1、May 2017 English price group 8No part of this translation may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS 91.140.80!%eBi“2663170www.din.deDIN E
2、N 1253-5Gullies for buildings Part 5: Gullies with light liquids closure;English version EN 12535:2017,English translation of DIN EN 1253-5:2017-05Ablufe fr Gebude Teil 5: Ablufe mit Leichtflssigkeitssperre;Englische Fassung EN 12535:2017,Englische bersetzung von DIN EN 1253-5:2017-05Avaloirs et sip
3、hons pour btiments Partie 5: Siphons avec obturateur pour liquides lgers;Version anglaise EN 12535:2017,Traduction anglaise de DIN EN 1253-5:2017-05SupersedesDIN EN 12535:200403www.beuth.deDocument comprises 11 pagesDTranslation by DIN-Sprachendienst.In case of doubt, the German-language original sh
4、all be considered authoritative.05.17 DIN EN 1253-5:2017-05 2 A comma is used as the decimal marker. National foreword This document (EN 1253-5:2017) has been prepared by Technical Committee CEN/TC 165 “Waste water engineering” (Secretariat: DIN, Germany). The preliminary work was done by Working Gr
5、oup WG 11 “Gratings, covers and other ancillary components for use inside buildings” of CEN/TC 165. The responsible German body involved in its preparation was DIN-Normenausschuss Wasserwesen (DIN Standards Committee Water Practice), Working Committee NA 119-05-11 AA “Gully devices, gullies, backflo
6、w devices and air admittance valves for use inside buildings (CEN/TC 165/WG 11)”. Amendments This standard differs from DIN EN 1253-5:2004-03 as follows: a) the Scope, certain functional requirements, the method of marking and the classification according to the flow rates have been modified followi
7、ng the introduction of EN 1253-1 and EN 1253-3; b) the standard has been editorially revised. Previous editions DIN 4043: 1961-07, 1982-10 DIN EN 1253-5: 2004-03 EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 1253-5 February 2017 ICS 91.140.80 Supersedes EN 1253-5:2003English Version Gullies f
8、or buildings - Part 5: Gullies with light liquids closure Avaloirsetsiphonspourbtiments-Partie5:Siphons avec obturateur pour liquides lgers Ablufe fr Gebude - Teil 5: Ablufe mit Leichtflssigkeitssperren This European Standard was approved by CEN on 14 December 2016. CEN members are bound to comply w
9、ith the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Man
10、agement Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same s
11、tatus as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Ma
12、lta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussel
13、s 2017 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 1253-5:2017 EEN 1253-5:2017 (E) 2 Contents Page European foreword . 3 1 Scope 4 2 Normative references 4 3 Terms and definitions . 4 4 Types 4 5 Materials . 4 6 Requirements .
14、5 6.1 General 5 6.2 Inflow . 5 6.3 Security height . 5 6.4 Tightness 5 6.5 Maintenance 6 6.6 Flow rates . 6 7 Test methods 7 7.1 General 7 7.2 Closing ability and tightness . 7 7.3 Security height . 7 8 Marking . 7 9 Evaluation of conformity 8 Bibliography 9 DIN EN 1253-5:2017-05 EN 1253-5:2017 (E)
15、3 European foreword This document (EN 1253-5:2017) has been prepared by Technical Committee CEN/TC 165 “Wastewater engineering”, the secretariat of which is held by DIN. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsem
16、ent, at the latest by August 2017, and conflicting national standards shall be withdrawn at the latest by August 2017. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN shall not be held responsible for identifying any or all su
17、ch patent rights. This document supersedes EN 1253-5:2003. This is the fifth part in EN 1253, a series of standards relating to different types of floor gullies, roof drains and access covers for drainage systems inside buildings. The EN 1253 series under the main title Gullies for buildings actuall
18、y consists of the following parts: Part 1: Trapped floor gullies with a depth water seal of at least 50 mm; Part 2: Roof drains and floor gullies without trap; Part 3: Evaluation of conformity; Part 4: Access covers; Part 5: Gullies with light liquids closure. Since the latest versions of EN 1253-5
19、the most significant technical changes are the following: a) introduction of the new standards on trapped floor gullies with a depth of water seal of at least 50 mm (EN 1253-1) and evaluation of conformity (EN 1253-3); b) amendment of scope, classification, requirements as well as methods of marking
20、. According to the CEN-CENELEC Internal Regulations, the national standards organisations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, G
21、ermany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. DIN EN 1253-5:2017-05 EN 1253-5:2017 (E) 4 1 Scope This European Standard spe
22、cifies requirements for the design, construction, performance, application and marking as well as test methods of factory made gullies with a light liquid closure for buildings. Light liquid closures for buildings are applied to avoid uncontrolled discharge of light liquids into drainage systems in
23、case of emergency. This European Standard does not apply to installations for separation of light liquids covered by EN 858-1. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated referen
24、ces, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1253-1:2015, Gullies for buildings - Part 1: Trapped floor gullies with a depth water seal of at least 50 mm EN 1253-3, Gullies for buildings - Part 3: Ev
25、aluation of conformity 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 1253-1:2015 and the following apply. 3.1 gully with a light liquid closure trapped floor gully with closure device which prevents the light liquid from entering the drainage system
26、 3.2 light liquid closure device which automatically closes the gully outlet when a certain level of light liquid is present 3.3 light liquid liquid with a density not greater than 0,95 g/cm3which is actually or practically insoluble in water and unsaponifiable Note 1 to entry: Such liquids are, e.g
27、. petrol, diesel fuel, fuel oil. 4 Types Type A: Gully with an integrated light liquid closure with a flow rate in accordance with Table 1 for the unlimited use in gravity drainage systems. Type B: Gully with light liquid closure which is incorporated as an accessory, with a minimum flow rate given
28、in Table 1, which may be reduced up to 30 % for use in gravity drainage systems. 5 Materials All material in contact with the light liquid and the wastewater shall be resistant to light liquids and to wastewater. DIN EN 1253-5:2017-05 EN 1253-5:2017 (E) 5 6 Requirements 6.1 General A gully with ligh
29、t liquid closure shall fulfil all requirements given in EN 1253-1, except for flow rates, and the following requirements given in 6.2 to 6.6. The manufacturer shall supply all the appropriate information concerning the use of the trapped gully with a light liquid closure, e.g. handling, transport, t
30、emporary storage and instructions for installation, operation and maintenance. 6.2 Inflow The inflow shall be through the grating on the top of the gully. Inlets under the grating and behind the light liquid closure are not allowed. The light liquid closure shall be sufficiently protected against du
31、st, dirt, inflow and others which could impair functioning. 6.3 Security height When the light liquid closure has closed the gully, there shall be a security distance between the sealing and the separating line between water and light liquid of 30 mm. Dimensions in millimetres Key 1 grating 4 sealin
32、g level 7 static water level 2 light liquid layer 5 float 3 parting line light liquid water 6 float guiding device Figure 1 Gully with light liquid closure 6.4 Tightness When tested in accordance with 7.2, the leakage shall be less than 0,1 l/h. DIN EN 1253-5:2017-05 EN 1253-5:2017 (E) 6 6.5 Mainten
33、ance Closure devices shall be easily removable for servicing. 6.6 Flow rates Where a gully with a light liquid closure device is designed, the gully flow rate shall be as given in Table 1. Table 1 Minimum flow rates Nominal size of outletaFloor gullies (qgrate) DN/OD DN/ID Minimum flow rate l/s Head
34、 of water h mm 32 0,4 20 30 0,4 40 0,6 40 0,6 50 0,8 50 0,8 63 0,8 75 0,8 70 0,8 75 0,8 90 0,8 100 1,4 100 1,4 110 1,4 125 2,8 125 2,8 150 4,0 160 4,0 aAll dimensions not mentioned in this table shall be tested with the next higher dimension. DIN EN 1253-5:2017-05 EN 1253-5:2017 (E) 7 7 Test methods
35、 7.1 General The gully shall, by means of the test methods in EN 1253-1, demonstrate the fulfilling the requirements given in EN 1253-1 and the following. 7.2 Closing ability and tightness After the flow rate test in accordance with EN 1253-1 add light liquid with a density corresponding to that ind
36、icated by the manufacturer 0,015 g/cm3at 12 C, slowly (0,1 l/s) into the gully, until the closure device closes, but at least up to the top of the grating. Place a container under the pipe outlet, and determine after 1 h the amount of water and light liquid in the container. 7.3 Security height When
37、 the closure device has closed (see 7.2), measure by suitable methods the distance between the sealing and the separating line between water and light liquid. 8 Marking Gullies with a light liquid closure device and their components shall bear the following clear and durable markings, for example, c
38、ast on, by engraving, painting, stamping or labelling (including electronic recognition labelling) as indicated in Table 2: a) EN 1253-5; b) name and/or mark of the manufacturer; c) period of manufacture (coded or not); d) identification of independent certification body, where applicable; e) identi
39、fication of DN, load class and type. DIN EN 1253-5:2017-05 EN 1253-5:2017 (E) 8 Table 2 Location of marking of gullies with a light liquid closure device ItemsdGully body Grating Float device Components Package EN 12535 X XaXaXaX Manufacturers name or mark X XaX Period of manufacture X Independent c
40、ertification bodybX Load class XcX DN XaX TypeeXa X aIf possible. bWhere applicable. cFor the classes H and K the marking is optional. dFurther marking may be added (e.g. for application). The marking shall be visible where possible, after the unit has been installed. eOnly for condition as specifie
41、d in Clause 4, Type B. Where the application of the marking would be detrimental to the production and/or functioning of the product, the marking shall be included on the packaging. 9 Evaluation of conformity The evaluation of conformity shall be provided as given in EN 1253-3. DIN EN 1253-5:2017-05 EN 1253-5:2017 (E) 9 Bibliography 1 EN 858-1, Separator systems for light liquids (e.g. oil and petrol) - Part 1: Principles of product design, performance and testing, marking and quality control DIN EN 1253-5:2017-05