1、 g49g50g3g38g50g51g60g44g49g42g3g58g44g55g43g50g56g55g3g37g54g44g3g51g40g53g48g44g54g54g44g50g49g3g40g59g38g40g51g55g3g36g54g3g51g40g53g48g44g55g55g40g39g3g37g60g3g38g50g51g60g53g44g42g43g55g3g47g36g58(EMC) requirementsThe European Standard EN 62310-2:2007 has the status of a British StandardICS 29.
2、200; 33.100Static transfer systems (STS) Part 2: Electromagnetic compatibility BRITISH STANDARDBS EN 62310-2:2007BS EN 62310-2:2007This British Standard was published under the authority of the Standards Policy and Strategy Committee on 30 March 2007 BSI 2007ISBN 978 0 580 50381 8Amendments issued s
3、ince publicationAmd. No. Date Commentssecretary.This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application.Compliance with a British Standard cannot confer immunity from legal obligations.National forewordThis British St
4、andard was published by BSI. It is the UK implementation of EN 62310-2:2007. It was derived by CENELEC from IEC 62310-2:2006.The CENELEC common modifications have been implemented at the appropriate places in the text and are indicated by tags (e.g. ).The UK participation in its preparation was entr
5、usted to Technical Committee PEL/22, Power electronics.A list of organizations represented on PEL/22 can be obtained on request to its EUROPEAN STANDARD EN 62310-2 NORME EUROPENNE EUROPISCHE NORM February 2007 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisa
6、tion Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B - 1050 Brussels 2007 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 62310-2:2007 E ICS 29.200; 33.100 English versi
7、on Static transfer systems (STS) - Part 2: Electromagnetic compatibility (EMC) requirements (IEC 62310-2:2006, modified) Systmes de transfert statique (STS) - Partie 2: Exigences pour la compatibilit lectromagntique (CEM) (CEI 62310-2:2006, modifie) Statische Transfersysteme (STS) - Teil 2: Anforder
8、ungen an die elektromagnetische Vertrglichkeit (EMV)(IEC 62310-2:2006, modifiziert) This European Standard was approved by CENELEC on 2006-09-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status
9、of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A
10、version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cypru
11、s, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. Foreword The text of document
12、22H/81/FDIS, future edition 1 of IEC 62310-2, prepared by SC 22H, Uninterruptible power systems (UPS), of IEC TC 22, Power electronic systems and equipment, was submitted to the IEC-CENELEC parallel vote. A draft amendment, prepared by the Technical Committee CENELEC TC 22X, Power electronics, was s
13、ubmitted to the formal vote. The combined texts were approved by CENELEC as EN 62310-2 on 2006-09-01. The following dates were fixed: latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2007-09-01 latest date by
14、 which the national standards conflicting with the EN have to be withdrawn (dow) 2009-09-01 This European Standard has been prepared under a mandate given to CENELEC by the European Commission and the European Free Trade Association and covers essential requirements of EC Directive 89/336/EEC. See A
15、nnex ZZ. Annexes ZA and ZZ have been added by CENELEC. _ Endorsement notice The text of the International Standard IEC 62310-2:2006 was approved by CENELEC as a European _ 2 EN 62310-2:2007Standard with agreed common modifications. CONTENTS 1 2 3 3.1 3.2 3.3 3.4 4 4.1 4.2 4.3 4.4 4.5 5 5.1 5.2 5.3 5
16、.4 6 6.1 6.2 6.3 6.4 6.5 Figure A.1 Circuit for disturbance voltage measurements on mains supply or STS Figure A.2 Test configuration for table-top equipment (conducted emission Figure A.3 Test configuration for floor-standing equipment (conducted emission 3 EN 62310-2:2007Scope.5 Normative referenc
17、es .6 Terms and definitions .7 General definitions 7 Circuit characteristics Specified values7 EMC definitions .9 Environments 9 STS categories.9 STS of category C1 .9 STS of category 2 .9 STS of category C3 .10 STS of category C4 .10 Categories and environment10 Emission 11 General requirements11 G
18、eneral measurement conditions 11 Conducted emissions 12 Radiated emissions .13 Immunity 13 General requirements and performance criteria.13 Basic immunity requirements high-frequency disturbances .14 Immunity to low-frequency signals.17 Immunity to power frequency magnetic field 17 Immunity to volta
19、ge dips, short interruptions and voltage variations.17 Annex A (normative) Electromagnetic emission Test methods18 Annex B (informative) Electromagnetic emission limits of magnetic field H field .29 Annex C (informative) Electromagnetic emission Limits of signal ports 31 Annex D (normative) Electrom
20、agnetic immunity Test methods .32 Annex E (informative) User installation testing (in situ testing).34 Bibliography35 Figure 1 Examples of ports 9 output .22 measurement).25 measurement).26 Annex ZA (normative) Normative references to international publications with their Annex ZZ (informative) Cove
21、rage of Essential Requirements of EC Directives38corresponding European publications.36Figure A.4 Test configuration for table-top equipment (radiated emission Figure A.5 Test configuration for floor-standing equipment (radiated emission Table 1 Limits of a.c. terminal interference voltage in the fr
22、equency range 0,15 MHz to 30 MHz for Category C2-STS, Category C1-STS equipment and Category C3-STS Table 5 Minimum immunity requirements for STS intended for STS of Category C2 4 EN 62310-2:2007requirement) .27 measurement).28 Figure B.1 Test set-up for measuring radiated disturbances.29 equipment.
23、12 Table 2 Limits of radiated emission in the frequency range 30 MHz to 1 000 MHz13 Table 3 Performance criteria for immunity tests .14 Table 4 Minimum immunity requirements for STSs intended for STS of Category C1 .15 and C316 Table B.1 STS which has a rated output current less than or equal to 16
24、A30 Table B.2 STS which has a rated output current greater than 16 A 30 Table C.1 Limits of signal ports31 STATIC TRANSFER SYSTEMS (STS) Part 2: Electromagnetic compatibility (EMC) requirements 1 Scope The IEC 62310 series applies to free standing operation a.c. static transfer systems (STS) intende
25、d to ensure the continuity of load supply through controlled transfer, with or without interruption of power, from two or more independent a.c. sources. The IEC 62310 series includes requirements for the switching elements, their control and protective elements, where applicable. The IEC 62310 serie
26、s also includes information for the overall integration of the STS and its accessories into the a.c. power network. This standard applies to systems up to 1 000 V a.c. which are intended to be used in single-phase, phase-phase or three-phase applications This part of IEC 62310 takes precedence over
27、all aspects of the generic standards, and no additional testing is necessary. The requirements have been selected so as to ensure an adequate level of Electromagnetic Compatibility (EMC) for STS at public and industrial locations. These levels cannot, however, cover extreme cases which may occur in
28、any location, but with extremely low probability of occurrence. It takes into account the differing test conditions necessary to encompass the range of physical sizes and power ratings of STS. A STS, whether presented as a unit or an assembly of units shall meet the relevant requirements of this par
29、t of IEC 62310 as a stand-alone product. EMC phenomena produced by any supply or load connected to the input or output of the STS equipment shall not be taken into account. This standard does not apply to: devices for d.c. source switching; single source systems; transfer systems using only electrom
30、echanical switching devices intended to be used in emergency power systems with interruption of the supply to the load during transfer; NOTE 1 Such equipment is covered by IEC 60947-6-1. automatic switching devices integrated into Uninterruptible Power Systems (UPS) covered by the IEC 62040 series.
31、NOTE 2 For STS intended to be used in vehicles, on board ships or aircraft, in tropical countries, for Emergency Power Systems (such as those used for health care facilities, fire fighting, emergency rescue, etc.), or at altitudes greater than 1 000 m, different requirements may be necessary. 5 EN 6
32、2310-2:2007This part of IEC 62310 is intended as a product standard allowing the EMC conformity assessment of products of categories C1, C2 and C3 as defined in Clause 4, before placing them on the market. Equipment of category C4 is treated as a fixed installation. Checking is generally done after
33、installation in its final place of use. Sometimes partial checking may be done before. See Annex E. This part of IEC 62310 concerns Electromagnetic Compatibility (EMC). See IEC 62310-1 for general and safety requirements. Special installation environments are not covered, nor are fault conditions of
34、 STS taken into account. This standard specifies: EMC requirements; test methods; minimum performance levels. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references
35、, the latest edition of the referenced document (including any amendments) applies. IEC 60050(161), International Electrotechnical Vocabulary (IEV) Chapter 161: Electromagnetic compatibility IEC 61000-2-2:2002, Electromagnetic compatibility (EMC) Part 2-2: Environment Compatibility levels for low-fr
36、equency conducted disturbances and signalling in public low-voltage power supply systems IEC 61000-3-2:2000, Electromagnetic compatibility (EMC) Part 3-2: Limits Limits for harmonic current emissions (equipment input current 16 A per phase) 2Amendment 1 (2001) Amendment 2 (2004) IEC 61000-4-1:2000,
37、Electromagnetic compatibility (EMC) Part 4-1: Overview of 61000-4 series IEC 61000-4-2:1995, Electromagnetic compatibility (EMC) Part 4-2: Testing and measure-ment techniques Electrostatic discharge immunity test 3Amendment 1 (1998) Amendment 2 (2000) IEC 61000-4-3:2002, Electromagnetic compatibilit
38、y (EMC) Part 4-3: Testing and measure-ment techniques Radiated, radio-frequency, electromagnetic field immunity test 4Amendment 1 (2002) IEC 61000-4-4:2004, Electromagnetic compatibility (EMC) Part 4-4: Testing and measure-ment techniques Electrical fast transient/ burst immunity test 2A consolidate
39、d edition 2.2 exists, including IEC 61000-3-2:2000, its Amendment 1 (2001) and its Amendment 2 (2004) . 3A consolidated edition 1.2 exists, including IEC 61000-4-2:1995, its Amendment 1 (1998) and its Amendment 2 (2000) . 4A consolidated edition 2.1 exists, including IEC 61000-4-3:2002 and its Amend
40、ment 1 (2002). 6 EN 62310-2:2007IEC 61000-4-5:1995, Electromagnetic compatibility (EMC) Part 4-5: Testing and measure-ment techniques Surge immunity test 5Amendment 1 (2000) IEC 61000-4-6:2004, Electromagnetic compatibility (EMC) Part 4-6: Testing and measure-ment techniques Immunity to conducted di
41、sturbances induced by radio frequency fields IEC 61000-4-8:1993, Electromagnetic compatibility (EMC) Part 4-8: Testing and measure-ment techniques Power frequency magnetic field immunity test. Basic EMC publication Amendment 1:2000 IEC 62310-1: 2005, Static Transfer Systems (STS) Part 1: General and
42、 safety requirements. CISPR 16-1-1:2003 Specification for radio disturbance and immunity measuring apparatus and methods Part 1: Radio disturbance and immunity measuring apparatus Measuring apparatus CISPR 16-1-2, Specification for radio disturbance and immunity measuring apparatus and methods Part
43、1-2: Radio disturbance and immunity measuring apparatus Ancillary equipment Conducted disturbances CISPR 16-1-5, Specification for radio disturbance and immunity measuring apparatus and methods Part 1-5: Radio disturbance and immunity measuring apparatus Antenna calibration test sites for 30 MHz to
44、1 000 MHz CISPR 22:2005, Information technology equipment Radio disturbance characteristics Limits and methods of measurement 3 Terms and definitions For the purposes of this document, the following terms and definitions apply. 3.1 General definitions For general definitions, the terms and definitio
45、ns given in IEC 62310-1, as well as the terms and definitions in IEC 60050 (161) related to EMC and to relevant phenomena apply. 3.2 Circuit characteristics Specified values 3.2.1 rating set of rated values and operating conditions of a machine or a device or equipment IEV 151-16-11, modified 5A con
46、solidated edition 1.1 exists, including IEC 61000-4-5:1995 and its Amendment 1 (2000). 7 EN 62310-2:20073.2.2 rated value quantity value assigned, generally by a manufacturer, for a specified operating condition of a component, device or equipment IEV 151-16-08, modified 3.2.3 nominal value suitable
47、 approximate quantity value used to designate or identify a component, device or equipment IEV 151-16-09, modified 3.2.4 rated voltage input or output voltage (for three-phase supply, the phase-to-phase voltage) as declared by the manufacturer 3.2.5 rated voltage range input or output voltage range
48、as declared by the manufacturer expressed by its lower and upper rated voltages 3.2.6 rated current input or output current of the equipment as declared by the manufacturer 3.2.7 rated frequency operating frequency as declared by the manufacturer 3.2.8 rated frequency range input or output frequency
49、 range as declared by the manufacturer, expressed by its lower and upper rated frequencies 3.2.9 linear load load where the current drawn from the supply is defined by the relationship: I = U/Z where I is the load current; U is the supply voltage; Z is the constant impedance 3.2.10 harmonic components components of the harmonic content as expressed in