1、BS EN15269-20:2009ICS 13.220.50; 91.060.50NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBRITISH STANDARDExtended applicationof test results forfire resistance and/or smoke control fordoor, shutter andopenable windowassemblies, includingtheir elements ofbuilding hardwarePart 2
2、0: Smoke control for hinged andpivoted steel, timber and metal framedglazed doorsetsThis British Standardwas published under theauthority of the StandardsPolicy and StrategyCommittee on 31 October2009. BSI 2009ISBN 978 0 580 65716 0Amendments/corrigenda issued since publicationDate CommentsBS EN 152
3、69-20:2009National forewordThis British Standard is the UK implementation of EN 15269-20:2009.The UK participation in its preparation was entrusted to TechnicalCommittee FSH/22/5, Test procedures for doors.A list of organizations represented on this committee can be obtained onrequest to its secreta
4、ry.This publication does not purport to include all the necessary provisionsof a contract. Users are responsible for its correct application.Compliance with a British Standard cannot confer immunityfrom legal obligations.BS EN 15269-20:2009EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 15269-2
5、0 September 2009 ICS 13.220.50; 91.060.50 English Version Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 20: Smoke control for hinged and pivoted steel, timber and me
6、talframed glazed doorsets Application tendue des rsultats dessais en matire de rsistance au feu et/ou dtanchit la fume des blocs-portes, blocs-fermetures et ouvrants de fentre, y compris leurs lments de quincaillerie intgrs - Partie 20 : tanchit la fume des blocs-portes battants et pivotants en acie
7、r, en bois et vitrs ossature mtallique Erweiterter Anwendungsbereich von Prfergebnissen zur Feuerwiderstandsfhigkeit und/oder Rauchdichtigkeit von Tren, Toren und Fenstern einschlielich ihrer Baubeschlge - Teil 20: Rauchdichtigkeit von Drehflgeltren und -toren aus Holz und Stahl sowie Metall-und Hol
8、zrahmentren mit Verglasungen This European Standard was approved by CEN on 1 August 2009. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date li
9、sts and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the re
10、sponsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary,
11、 Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: A
12、venue Marnix 17, B-1000 Brussels 2009 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 15269-20:2009: EBS EN 15269-20:2009EN 15269-20:2009 (E) 2 Contents Page Foreword 3Introduction .41 Scope 52 Normative references 53 Definitions 6
13、4 Determination of the field of extended application 64.1 General 64.2 Procedure for evaluation 64.3 Procedure for maximum field of extended application .64.4 Interpretation of test results .75 Extended application report .76 Classification report 7Annex A (normative) Construction parameter variatio
14、ns 8Annex B (normative) Arrangements for doorsets incorporating side and/or overpanels . 37Bibliography . 40BS EN 15269-20:2009EN 15269-20:2009 (E) 3 Foreword This document (EN 15269-20:2009) has been prepared by Technical Committee CEN/TC 127 “Fire safety in buildings”, the secretariat of which is
15、held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by March 2010, and conflicting national standards shall be withdrawn at the latest by March 2010. Attention is drawn to the possibility th
16、at some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. The (pr/Fpr)EN 15269 series of standards Extended application of test results for fire resistance and/or smoke control for doo
17、r, shutter and openable window assemblies, including their elements of building hardware currently consists of: Part 1: General Requirements Part 2: Fire resistance of hinged and pivoted steel doorsets Part 3: Fire resistance of hinged and pivoted timber doorsets and openable timber framed windows P
18、art 4: Fire resistance of hinged and pivoted glass doorsets Part 5: Fire resistance of hinged and pivoted, metal framed, glazed doorsets and openable windows Part 6: Fire resistance of sliding timber doorsets Part 7: Fire resistance of sliding steel doorsets Part 8: Fire resistance of horizontally f
19、olding timber doorsets Part 9: Fire resistance of horizontally folding steel doorsets Part 10: Fire resistance of steel rolling shutters Part 11: Fire resistance of operable fabric curtains Part 20: Smoke control for hinged and pivoted steel, timber and metal framed glazed doorsets This document has
20、 been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria
21、, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. BS EN 15269-20:2009EN 15269-20:
22、2009 (E) 4 Introduction This document is one of a series of standards listed above and is intended to be used for the purpose of producing an extended application report based on the evaluation of one or more fire resistance and/or smoke control tests. These standards may also be used to identify th
23、e best selection of test specimens required to cover a wide range of product variations. Before there can be any consideration for extended application the doorset shall have been tested in accordance with EN 1634-3 to achieve a test result which could generate a classification in accordance with EN
24、 13501-2 at least equal to the classification subsequently required from extended application considerations. A review of the doorset construction parameters can indicate that one or more characteristics may be improved by a particular parameter variation. All evaluations shall be made on the basis
25、of retaining the fire resistance classifications obtainable from testing to EN 1634-3. However, this shall never lead to an increased classification for any specific fire or smoke performance parameter beyond that achieved during any one test unless specifically identified in the relevant Constructi
26、on Parameter Variation tables within this series of standards. The classification of smoke control of doiorsets foresees the addition of the symbol “C“ indicating that the product also satisfies the “self closing“ criterion. The “C“ classification is complimented by the digits 0 to 5 according to th
27、e use category on the basis of details included in the relevant product standards. The effect on the “C“ classification following an extended application process is not addressed in this standard. BS EN 15269-20:2009EN 15269-20:2009 (E) 5 1 Scope This Part of (pr/Fpr)EN 15269, which should be read i
28、n conjunction with prEN 15269-1, covers hinged and pivoted steel doorsets, hinged and pivoted timber doorsets (including timber framed glazed doorsets) and hinged and pivoted metal framed glazed doorsets of single or double-leaf construction. The document prescribes the methodology for extending the
29、 application of test results obtained from test(s) conducted in accordance with EN 1634-3. NOTE It is anticipated that the above scope will be extended to cover other product types when the relevant test information and expertise become available. Subject to the completion of the appropriate test or
30、 tests, the extended application may cover Ambient Temperature Smoke Control (Sa) and Medium Temperature Smoke Control (Sm) classifications and all or some of the following variations: glazed elements, louvres and/or vents; side, transom or overpanels; items of building hardware; decorative finishes
31、; intumescent, smoke, draught or acoustic seals; alternative supporting construction(s). 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition
32、of the referenced document (including any amendments) applies. EN 1363-1:1999, Fire resistance tests Part 1: General requirements EN 1634-1:2008, Fire resistance and smoke control tests for door, shutter and openable window assemblies and elements of building hardware Part 1: Fire resistance tests f
33、or doors, shutters and openable windows EN 1634-2, Fire resistance and smoke control tests for door, shutter and openable window assemblies and elements of building hardware Part 2: Fire resistance characterisation test for elements of building hardware EN 1634-3:2004, Fire resistance and smoke cont
34、rol tests for door and shutter assemblies, openable windows and elements of building hardware Part 3: Smoke control test for door and shutter assemblies EN 13501-2:2007, Fire classification of construction products and building elements Part 2: Classification using data from fire resistance tests, e
35、xcluding ventilation services prEN 15269-1:2009, Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware Part 1: General Requirements EN ISO 13943:2000, Fire safety Vocabulary (ISO 1
36、3943:2000) BS EN 15269-20:2009EN 15269-20:2009 (E) 6 3 Definitions For the purposes of this Part of EN 15269, the terms and definitions given in EN 1363-1:1999, EN ISO 13943:2000, EN 1634-1:2008, EN 1634-3:2004 and prEN 15269-1:2009 together with the following apply : 3.1 core material fitted centra
37、lly within the thickness of a door leaf which may consist of a single sheet of material or a combination either of sheets of the same material or layers of different materials 4 Determination of the field of extended application 4.1 General 4.1.1 Before there can be any consideration for extended ap
38、plication the doorset shall have been tested and classified in accordance with EN 1634-3 and EN 13501-2 respectively in order to establish a classification for the doorset. 4.1.2 A review of the doorset construction parameters can indicate that one or more characteristics may be improved by a partic
39、ular parameter variation. All evaluations shall be made on the basis of retaining the classifications obtainable from testing to EN 1634-3, including those lower than the test duration. However, this shall never lead to an increased classification for any specific parameter beyond that achieved duri
40、ng any one test unless specifically identified in the relevant Construction Parameter Variation tables. 4.1.3 All evaluations shall be made on the basis of retaining the classification obtained from testing to EN 1634-3. 4.1.4 If, by following the ensuing procedure, any part of the classification ca
41、nnot be achieved by extended application rules that part of classification shall be omitted from the subsequent extended application report and classification report. 4.2 Procedure for evaluation 4.2.1 Identify the variations from the original test specimen(s) which are required to be covered by an
42、extended application report. 4.2.2 Locate the variations in the appropriate parameter variation by reference to columns (1) and (2) of Table A.1. 4.2.3 Review the type of classification to be retained from column (3) of Table A.1 and establish from the contents of column (4) of Table A.1 whether any
43、 extended application is available without the need for further testing. 4.2.4 Where this is deemed to be possible this can be recorded in the extended application report together with any appropriate restrictions and the stated rules from column (4) in Table A.1. 4.2.5 Where the variations required
44、 can only be achieved from additional testing according to column (5), the additional test can be made on a similar specimen type to the original test against which the extended application is sought. Alternatively, column (5) in Table A.1 identifies an option for alternative testing and relevant te
45、st parameters. 4.3 Procedure for maximum field of extended application 4.3.1 It is possible to provide a limited field of extended application from the results of a single test. However, where a manufacturer intends to produce a range of doors incorporating single doors and also double doors with or
46、 without glazing, with alternative elements of building hardware, etc., it is recommended BS EN 15269-20:2009EN 15269-20:2009 (E) 7 that careful consideration is given to the complete range of doorset designs and options in order to minimise the testing required before testing commences. 4.3.2 Estab
47、lish all the parameter variations which are required to be part of the product range. 4.3.3 Select specimens for the first tests in the series to ensure that the most important parameter variations for the manufactured products are covered. 4.3.4 Complete the first test or a series of tests and prep
48、are a field of direct application and possibly a classification report from the results of the test(s). 4.3.5 Establish which of the original desired parameter variations have not been covered by the direct application and classification report. 4.3.6 Identify these parameter variations in Annex A a
49、nd establish where an extended application is possible without further testing. 4.3.7 Record this for the extended application report together with any restrictions and rules given in column (5) in Table A.1. 4.3.8 Evaluate which, if any, of the desired parameter variations have not been covered by the field of direct application or the initial field of extended application derived from 4.3.7 above. 4.3.9 Select the required outstanding parameter var