1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationEnergy performance of lamp controlgearPart 1: Controlgear for fluorescent lamps Method of measurement to determine the total input power of controlgear circuits and the efficienc
2、y of the controlgearBS EN 62442-1:2011Copyright European Committee for Electrotechnical Standardization Provided by IHS under license with CENELECNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-National forewordThis British Standard is the UK implementation of EN 6
3、2442-1:2011, incorporating CENELEC corrigendum May 2012. It is identical to IEC 62442-1:2011. It supersedes BS EN 50294:1998, which will be with-drawn on 16 November 2014. CENELEC corrigendum May 2012 adds supersession information to the CENELEC foreword and title page.The UK participation in its pr
4、eparation was entrusted by Technical Committee CPL/34, Lamps and Related Equipment, to Subcommittee CPL/34/3, Auxiliaries for lamps.A list of organizations represented on this subcommittee can be obtained on request to its secretary.This publication does not purport to include all the necessary prov
5、isions of a contract. Users are responsible for its correct application. The British Standards Institution 2012.Published by BSI Standards Limited 2012 ISBN 978 0 580 55708 8 ICS 29.140.99;17.220.20Compliance with a British Standard cannot confer immunity from legal obligations.This British Standard
6、 was published under the authority of the Standards Policy and Strategy Committee on 31 May 2012.Amendments/corrigenda issued since publicationDate Text affectedBRITISH STANDARDBS EN 62442-1:2011Copyright European Committee for Electrotechnical Standardization Provided by IHS under license with CENE
7、LECNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-EUROPEAN STANDARD EN 62442-1 NORME EUROPENNE EUROPISCHE NORM November 2011 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elek
8、trotechnische Normung Management Centre: Avenue Marnix 17, B - 1000 Brussels 2011 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 62442-1:2011 E ICS 29.140.99 English version Energy performance of lamp controlgear - Part 1: Contro
9、lgear for fluorescent lamps - Method of measurement to determine the total input power of controlgear circuits and the efficiency of the controlgear (IEC 62442-1:2011) Performance nergtique des appareillages de lampes - Partie 1: Appareillages des lampes fluorescence - Mthode de mesure pour la dterm
10、ination de la puissance dentre totale des circuits dappareillage et du rendement des appareillages (CEI 62442-1:2011) Energieeffizienz von Lampenbetriebsgerten - Teil 1: Betriebsgerte fr Leuchtstofflampen - Messverfahren zur Bestimmung der Gesamteingangsleistung von Betriebsgerteschaltungen und des
11、Wirkungsgrades von Betriebsgerten (IEC 62442-1:2011) This European Standard was approved by CENELEC on 2011-11-16. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without
12、any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other
13、language made by translation under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
14、 the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. Supersedes EN 50294:1998 + A1:20
15、01 + A2:2003Copyright European Committee for Electrotechnical Standardization Provided by IHS under license with CENELECNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-EN 62442-1:2011 - 2 - Foreword The text of document 34C/987/FDIS, future edition 1 of IEC 62442-1
16、, prepared by SC 34C, “Auxiliaries for lamps“, of IEC/TC 34, “Lamps and related equipment“ was submitted to the IEC-CENELEC parallel vote and approved by CENELEC as EN 62442-1:2011. The following dates are fixed: latest date by which the document has to be implemented at national level by publicatio
17、n of an identical national standard or by endorsement (dop) 2012-08-16 latest date by which the national standards conflicting with the document have to be withdrawn (dow) 2014-11-16 Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights.
18、 CENELEC and/or CEN shall not be held responsible for identifying any or all such patent rights. Endorsement notice The text of the International Standard IEC 62442-1:2011 was approved by CENELEC as a European Standard without any modification. BS EN 62442-1:2011This document supersedes EN 50294:199
19、8 + A1:2001 + A2:2003.Copyright European Committee for Electrotechnical Standardization Provided by IHS under license with CENELECNot for ResaleNo reproduction or networking permitted without license from IHS-,-,- 3 - EN 62442-1:2011 Annex ZA (normative) Normative references to international publica
20、tions with their corresponding European publications The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) appli
21、es. NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD applies. Publication Year Title EN/HD Year IEC 60081 - Double-capped fluorescent lamps - Performance specifications EN 60081 - IEC 60901 - Single-capped fluorescent lamps - Pe
22、rformance specifications EN 60901 - IEC 60921 2004 Ballasts for tubular fluorescent lamps - Performance requirements EN 60921 2004 IEC 60929 + corr. September 2011 2011 AC and/or DC-supplied electronic control gear for tubular fluorescent lamps - Performance requirements EN 60929 2011 IEC 61347-2-3
23、- Lamp controlgear - Part 2-3: Particular requirements for a.c. and/or d.c. supplied electronic control gear for fluorescent lamps EN 61347-2-3 - IEC 61347-2-8 - Lamp controlgear - Part 2-8: Particular requirements for ballasts for fluorescent lamps EN 61347-2-8 - BS EN 62442-1:2011Copyright Europea
24、n Committee for Electrotechnical Standardization Provided by IHS under license with CENELECNot for ResaleNo reproduction or networking permitted without license from IHS-,-,- 2 62442-1 IEC:2011 CONTENTS 1 Scope . 5 2 Normative references 5 3 Terms and definitions . 6 4 General 8 4.1 Applicability .
25、8 4.2 Declaration of ballast lumen factor . 8 4.3 Dimmable controlgear 8 4.4 Multi-wattage and/or multi-lamp controlgear . 8 4.5 Accuracy of measurement . 8 4.6 Sampling of controlgear for testing . 8 4.7 Number of samples 9 4.8 Conditioning of lamps 9 4.9 Test voltages and frequencies . 9 5 Method
26、of measurement and calculation of total input power of controlgear lamp circuits and the efficiency of controlgear 9 5.1 Correction for ballast lumen factor . 9 5.2 Method of measurement 9 5.3 Measurement and calculation of the total input power of magnetic wire wound controlgear lamp circuits . 10
27、5.4 Calculation of the efficiency of magnetic wire wound controlgear 10 5.5 Measurement and calculation of the total input power of electronic controlgear lamp circuits 10 5.6 Calculation of the efficiency of electronic controlgear . 12 5.7 Measuring the standby power. 12 Annex A (normative) Energy
28、performance measurement setup . 13 Annex B (informative) Application of the reference ballast when assessing lamps in electronic operation . 17 Bibliography 18 Figure 1 Configuration of lamp and photocell sensor . 12 Figure A.1 Measurement of magnetic wire wound controlgear lamp circuits 13 Figure A
29、.2 Measurement of a.c. supplied electronic controlgear lamp circuits 14 Figure A.3 Test setup for measuring standby power 14 Figure A.4 Side view of light output measurement system . 15 Figure A.5 Top view of light output measurement system 15 Table 1 Typical nominal electricity supply details for s
30、ome regions 9 BS EN 62442-1:2011Copyright European Committee for Electrotechnical Standardization Provided by IHS under license with CENELECNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-62442-1 IEC:2011 5 ENERGY PERFORMANCE OF LAMP CONTROLGEAR Part 1: Controlgear
31、 for fluorescent lamps Method of measurement to determine the total input power of controlgear circuits and the efficiency of the controlgear 1 Scope This part of IEC 62442 defines a measurement and calculation method of the total input power for controlgear lamp circuits when operating with their a
32、ssociated fluorescent lamp(s). The calculation method for the efficiency of the lamp controlgear is also defined. This International Standard applies to electrical controlgear lamp circuits consisting only of the controlgear and the lamp(s). It is intended for use on a.c. supplies up to 1 000 V at 5
33、0 Hz or 60 Hz. NOTE Requirements for testing individual controlgear during production are not included. It specifies the measurement method for the total input power and the calculation method of the controlgear efficiency for all controlgear used for domestic and normal commercial purposes operatin
34、g with the following fluorescent lamps: linear fluorescent lamps; single-ended (compact) fluorescent lamps; other general purpose fluorescent lamps. This International Standard does not apply to: controlgear which form an integral part of the lamp; controllable wire-wound magnetic controlgear; lumin
35、aires, which rely on additional optical performance aspects. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (
36、including any amendments) applies. IEC 60081, Double-capped fluorescent lamps Performance specifications IEC 60901, Single-capped fluorescent lamps Performance requirements IEC 60921:2004, Ballasts for tubular fluorescent lamps Performance requirements IEC 60929:2011, AC and/or DC-supplied electroni
37、c control gear for tubular fluorescent lamps Performance requirements IEC 61347-2-3, Lamp control gear Part 2-3: Particular requirements for a.c. and/or d.c. supplied electronic control gear for fluorescent lamps IEC 61347-2-8, Lamp controlgear Part 2-8: Particular requirements for ballasts for fluo
38、rescent lamps BS EN 62442-1:2011Copyright European Committee for Electrotechnical Standardization Provided by IHS under license with CENELECNot for ResaleNo reproduction or networking permitted without license from IHS-,-,- 6 62442-1 IEC:2011 3 Terms and definitions For the purposes of this document
39、, the following terms and definitions apply. 3.1 nominal value suitable approximate quantity value used to designate or identify a component, device or equipment 3.2 limiting value the greatest or smallest admissible value of one of the quantities 3.3 rated value quantity value for specified operati
40、ng conditions of a component, device or equipment The value and conditions are specified in the relevant standard or assigned by the manufacturer or responsible vendor NOTE For the different kinds of operation, rated electrical values are given on the lamp data sheets as: rated electrical values und
41、er “electrical characteristics”, if the lamp is defined for 50 Hz / 60 Hz operation only, rated electrical values under “electrical characteristics”, if the lamp is defined for high frequency ( 20 kHz) operation only, rated electrical values and typical electrical values, if the lamp is defined simu
42、ltaneously for 50 Hz / 60 Hz operation and high frequency operation for 50 Hz / 60 Hz operation: rated electrical values under “electrical characteristics”, and for high frequency operation: rated electrical values under “typical lamp characteristics”. 3.4 controlgear one or more components between
43、the supply and one or more lamps which may serve to transform the supply voltage, limit the current of the lamp(s) to the required value, provide starting voltage and preheating current, prevent cold starting, correct power factor or reduce radio interference 3.5 electromagnetic controlgear controlg
44、ear which by means of inductance, or a combination of inductance and capacitance, serves mainly to limit the current of the lamp(s) to the required value Frequency of the lamp operation is the same as supply frequency. 3.6 electronic controlgear a.c. and/or d.c. supplied to a.c. invertor including s
45、tabilizing elements for starting and operating one or more tubular fluorescent lamps, generally at high frequency 3.7 fluorescent lamp discharge lamp of the low pressure mercury type, in which most of the light is emitted by one or several layers of phosphors excited by the ultra-violet radiation fr
46、om the discharge 3.8 controlgear lamp circuit electrical circuit, or part thereof, normally built in a luminaire, consisting of the controlgear and lamp(s) BS EN 62442-1:2011Copyright European Committee for Electrotechnical Standardization Provided by IHS under license with CENELECNot for ResaleNo r
47、eproduction or networking permitted without license from IHS-,-,-62442-1 IEC:2011 7 3.9 reference ballast special ballast, either inductive for lamps for operation on a.c. mains frequencies, or resistive for lamps for operation on high frequency It is designed for the purpose of providing comparison
48、 standards for use in testing ballasts, for the selection of reference lamps and for testing regular production lamps under standardized conditions. It is essentially characterized by the fact that, at its rated frequency, it has a stable voltage/current ratio which is relatively uninfluenced by variations in current, temperature and magnetic surroundings, as outlined in IEC 60929. NOTE Annex B provides details of calculating the reference ballast characteristics and the method of operation with the reference ballast. 3.10 referenc