1、BSI Standards PublicationBS EN 50288-6-1:2013Multi-element metallic cablesused in analogue and digitalcommunication and control -Part 6-1: Sectional specification forunscreened cables characterised up to 250MHz Horizontal and building backbonecablesCopyright British Standards Institution Provided by
2、 IHS under license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-6-1:2013 BRITISH STANDARDNational forewordThis British Standard is the UK implementation of EN50288-6-1:2013. It supersedes BS EN 50288-6-1:2003 which iswith
3、drawn.The UK participation in its preparation was entrusted to TechnicalCommittee EPL/46, Cables, wires and waveguides, radio frequencyconnectors and accessories for communication and signalling.A list of organizations represented on this committee can beobtained on request to its secretary.This pub
4、lication does not purport to include all the necessaryprovisions of a contract. Users are responsible for its correctapplication. The British Standards Institution 2014. Published by BSI StandardsLimited 2014ISBN 978 0 580 77102 6ICS 33.120.20Compliance with a British Standard cannot confer immunity
5、 fromlegal obligations.This British Standard was published under the authority of theStandards Policy and Strategy Committee on 28 February 2014.Amendments issued since publicationDate Text affectedCopyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Not
6、 for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-6-1:2013EUROPEAN STANDARD EN 50288-6-1 NORME EUROPENNE EUROPISCHE NORM May 2013 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komi
7、tee fr Elektrotechnische Normung Management Centre: Avenue Marnix 17, B - 1000 Brussels 2013 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 50288-6-1:2013 E ICS 33.120.20 Supersedes EN 50288-6-1:2003 English version Multi-element
8、 metallic cables used in analogue and digital communication and control - Part 6-1: Sectional specification for unscreened cables characterised up to 250 MHz - Horizontal and building backbone cables Cbles mtalliques lments multiples utiliss pour les transmissions et les commandes analogiques et num
9、riques - Partie 6-1: Spcification intermdiaire pour les cbles non blinds pour applications jusqu 250 MHz - Cbles horizontaux et verticaux de btiment Mehradrige metallische Daten- und Kontrollkabel fr analoge und digitale bertragung - Teil 6-1: Rahmenspezifikation fr ungeschirmte Kabel bis 250 MHz -
10、Kabel fr den Horizontal- und Steigbereich This European Standard was approved by CENELEC on 2013-03-18. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alterat
11、ion. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language ma
12、de by translation under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech
13、Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingd
14、om. Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-6-1:2013EN 50288-6-1:2013 - 2 - Contents Page Foreword . 3 1 Scope 4 2 Normative references . 4 3 Term
15、s, definitions, symbols and abbreviations . 4 3.1 Terms and definitions 4 4 Cable construction . 5 4.1 Conductor . 5 4.2 Insulation 5 4.3 Cabling elements 5 4.4 Identification of cabling elements 5 4.5 Screening of cabling elements 5 4.6 Cable make-up 5 4.7 Filling compound . 5 4.8 Interstitial fill
16、ers . 5 4.9 Screening of the cable core 5 4.10 Moisture barriers . 5 4.11 Wrapping layers 5 4.12 Sheath 5 5 Tests and requirements for completed cables 6 5.1 Electrical tests . 6 5.2 Mechanical tests requirements . 8 5.3 Environmental tests 9 5.4 Fire performance tests . 9 Annex A (Informative) Maxi
17、mum voltage, current and temperature rating for cables used for POE applications 10 Annex B (Informative) Blank Detail Specification . 11 Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or networking permitted without l
18、icense from IHS-,-,-BS EN 50288-6-1:2013- 3 - EN 50288-6-1:2013 Foreword This document EN 50288-6-1:2013 has been prepared by CLC/SC 46XC “Multicore, Multipair and Quad Data communication cables,“ of CLC/TC 46X, “Communication cables“. The following dates are fixed: latest date by which this documen
19、t has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2014-03-18 latest date by which the national standards conflicting with this document have to be withdrawn (dow) 2016-03-18 This document supersedes EN 50288-6-1:2003. EN 50288-6-1:2013
20、 includes the following significant technical changes with respect to EN 50288-6-1:2003: - the addition of the Blank Detail Specification Annex; - a number minor corrections and updating of references; - the re-classification of ELFEXT to ACR-F. This Part 6-1 is to be read in conjunction to EN 50288
21、-1. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CENELEC and/or CEN shall not be held responsible for identifying any or all such patent rights. This standard covers the Principle Elements of the Safety Objectives for Electrica
22、l Equipment Designed for Use within Certain Voltage Limits (LVD - 2006/95/EC). _ Copyright British Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-6-1:2013EN 50288-6-1:2013
23、 - 4 - 1 Scope EN 50288-6-1 is a sectional specification for unscreened cables, characterised from 1 MHz up to 250 MHz, to be used in horizontal and building backbone wiring as defined in EN 50173. This sectional specification contains the electrical, mechanical, transmission and environmental perfo
24、rmance characteristics of the cables, when tested in accordance with the referenced test methods. This sectional specification is to be read in conjunction with EN 50288-1 that contains the essential provisions for its application. The cables covered in this sectional specification are intended to o
25、perate with voltages and currents normally encountered in communication systems. These cables are not intended to be used in conjunction with low impedance sources, for example, the electric power supplies of public utility mains. 2 Normative references The following documents, in whole or in part,
26、are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 50173 series Information technology Generic cablin
27、g systems EN 50288-1 Multi-element metallic cables used in analogue and digital communication and control Part 1: Generic specification EN 50289 series Communication cables Specifications for test methods EN 50290 series Communication cables EN 60811 series Electric and optical fibre cables - Test m
28、ethods for non-metallic materials (IEC 60811 series) IEC 60189-2 Low-frequency cables and wires with PVC insulation and PVC sheath Part 2: Cables in pairs, triples, quads and quintuples for inside installations 3 Terms, definitions, symbols and abbreviations 3.1 Terms and definitions For the purpose
29、s of this document the terms and definitions given in EN 50288-1 apply. 3.2 Symbols and abbreviations For the purposes of this document, the following abbreviations apply. EX Exogenous (derived or originating externally) POE Power Over Ethernet Copyright British Standards Institution Provided by IHS
30、 under license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-6-1:2013- 5 - EN 50288-6-1:2013 4 Cable construction 4.1 Conductor The conductor shall be solid copper and meet the requirements of EN 50288-1, 4.1 The conductor
31、 shall be plain or metal coated. The nominal conductor diameter shall be 0,5 mm and 0,8 mm. NOTE Constructions with copper clad conductors do not meet the requirements 4.2 Insulation The insulation shall be of a suitable material according to the relevant part of EN 50290-2. 4.3 Cabling elements The
32、 cable element shall be a pair or a quad. 4.4 Identification of cabling elements Unless otherwise specified, the colour coding for identification is given in IEC 60189-2. The colours shall meet the requirements of EN 50288-1, 4.4 4.5 Screening of cabling elements Not applicable. 4.6 Cable make-up Th
33、e cable elements shall be laid up in concentric layer(s) or units to form the cable core. 4.7 Filling compound Not applicable. 4.8 Interstitial fillers Where fillers are used they shall meet the requirements of EN 50288-1, 4.8 4.9 Screening of the cable core Not applicable. 4.10 Moisture barriers No
34、t applicable. 4.11 Wrapping layers Where wrapping layers are used they shall be in accordance with EN 50288-1, 4.11. 4.12 Sheath The sheath shall be of a suitable material according to the relevant part of EN 50290-2. Copyright British Standards Institution Provided by IHS under license with BSI - U
35、ncontrolled Copy Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-6-1:2013EN 50288-6-1:2013 - 6 - 5 Tests and requirements for completed cables The following tables give the tests to be applied, together with the respective limits, in order to demonstrat
36、e compliance with this specification. 5.1 Electrical tests 5.1.1 Low-frequency and d.c. electrical measurements Table 1 - Low-frequency and d.c. electrical measurements EN 50288-1 sub-clause Parameter Requirement 5.1.1.1 Conductor loop resistance 19,0 /100 m 5.1.1.2 Conductor resistance unbalance 2,
37、0 % 5.1.1.3 Dielectric strength conductor/conductor 1,0 kV d.c. or 0,7 kV a.c. for 1 min or 2,5 kV d.c. or 1,7 kV a.c. for 2 s 5.1.1.4 Insulation resistance 5 ,000 M km when tested in accordance with EN 50289-1-4 5.1.1.5 Mutual capacitance No requirement specified 5.1.1.6 Capacitance unbalance to ea
38、rth 1 200 pF/km 5.1.2 High-frequency electrical and transmission measurements Table 2 - High-frequency electrical and transmission requirements EN 50288-1 sub-clause Parameter Requirement 5.1.2.1 Velocity of propagation Phase delay 534+36/f ns/100 m, 1 MHz f 250 MHz 5.1.2.2 Propagation delay differe
39、nce (skew) 45 ns/100 m at 100 MHz 5.1.2.3 Longitudinal attenuation2) 3) 4) 5.1.2.4 Near-end unbalance attenuation 40-10log(f) dB, 1 MHz f 250 MHz 1 4 10 16 20 31,25 62,5 100 155 200 250 MHz 2,1 3,8 6,0 7,6 8,5 10,7 15,5 19,9 25,3 29,1 33,0 dB/100m 1,82f+0,0169f+0,25/f, 1 MHz f 250 MHz Copyright Brit
40、ish Standards Institution Provided by IHS under license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-6-1:2013- 7 - EN 50288-6-1:2013 EN 50288-1 sub-clause Parameter Requirement 5.1.2.5 Near-end crosstalk (NEXT)1) 2) 5.1.2
41、.6 Attenuation to crosstalk ratio at the far end 2)6) (ACR-F) 1 4 10 16 20 31,25 62,5 100 155 200 250 MHz 66,0 58,0 50,0 45,9 44,0 40,1 34,1 30,0 26,2 24,0 22,0 dB 70-20log(f), 1 MHz f 250 MHz (maximum 66 dB), values referenced to 100 m 5.1.2.7.1 Power sum near-end crosstalk 2) (PSNEXT) 5.1.2.7.2 Po
42、wer Sum Attenuation to crosstalk ratio at the far end 2)6) (PSACR-F) 5.1.2.8 Mean characteristic Impedance 100 5 , 120 5 , at 100 MHz 5.1.2.9 Return loss5)5.1.2.10 Coupling attenuation 40 dB, 30 MHz f 100 MHz 40-20log(f/100) dB, 100 MHz f 1 000 MHz 1)For hybrid cables and multi-unit cables, PSNEXT b
43、etween all non fibre recognised cable units shall be 3 dB better than the specified pair to pair NEXT at all specified frequencies. 2)The values in the table are for information only. The formula given shall be used to determine compliance, rounded to one decimal place. 3)Above 20 C the attenuation
44、shall meet values adjusted for temperature. Up to 40 C the temperature coefficient of 0,4 % per degree rise shall be used and for temperatures from 40 C to 60 C the temperature coefficient shall be 0,6 % per degree. 4)Values between 1 MHz and 4 MHz are for information only. 5)For the measurement of
45、return loss, a test sample having a round trip loss 40 dB at any measured frequency should be used. 6) ELFEXT is now re-classified as ACR-F, PSELFEXT is now re-classified PSACR-F, see Annex A of EN 50288-1 for explanation 1 4 10 16 20 31,25 62,5 100 155 200 250 MHz 75.3 66,3 60,3 57,2 55,8 52,9 48,4
46、 45,3 42,4 40,8 39,3 dB 75,3-15log(f), 1 MHz f 250 MHz 1 4 10 16 20 31,25 62,5 100 155 200 250 MHz 72.3,0 63,3 57,3 54,2 52,8 49,9 45,4 42,3 39,4 37,8 36,3 dB 72,3-15log(f) 1 MHz f 250 MHz 1 4 10 16 20 31,25 62,5 100 155 200 250 MHz 64,0 55,0 47,0 43,0 41,0 37,1 31,1 27,0 23,2 21,0 19,0 dB 67-20log(
47、f), 1 MHz f 250 MHz (maximum 64 dB), values referenced to 100 m 4 8 10 16 20 31,25 62,5 100 155 200 250 MHz 23,1 24,5 25,0 25,0 25,0 23,6 21,5 20,1 18,8 18,0 17,3 dB 20+5log(f), 4 MHz f 10 MHz; 25,0 dB, 10 MHz f 20 MHz; 25-7log(f/20), 20 MHz f 250 MHz; Copyright British Standards Institution Provide
48、d by IHS under license with BSI - Uncontrolled Copy Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 50288-6-1:2013EN 50288-6-1:2013 - 8 - 5.2 Mechanical tests requirements Table 3 - Mechanical test requirements EN 50288-1 sub-clause Parameter Requirement 5.2.1 Conductor elongation at break EN 50289-3-2 10 % 5.2.2 Shrinkage of insulation EN 50289-3-4 5 % for 1 h at