1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationBS EN 15599-1:2010Thermal insulation productsfor building equipment andindustrial installations In-situ thermal insulation formedfrom expanded perlite (EP)productsPart 1: Specifi
2、cation for bonded and loose-fill products before installationBS EN 15599-1:2010 BRITISH STANDARDNational forewordThis British Standard is the UK implementation of EN 15599-1:2010.The UK participation in its preparation was entrusted to TechnicalCommittee PRI/72, Rigid cellular materials.A list of or
3、ganizations represented on this committee can beobtained on request to its secretary.This publication does not purport to include all the necessaryprovisions of a contract. Users are responsible for its correctapplication. BSI 2010ISBN 978 0 580 68707 5ICS 91.100.60Compliance with a British Standard
4、 cannot confer immunity fromlegal obligations.This British Standard was published under the authority of theStandards Policy and Strategy Committee on 31 August 2010.Amendments issued since publicationDate Text affectedBS EN 15599-1:2010EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 15599-1 Ju
5、ly 2010 ICS 91.100.60 English Version Thermal insulation products for building equipment and industrial installations - In-situ thermal insulation formed from expanded perlite (EP) products - Part 1: Specification for bonded and loose-fill products before installation Produits isolants thermiques po
6、ur lquipement du btiment et les installations industrielles - Isolation thermique forme en place base de granulats lgers de Perlite expanse (EP) - Partie 1: Spcification de produits lis et en vrac avant mise en oeuvre Wrmedmmstoffe fr die technische Gebudeausrstung und fr betriebstechnische Anlagen
7、in der Industrie - An der Verwendungsstelle hergestellte Wrmedmmung mit Produkten aus expandiertem Perlit (EP) - Teil 1: Spezifikation fr gebundene und Schttprodukte vor dem Einbau This European Standard was approved by CEN on 6 May 2010. CEN members are bound to comply with the CEN/CENELEC Internal
8、 Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member.
9、 This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions. CEN members
10、are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Swe
11、den, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2010 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members.
12、 Ref. No. EN 15599-1:2010: EBS EN 15599-1:2010EN 15599-1:2010 (E) 2 Contents Page Foreword 41 Scope 52 Normative references 53 Terms and definitions, Symbols and Abbreviations 63.1 Terms and Definitions .63.2 Symbols and Abbreviations .73.2.1 Symbols used in this standard .73.2.2 Abbreviations used
13、in this standard74 Requirements .74.1 General 74.2 For all applications 74.2.1 Thermal resistance and thermal conductivity 74.2.2 Loose bulk density 84.2.3 Particle size 84.2.4 Reaction to fire .84.2.5 Durability characteristics 94.3 For specific applications .94.3.1 General 94.3.2 Maximum service t
14、emperature .94.3.3 Minimum service temperature 94.3.4 Crushing resistance 94.3.5 Water vapour permeability . 104.3.6 Release of dangerous substances 104.3.7 Continuous glowing combustion 105 Test methods . 105.1 Sampling 105.2 Conditioning 105.3 Testing . 105.3.1 General . 105.3.2 Thermal conductivi
15、ty 116 Designation Code . 117 Evaluation of conformity 128 Marking and labelling . 12Annex A (normative) Factory production control . 14Annex B (normative) Preparation of the test specimens to measure thermal conductivity . 15Annex C (normative) Special conditions to be used for the determination of
16、 organic content . 16C.1 Principle . 16C.2 Apparatus 16C.3 Procedure 16C.4 Calculation and expression of results 16C.5 Test report . 16Annex D (normative) Determination of maximum service temperature 17D.1 Principle . 17D.2 Apparatus 17D.3 Procedure 17D.4 Test report . 18BS EN 15599-1:2010EN 15599-1
17、:2010 (E) 3 Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU Construction Products Directive . 19ZA.1 Scope and relevant characteristics . 19ZA.2 Procedures for attestation of conformity of loose-fill expanded perlite products . 20ZA.2.1 Systems of attesta
18、tion of conformity 20ZA.2.2 EC declaration of conformity . 21ZA.3 CE Marking and labelling 22Bibliography 25BS EN 15599-1:2010EN 15599-1:2010 (E) 4 Foreword This document (EN 15599-1:2010) has been prepared by Technical Committee CEN/TC 88 “Thermal insulating materials and products”, the secretariat
19、 of which is held by DIN. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by January 2011, and conflicting national standards shall be withdrawn at the latest by January 2011. Attention is drawn to t
20、he possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document has been prepared under a mandate given to CEN by the European Commission and the European Free
21、 Trade Association, and supports essential requirements of EU Directive(s). For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document. This European Standard consists of two parts which form a package. The first part, which is the harmonised part sat
22、isfying the mandate, the CPD and is the basis for the CE marking, covers the products, which are placed on the market. The second part, which is the non-harmonised part, covers the specification for the installed products. This document contains five Annexes: Annex A (normative) - Factory production
23、 control Annex B (normative) - Preparation of test specimens to measure thermal conductivity Annex C (normative) - Special conditions to be used for the determination of organic content Annex D (normative) - Determination of maximum service temperature Annex ZA (informative) - Clauses of this Europe
24、an Standard addressing the provisions of the EU Construction Products Directive This European Standard is one of a series for polyurethane/polyisocyanurate, expanded perlite and exfoliated vermiculite in-situ formed insulation products used in building equipment and industrial installations, but thi
25、s standard may be used in other areas where appropriate. EN 14316-1 covers the use of expanded perlite in buildings. The reduction in energy used and emissions produced during the installed life of insulation products exceeds by far the energy used and emissions made during the production and dispos
26、al processes. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Ic
27、eland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. BS EN 15599-1:2010EN 15599-1:2010 (E) 5 1 Scope This European Standard specifies the requirements for expanded perlite p
28、roducts which are used for the thermal insulation of building equipment and industrial installations with an operating temperature in the range of approximately 270 C to +650 C. This European Standard specifies the requirements for the four types of expanded perlite products Perlite Aggregate (EPA),
29、 Coated Perlite (EPC), Hydrophobic Perlite (EPH) and Premixed Perlite (EPM), containing less than 1 % by mass organic material as determined by Annex C. This European Standard is a specification for the insulation products before installation. This European Standard describes the product characteris
30、tics and includes procedures for testing, evaluation of conformity, marking and labelling. This European Standard does not specify the required level of a given property to be achieved by a product to demonstrate fitness for purpose in a particular application. The levels required for a given applic
31、ation are to be found in regulations or non-conflicting standards. This European Standard does not cover factory made insulation products of formed shapes and boards made with expanded perlite, and does not cover products intended to be used for the insulation of buildings. The products covered by t
32、his standard are not intended to be used primarily for airborne sound insulation or sound absorption applications although they may improve the performance of the installation in these respects when installed for their primary insulation intended use. 2 Normative references The following referenced
33、documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 932-1, Tests for general properties of aggregates Part 1: Methods for s
34、ampling EN 932-2, Tests for general properties of aggregates Part 2: Methods for reducing laboratory samples EN 933-1, Tests for geometrical properties of aggregates Part 1: Determination of particle size distribution Sieving method EN 993-14, Methods of test for dense shaped refractory products Par
35、t 14: Determination of thermal conductivity by the hot-wire (cross-array) method EN 1097-3, Tests for mechanical and physical properties of aggregates Part 3: Determination of loose bulk density and voids EN 12086, Thermal insulating products for building applications Determination of water vapour t
36、ransmission properties EN 12667, Thermal performance of building materials and products Determination of thermal resistance by means of guarded hot plate and heat flow meter methods Products of high and medium thermal resistance EN 13055-1, Lightweight aggregates Part 1: Lightweight aggregates for c
37、oncrete, mortar and grout EN 13055-2, Lightweight aggregates Part 2: Lightweight aggregates for bituminous mixtures and surface treatments and for unbound and bound applications BS EN 15599-1:2010EN 15599-1:2010 (E) 6 EN 13172, Thermal insulating products Evaluation of conformity EN 13820, Thermal i
38、nsulating materials for building applications Determination of organic content EN 14706, Thermal insulating products for building equipment and industrial installations Determination of maximum service temperature EN ISO 13787, Thermal insulation products for building equipment and industrial instal
39、lations Determination of declared thermal conductivity (ISO 13787:2003) 3 Terms and definitions, Symbols and Abbreviations 3.1 Terms and Definitions For the purposes of this document, the following terms and definitions apply. 3.1.1 expanded perlite lightweight granular (insulation) material manufac
40、tured from naturally occurring volcanic rock expanded by heat to form a cellular structure EN ISO 9229 3.1.2 perlite aggregate expanded perlite with no treatment or surface coating, used as a loose insulation in cavities 3.1.3 coated perlite expanded perlite which has a coating 3.1.4 hydrophobic per
41、lite expanded perlite which is treated to give specific hydrophobic properties and used where moisture or water repellency is required 3.1.5 premixed perlite expanded perlite premixed with binders to form bonded materials in end use applications 3.1.6 level given value which is the upper or lower li
42、mit of requirement, where the level is given by the declared value of the characteristic concerned 3.1.7 class combination of two levels of the same property between which the performance shall fall, where the level is given by the declared value of the characteristic concerned BS EN 15599-1:2010EN
43、15599-1:2010 (E) 7 3.2 Symbols and Abbreviations 3.2.1 Symbols used in this standard Dis the declared thermal conductivity W/(mK) is the water vapour diffusion resistance factor CR is the symbol of the declared value for crushing resistance LD is the symbol of the declared value for loose bulk densi
44、ty PS is the symbol of the declared particle size ST(+) is the symbol of the declared maximum service temperature ST(-) is the symbol of the declared minimum service temperature 3.2.2 Abbreviations used in this standard EP is expanded perlite as defined in 3.1.1 EPA is perlite aggregate as defined i
45、n 3.1.2 EPC is coated perlite as defined in 3.1.2 EPH is hydrophobic perlite as defined in 3.1.2 EPM is premixed perlite as defined in 3.1.2 ITT is initial type testing. 4 Requirements 4.1 General Product properties shall be assessed in accordance with Clause 5. To comply with this standard, product
46、s shall meet the requirements of 4.2, and the requirements of 4.3 as appropriate. One test result for a product property is the average of the measured values on the number of test specimens given in Table 1. 4.2 For all applications 4.2.1 Thermal resistance and thermal conductivity Thermal conducti
47、vity shall be based upon measurements carried out in accordance with EN 12667 (limited to 110 C) or EN 993-14 (this test is calibrated against EN 12667). In each case the thermal conductivity values shall be determined by the manufacturer and verified in accordance with EN ISO 13787. They shall be d
48、eclared by the manufacturer according to the above specified measurement standards covering the product service temperature range. The following conditions apply: measured values shall be expressed with three significant figures; declared thermal conductivity curve shall be given as a limit curve, d
49、efined in EN ISO 13787; BS EN 15599-1:2010EN 15599-1:2010 (E) 8 values of the thermal conductivity, D, shall be rounded upwards to the nearest 0,001 W/(m K). The declared equation/limit curve is the “declared reference“ with three significant figures, that is to 0,0001 W/(mK) for values below 0,1 W/(mK) and in 0,0