vacuum or external impact. NOTE 2 This type of pipe is flexible by virtue of its material, e. g. elastomer. NOTE 3 For non-metallic flexible tube are to be intended all the pipes made of plastic or rubber: mono-layer, multi-layer, rei
32、nforced and non-reinforced ones. Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 03/06/2009 08:04, Uncontrolled Copy, (c) BSIBS EN 1736:2008EN 1736:2008 (E) 7 Flexible Pipe Elements metallic flexibe pipe (3.2) metallic flexible tube (3.3) non-metallic flexible tube (3.4) flexibility is config
33、uration dependent (e. g. coils) flexibility is construction dependent (e. g. bellows) flexibility is material dependent (e. g. elastomer) Figure 1 Types of flexible pipe elements 3.5 expansion joint tubular pipe element shaped in such a way that it provides limited movement to accommodate thermal ex
34、pansion without reaching its elastic limit 3.6 vibration isolator short flexible tube usually of metallic construction which is intended to reduce the effects of vibration from the compressor to other parts of the refrigerating system or vice versa 3.7 maximum allowable pressure PS maximum pressure
35、for which the equipment is designed, as specified by the manufacturer 3.8 maximum/minimum allowable temperature TS maximum/minimum temperature for which the equipment is designed, as specified by the manufacturer 4 Applications 4.1 General 4.1.1 The refrigerating system shall be so designed and cons
36、tructed that the components being connected by the flexible pipe elements and non-metallic tubes cannot move in such a way as to stress the pipe element beyond its elastic limit. 4.1.2 Flexible pipe elements and non-metallic tubes shall be installed in accordance with the manufacturers instructions.
37、 4.1.3 Flexible pipe elements, vibration isolators, expansion joints and non-metallic tubes shall be used only if necessary. Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 03/06/2009 08:04, Uncontrolled Copy, (c) BSIBS EN 1736:2008EN 1736:2008 (E) 8 4.2 Significantly moved flexible pipe elem
38、ents NOTE Such elements are subjected to regular movement through significant distance to allow the operation of refrigerating equipment such as plate freezers. 4.2.1 Significantly moved flexible pipe elements shall be supported and connected in such a way that they are not bent to radii less than t
39、hose specified by the manufacturer. 4.2.2 Significantly moved flexible pipe elements shall not allow the generation of static electricity when non-conducting refrigerants pass through them at high velocity. NOTE This may be achieved by the use of antistatic plastic as lining. 4.2.3 Significantly mov
40、ed flexible pipe elements shall be so installed that there is no danger of the outer covering being abraded on stationary objects during movement of the flexible pipe. 4.2.4 Significantly moved flexible pipe elements shall be so constructed and connected that they are not liable to damage by the fre
41、ezing of water or by corrosion by humidity at the surface or at joints. 4.2.5 The manufacturer of significantly moved non-metallic flexible tubes shall specify the permeability of the pipe element to water vapour and to the refrigerants for which it is suitable (see Clauses 7 and 8). 4.3 Intermitten
42、tly moved flexible pipe elements NOTE Such elements move intermittently to take up relative movement between components of the refrigerating system. 4.3.1 Intermittently moved flexible pipe elements shall be supported and connected in such a way that they are not bent to radii less than those specif
43、ied by the manufacturer. 4.3.2 Intermittently moved flexible pipe elements shall not allow the generation of static electricity when non-conducting refrigerants pass through them at high velocity. NOTE This may be achieved by the use of antistatic plastic as lining. 4.3.3 Intermittently moved flexib
44、le pipe elements shall be so installed that there is no danger of the outer covering being abraded on stationary objects during movement of the flexible pipe. 4.3.4 Intermittently moved flexible pipe elements shall be so constructed and connected that they are not liable to damage by the freezing of
45、 water or by corrosion by humidity at the surface or at joints. 4.3.5 The manufacturer of intermittently moved non-metallic flexible tubes shall specify the permeability of the pipe element to water vapour and to the refrigerants for which it is suitable (see Clauses 7 and 8). 4.4 Fixed installed fl
46、exible pipe elements NOTE Such elements are used to minimise assembly difficulty by accommodating slight misalignments or relative movement between components of the refrigerating system. 4.4.1 Fixed installed flexible pipe elements shall be supported and connected in such a way that they are not be
47、nt to radii less than those specified by the manufacturer. 4.4.2 Fixed installed flexible pipe elements shall not allow the generation of static electricity when non-conducting refrigerants pass through them at high velocity. NOTE This may be achieved by the use of antistatic plastic as lining. Lice
48、nsed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 03/06/2009 08:04, Uncontrolled Copy, (c) BSIBS EN 1736:2008EN 1736:2008 (E) 9 4.4.3 Fixed installed flexible pipe elements shall be so constructed and connected that they will not be damaged by freezing of water or by corrosion by humidity at the su
49、rface or at joints. 4.4.4 The manufacturer of fixed installed non-metallic flexible tubes shall specify the permeability of the pipe element to water vapour and to the refrigerants for which it is suitable (see Clauses 7 and 8). 4.5 Vibration isolators NOTE 1 Vibration isolators are commonly used as suction and discharge connections for compressors and are also sometimes used as connections to evaporators and condensers. NOTE 2 Vibration isolators are not suitable for preventing the transmission of gas pulsation. 4.5.1 Vibration isolators shall be so i