BS EN 60709-2010 Nuclear power plants - Instrumentation and control systems important to safety - Separation《核电站 重要安全性仪器仪表和控制系统 隔离》.pdf

上传人:eveningprove235 文档编号:576175 上传时间:2018-12-13 格式:PDF 页数:24 大小:839.83KB
下载 相关 举报
BS EN 60709-2010 Nuclear power plants - Instrumentation and control systems important to safety - Separation《核电站 重要安全性仪器仪表和控制系统 隔离》.pdf_第1页
第1页 / 共24页
BS EN 60709-2010 Nuclear power plants - Instrumentation and control systems important to safety - Separation《核电站 重要安全性仪器仪表和控制系统 隔离》.pdf_第2页
第2页 / 共24页
BS EN 60709-2010 Nuclear power plants - Instrumentation and control systems important to safety - Separation《核电站 重要安全性仪器仪表和控制系统 隔离》.pdf_第3页
第3页 / 共24页
BS EN 60709-2010 Nuclear power plants - Instrumentation and control systems important to safety - Separation《核电站 重要安全性仪器仪表和控制系统 隔离》.pdf_第4页
第4页 / 共24页
BS EN 60709-2010 Nuclear power plants - Instrumentation and control systems important to safety - Separation《核电站 重要安全性仪器仪表和控制系统 隔离》.pdf_第5页
第5页 / 共24页
亲,该文档总共24页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

1、BRITISH STANDARDBS EN 60709:2010 Nuclear power plants Instrumentation and control systems important to safety SeparationICS 27.120.20 g49g50g3g38g50g51g60g44g49g42g3g58g44g55g43g50g56g55g3g37g54g44g3g51g40g53g48g44g54g54g44g50g49g3g40g59g38g40g51g55g3g36g54g3g51g40g53g48g44g55g55g40g39g3g37g60g3g38g

2、50g51g60g53g44g42g43g55g3g47g36g58Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 08/12/2010 06:13, Uncontrolled Copy, (c) BSINational forewordThis British Standard is the UK implementation of EN 60709:2010. It is identical to IEC 60709:2004. It supersedes BS IEC 60709:2004, which is withdraw

3、n.The UK participation in its preparation was entrusted to Technical Committee NCE/8, Reactor instrumentation.A list of organizations represented on this committee can be obtained on request to its secretary.This publication does not purport to include all the necessary provisions of a contract. Use

4、rs are responsible for its correct application.Compliance with a British Standard cannot confer immunity from legal obligations.BS EN 60709:2010This British Standard was published under the authority of the Standards Policy andStrategy Committee on 10 November 2004 BSI 2010Amendments/corrigenda issu

5、ed since publicationDate Comments 31 August 2010 This corrigendum renumbers BS IEC 60709:2004 as BS EN 60709:2010ISBN 978 0 580 68113 4Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 08/12/2010 06:13, Uncontrolled Copy, (c) BSIEUROPEAN STANDARD EN 60709 NORME EUROPENNE EUROPISCHE NORM May 201

6、0 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Management Centre: Avenue Marnix 17, B - 1000 Brussels 2010 CENELEC - All rights of exploitation in any form and by any means reserved wo

7、rldwide for CENELEC members. Ref. No. EN 60709:2010 E ICS 27.120.20 English version Nuclear power plants - Instrumentation and control systems important to safety - Separation (IEC 60709:2004) Centrales nuclaires de puissance - Systmes dinstrumentation et de contrle commande importants pour la sret

8、- Sparation (CEI 60709:2004) Kernkraftwerke - Leittechnische Systeme mit sicherheitstechnischer Bedeutung - Physikalische und elektrische Trennung (IEC 60709:2004) This European Standard was approved by CENELEC on 2010-05-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulati

9、ons which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This E

10、uropean Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members a

11、re the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Sl

12、ovenia, Spain, Sweden, Switzerland and the United Kingdom. Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 08/12/2010 06:13, Uncontrolled Copy, (c) BSIForeword The text of the International Standard IEC 60709:2004, prepared by SC 45A, Instrumentation and control of nuclear facilities, of IEC

13、TC 45, Nuclear instrumentation, was submitted to the CENELEC formal vote for acceptance as a European Standard and was approved by CENELEC as EN 60709 on 2010-05-01. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and CENELEC

14、shall not be held responsible for identifying any or all such patent rights. The following dates were fixed: latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2011-05-01 latest date by which the national stand

15、ards conflicting with the EN have to be withdrawn (dow) 2013-05-01 Annex ZA has been added by CENELEC. As stated in the nuclear safety Directive 2009/71/EURATOM, Chapter 1, Article 2, item 2, Member States are not prevented from taking more stringent safety measures in the subject-matter covered by

16、the Directive, in compliance with Community law. In a similar manner, this European Standard does not prevent Member States from taking more stringent nuclear safety measures in the subject-matter covered by this European Standard.” _ Endorsement notice The text of the International Standard IEC 607

17、09:2004 was approved by CENELEC as a European Standard without any modification. 2BS EN 60709:2010EN 60709:2010 (E)Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 08/12/2010 06:13, Uncontrolled Copy, (c) BSICONTENTS INTRODUCTION. 4 1 Scope. 7 2 Normative references . 7 3 Terms and definitions

18、 . 8 4 General principles for separation within I in Clause 5, to establish design basis criteria for I in Clause 6, to give requirements to be fulfilled for cabling separation within an I this subset is to be identified at the beginning of any project. Where independence is required by general safe

19、ty standards such as IAEA safety guides or IEC 61513, one aspect of achieving this independence is physical separation between the systems and their equipment that perform functions important to safety. This standard defines the assessments needed and the technical requirements to be met for I betwe

20、en systems of the same safety category; between redundant safety groups of the same I from systems of lower category to systems of higher category and in some specific cases from systems of higher category to systems of lower category. The types of possible failure-initiating events contained in the

21、 following subclauses shall be taken into consideration (i.e. identified, documented and justified). Adequate provisions shall be made in the I the major weaknesses of existing I the existing separation, or feasible improvements of separation, shall be evaluated through a systematic methodology, rec

22、ognising particular strengths or alternatives to the requirements of this standard; an alternative set of separation rules may be established, recognising and justifying existing conditions proven through records of plant operation; alternative technologies shall be presented and evaluated in the ca

23、se of special plant situations; e.g. through use of barriers, optical cabling, distribution of the I identification of subsystems, which can be separated without the need of intermediate interfaces; suitability of the existing separation to the new I cable routing limits and an evaluation of the nee

24、ds coming from new technologies for special cable trays for fibre optic cables, bus cables and requirements for separation. Guidance for the decision on upgrading and modernisation of I b) barriers when used between redundant systems or cables shall have a fire rating commensurate with the fire haza

25、rd protection requirements. 5.2 Environmental conditions during and after accidents I b) open circuits; c) application of the maximum a.c. or d.c. potential that could reasonably occur, considering potentials and sources available in both the category A and non-category A systems; d) electromagnetic

26、 and electrostatic interference. The properties of an isolation device shall include tolerance of and isolation for the electrical surges and spikes defined in IEC 61000-6-5; tolerance and isolation for EMI to IEC 61000-6-5; simple barriers between close or adjacent terminals or contact groups on re

27、lay equipment used for electrical isolation; prevention of transmission of excessively high or damaging voltages. In this context, an assessment should be done of the maximum voltage that could be envisaged under normal and faulted conditions, and its potential effects on the equipment important to

28、safety when applied to the isolation device terminals of the circuit of lesser importance to safety. Precautions should also be taken to minimise the possibility that failure in a non-category A system causes spurious or premature actuation of a category A function. 5.3.3 Actuation priority Where pl

29、ant equipment that is controlled by a category A system is also controlled by signals from a lower category system, isolation devices shall be provided which ensure priority of the category A system actions over those of the lower category system. Failures of, or normal actions by, the lower categor

30、y system shall not interfere with the category A functions under plant conditions requiring success of those category A functions. The priority isolation devices shall be categorised as part of the category A system. Failures and mal-operations in the non-category A systems shall cause no change in

31、response, drift, accuracy, sensitivity to noise, or other characteristics of the category A system which might impair the ability of the system to perform its safety functions. Where signals are extracted from category B or C systems for use in lower category systems, isolation devices may not be re

32、quired; however, good engineering practices should be followed to prevent the propagation of faults. In cases where systems performing category B functions need to take on the aspects of category A systems due to the functions performed, isolation shall be applied. Fibre optic communications provide

33、 a very effective means of achieving electrical isolation, and should be applied wherever practical. 14BS EN 60709:2010EN 60709:2010 (E)Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 08/12/2010 06:13, Uncontrolled Copy, (c) BSI5.4 Independence from control systems The use of category A syste

34、m signals in control systems (regardless of category) requires precautions beyond those required when category A system signals are used only for monitoring or protection purposes. A sensor failure could cause a control system measured value outside the demand tolerance, and a consequent unsafe cont

35、rol action, while preventing detection of the unsafe condition by the protection system. The protection system and the control system shall be designed so that a postulated single failure including consequential failures concerning signals transferred between these two systems cannot cause an accide

36、nt or transient requiring safety action and, at the same time, cause unacceptable degradation of the category A system. For the case where a single random failure, and any consequential failures, within the category A system could cause a control system action that results in a condition requiring s

37、afety action, then the category A system should be capable of providing this action even when degraded by a second random failure. Provisions shall be included so that this requirement can still be met if a component or assembly is by-passed or removed from service for any reason including test or m

38、aintenance purposes. Acceptable provisions will depend on the type of reactor and on the possible failures. They include reducing the required majority voting coincidence when sensor failure or equipment faults are detected, removing the control signals taken from the redundant components or assembl

39、ies when the signals are determined to not represent the true process condition, initiating a safety action from the safety logic assembly, thus putting the plant in a state no longer adversely impacted by the control system action, providing protection by use of different physical parameters. A one

40、 from two voted protection system providing control signals will require justification by trade-off arguments (see 4.7), even if effective bypasses and high sensor and equipment reliability with proof testing is claimed. A two from three voted system can meet the requirements with fail-safe equipmen

41、t and automatic detection of failed sensors if suitable bypass facilities are used during maintenance. Where it can be shown that, due to the original event, the simultaneous failure of redundant safety monitoring assemblies is unlikely, safety monitoring assemblies which compare signals may be prov

42、ided. These safety monitoring assemblies shall provide an indication, alarm or safety action signal or make the logic more restrictive when one signal deviates excessively from other redundant signals of the same plant condition or parameter. The safety monitoring assemblies which perform the compar

43、ison shall be provided with adequate isolation to prevent interaction between redundant channels. An example of this involves sending all sensor values to each redundant safety system channel. Each channel then compares the values to detect out-of-line or abnormal values. Each channel may then vote

44、all sensors values, or detect the most adverse sensor in each channel for the voted action. The sensors which are detected as faulty should be alarmed and the values may be made available for display. 15BS EN 60709:2010EN 60709:2010 (E)Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 08/12/201

45、0 06:13, Uncontrolled Copy, (c) BSI6 Requirements for cabling separation 6.1 General requirement Redundant portions of category A systems shall be designed and installed in such a way that the single events specified in all subclauses of Clause 4 cannot result in a failure of the category A function

46、. Redundant portions of category B systems shall be designed and installed in such a way that the single events specified in 4.2 and 4.3 cannot result in a failure of the category B function. Treatment of failure initiating events specified in 4.4 and 4.5 to category B systems shall be on a case by

47、case basis as discussed in the general principles (Clause 4). The items in the following subclauses shall be taken into account. 6.2 Separation Separation shall be achieved by safety structures, barriers or physical distance or by any combination of these methods. 6.2.1 Separation of redundant cable

48、s inside the I any given route, tray, conduit, duct, vertical duct or penetration shall carry or contain only cables of the same redundant group; for the I for plant failure and external failure events (see 4.4 and 4.5), such as fire or structure collapse, greater physical separation including barri

49、ers and/or safety structures shall be applied. 6.2.2 Lesser separation distances Lesser separation distances than those specified in 6.2.1 may be established by analysis of the proposed cable installation. The analysis should be based on tests performed to determine the flame retardant characteristics of the proposed cable installation considering features such as insulation and jacket materials, raceway fill, raceway types, and arrangements. For lesser separation distances in hazardous areas, the degree of hazards

展开阅读全文
相关资源
  • BS ISO IEC 29150-2011 Information technology Security techniques Signcryption《信息技术 安全技术 签密》.pdfBS ISO IEC 29150-2011 Information technology Security techniques Signcryption《信息技术 安全技术 签密》.pdf
  • BS ISO IEC 15408-1-2009 Information technology - Security techniques - Evaluation criteria for IT Security - Introduction and general model《信息技术 安全技术 IT安全评价准则 一.pdfBS ISO IEC 15408-1-2009 Information technology - Security techniques - Evaluation criteria for IT Security - Introduction and general model《信息技术 安全技术 IT安全评价准则 一.pdf
  • BS ISO 7295-1988+A1-2014 Tyre valves for aircraft Interchangeability dimensions《飞机轮胎汽门嘴 互换性尺寸》.pdfBS ISO 7295-1988+A1-2014 Tyre valves for aircraft Interchangeability dimensions《飞机轮胎汽门嘴 互换性尺寸》.pdf
  • BS ISO 15118-1-2013 Road vehicles Vehicle to grid communication interface General information and use-case definition《道路车辆 车辆到电力通讯接口 通用信息和使用案例定义》.pdfBS ISO 15118-1-2013 Road vehicles Vehicle to grid communication interface General information and use-case definition《道路车辆 车辆到电力通讯接口 通用信息和使用案例定义》.pdf
  • BS ISO 13765-2-2004 Refractory mortars - Determination of consistency using the reciprocating flow table method《耐熔灰浆 使用往复流动表法测定一致性》.pdfBS ISO 13765-2-2004 Refractory mortars - Determination of consistency using the reciprocating flow table method《耐熔灰浆 使用往复流动表法测定一致性》.pdf
  • BS ISO 10998-2008+A1-2014 Agricultural tractors Requirements for steering《农业拖拉机 操纵要求》.pdfBS ISO 10998-2008+A1-2014 Agricultural tractors Requirements for steering《农业拖拉机 操纵要求》.pdf
  • BS Z 9-1998 Space data and information transfer systems - Advanced orbiting systems - Networks and data links - Architectural specification《空间数据和信息传输系统 高级轨道系统 网络和数据链接 结构规范》.pdfBS Z 9-1998 Space data and information transfer systems - Advanced orbiting systems - Networks and data links - Architectural specification《空间数据和信息传输系统 高级轨道系统 网络和数据链接 结构规范》.pdf
  • BS Z 7-1998 Space data and information transfer systems - ASCII encoded English《空间数据和信息传输系统 ASCII 编码英语》.pdfBS Z 7-1998 Space data and information transfer systems - ASCII encoded English《空间数据和信息传输系统 ASCII 编码英语》.pdf
  • BS Z 5-1997 Space data and information transfer systems - Standard formatted data units - Control authority procedures《航天数据和信息发送系统 标准格式数据单元 控制授权程序》.pdfBS Z 5-1997 Space data and information transfer systems - Standard formatted data units - Control authority procedures《航天数据和信息发送系统 标准格式数据单元 控制授权程序》.pdf
  • BS Z 4-1997 Space data and information transfer systems - Standard formatted data units - Structure and construction rules《航天数据和信息传输系统 标准格式数据单元 结构和构造规则》.pdfBS Z 4-1997 Space data and information transfer systems - Standard formatted data units - Structure and construction rules《航天数据和信息传输系统 标准格式数据单元 结构和构造规则》.pdf
  • 猜你喜欢
    相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > BS

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1