1、March 2008DEUTSCHE NORM English price group 12No part of this standard may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS 23.060.99!$M38“1421621ww
2、w.din.deDDIN EN 15081Industrial valves Mounting kits for part-turn valve actuator attachmentEnglish version of DIN EN 15081:2008-03Industriearmaturen Montagestze fr Anschlsse von Schwenkantrieben an ArmaturenEnglische Fassung DIN EN 15081:2008-03SupersedesDIN EN 15081:2008-01www.beuth.deDocument com
3、prises 20 pagesDIN EN 15081:2008-03 2 National foreword This standard has been prepared by Technical Committee CEN/TC 69 “Industrial valves” (Secretariat: AFNOR, France). The responsible German body involved in its preparation was the Normenausschuss Armaturen (Valves Standards Committee), Technical
4、 Committee NA 003-00-11 AA Schnittstellen zu Antrieben. Amendments This standard differs from DIN EN 15081:2008-01 as follows: a) (German version only:) In the header “prEN 15081:2007 (D)” has been corrected to read “EN 15081:2007 (D)”. b) The Foreword has been modified. Previous editions DIN EN 150
5、81: 2008-01 EUROPEAN STANDARDNORME EUROPENNEEUROPISCHE NORMEN 15081October 2007ICS 23.060.99English VersionIndustrial valves - Mounting kits for part-turn valve actuatorattachmentRobinetterie industrielle - Kits de montage pourraccordement des actionneurs fraction de tourIndustriearmaturen - Montage
6、stze fr Anschlsse vonSchwenkantrieben an ArmaturenThis European Standard was approved by CEN on 26 August 2007.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alter
7、ation. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the CEN Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by transl
8、ationunder the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as theofficial versions.CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,France, Germany, Gr
9、eece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMIT EUROPEN DE NORMALISATIONEUROPISCHES KOMITEE FR NORMUNGManagement
10、Centre: rue de Stassart, 36 B-1050 Brussels 2007 CEN All rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 15081:2007: EEN 15081:2007 (E) 2 Contents Page Foreword3 1 Scope 4 2 Normative references 4 3 Terms and definitions .4 4 Design requirem
11、ents .5 4.1 General5 4.2 Materials .5 4.3 Design temperature .6 4.4 Environmental corrosion protection6 4.5 Mounting kit6 4.6 Coupling .7 4.7 Designation 7 4.8 Position indicator.8 4.9 Buried service 8 4.10 Safety requirement (mechanical/thermal protection) 8 4.11 Orientation8 4.12 Additional anti-r
12、otation means.8 4.13 Valve/actuator package maintenance8 5 Dimensions.9 5.1 Bracket9 5.2 Valve top flange .10 5.3 Coupling .10 5.4 Spools and adapter flanges12 6 Marking .12 6.1 General12 6.2 Mandatory information12 6.3 Optional information .12 7 Documentation.12 7.1 Language 12 7.2 Product document
13、ation 12 Annex A (normative) Coupling axial clearance13 Annex B (informative) Proposed stem details for ball and butterfly valves15 B.1 General15 B.2 Proposed stem details for ball valves .16 B.3 Proposed stem details for butterfly valves .16 Bibliography 18 DIN EN 15081:2008-03 : EN 15081:2007 (E)
14、3 Foreword This document (EN 15081:2007) has been prepared by Technical Committee CEN/TC 69 “Industrial valves”, the secretariat of which is held by AFNOR. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the la
15、test by April 2008, and conflicting national standards shall be withdrawn at the latest by April 2008. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all suc
16、h patent rights. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,
17、 Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. DIN EN 15081:2008-03 : EN 15081:2007 (E) 4 1 Scope This European Standard provides requirements for metallic mounting kits for
18、 part-turn on-off valves and actuator attachments to enable safe and reliable operation. It includes all components transmitting torques from actuators to valves with a maximum flange torque up to 16 000 Nm (up to F30 flange type). It applies to part-turn valves and actuators having attachment flang
19、es and drive components as described in EN ISO 5211. It includes recommendations and methods for design and environmental corrosion protection. When reference is made to this European Standard, all the requirements apply, unless otherwise agreed between the purchaser and the manufacturer/supplier, p
20、rior to order. For the scope of this European Standard, the term “Valve” covers valve or shaft extension top-flange. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated ref
21、erences, the latest edition of the referenced document (including any amendments) applies. EN 736-1:1995, Valves Terminology Part 1: Definition of types of valves EN 736-2:1997, Valves Terminology Part 2: Definition of components of valves EN 736-3:1999, Valves Terminology Part 3: Definition of term
22、s EN ISO 5211:2001, Industrial valves Part-turn valve actuator attachments (ISO 5211:2001) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 736-1:1995, EN 736-2:1997 and EN 736-3:1999 and the following apply. 3.1 mounting kit kit comprising an intermed
23、iate support, coupling and bolting 3.2 intermediate support mechanical component (bracket, spool, adapter flange) that allows the attachment between a part-turn valve and actuator 3.3 coupling driven component that allows torque transmission from an actuator driving component to the valve shaft and
24、which includes a position indicator 3.4 axial coupling clearance clearance to ensure that there is axial movement between the actuator and the valve stem to avoid thrust being applied between the driving and driven components DIN EN 15081:2008-03 EN 15081:2007 (E) 5 3.5 part-turn actuator actuator t
25、hat transmits torque to the valve for a rotation of one revolution or less and which does not have to be capable of withstanding thrust 3.6 valve top flange part of the valve which allows the attachment of actuating devices and ancillaries via an intermediate support 3.7 valve shaft part of the valv
26、e transmitting the drive torque to the obturator 3.8 part-turn actuator attachment attachment interface of the actuator which includes: flange necessary to attach the part-turn actuator to the intermediate support; driving component of the part-turn actuator necessary to attach it to the coupling or
27、 to the driven component of the valve, which may be an integral part or a removable component of the actuator 3.9 maximum actuator output torque maximum output torque of the actuator available at the maximum motive energy input 3.10 maximum allowable shaft torque (MAST) maximum torque that can be ap
28、plied to all the driven components, without damage and/or plastic deformation being sustained by any part 4 Design requirements 4.1 General Part-turn actuators shall be in accordance with EN ISO 5211. 4.2 Materials Unless otherwise agreed, mounting kit materials shall be: for intermediate supports,
29、of cast iron (CI), carbon steel (CS) or stainless steel (SS); for coupling, see performance classes (Table 2); for bolting (environmental corrosion categories according to Table 1): categories C2 and C3: stainless steel or a suitably corrosion protected carbon steel; categories C4 and C5-I: stainles
30、s steel; other categories: material to be specified by the purchaser. Special care shall be taken for material selection, in the event of environmental critical conditions. DIN EN 15081:2008-03 :EN 15081:2007 (E) 6 4.3 Design temperature The mounting kit shall be designed for operation at an ambient
31、 temperature range between 20 C and + 60 C. 4.4 Environmental corrosion protection Mounting kits shall be protected against corrosion by suitable material selection and/or surface treatment. The manufacturers technical documentation shall specify the choice of the materials and/or the type of the su
32、rface treatment. Surface treatment system for carbon or low-alloy steels (e.g. according to EN 10025) shall be chosen according to the classification categories given in Table 1. Test assessment and test procedures are the responsibility of the manufacturer. NOTE Table 1 may be used to define the co
33、rrosion category and help the mounting kit manufacturers to define the surface treatment for corrosion protection. Table 1 Environmental corrosion categories Typical environments Corrosion category Exterior Interior C2 (low) Atmospheres with low level of pollution. Mostly rural areas. Unheated build
34、ings where condensation may occur, e.g. depots, sport halls. C3 (medium) Urban and industrial atmospheres, moderate sulphur dioxide pollution. Coastal areas with low salinity. Production rooms with high humidity and some air pollution, e.g. food-processing plants, laundries, breweries. C4 (high) Ind
35、ustrial areas and coastal areas with moderate salinity. Chemical plants, swimming pools, coastal shipyards. C5-I (very high - industrial) Industrial areas with high humidity and aggressive atmosphere. Buildings or areas with almost permanent condensation and with high pollution. C5-M (very high mari
36、ne) Coastal and offshore areas with high salinity. Buildings or areas with almost permanent condensation and with high pollution. Immersed in water or buried in soil: Im 1 (Immersed in fresh water) River installations, hydro-electric power plants. Im 2 (Immersed in sea or brackish water) Harbour are
37、as and offshore structures. Im 3 (buried in soil) Buried pipelines NOTE This table is taken from EN ISO 12944-2:1998. 4.5 Mounting kit 4.5.1 Stiffness The dimensions of the mounting kit given in this European Standard ensure that the maximum flange torque - given in Table 1 of EN ISO 5211 - can be t
38、ransmitted safely. For non-vertically mounted actuators, the user may need to design an extra support. DIN EN 15081:2008-03 EN 15081:2007 (E) 7 When specified by the purchaser, the mounting kit shall also be designed for external loads (e.g. stepping load, earthquake, wind loading, additional plant
39、induced dynamic loads). In this case, for instance, the thickness as given in Table 3 may be increased. 4.5.2 Intermediate support style The intermediate support provides two equal or different attachment interfaces (actuator and valve), as per EN ISO 5211. The most common type is a “rectangular” br
40、acket, as defined in 5.1. The “rectangular“ type is predominantly manufactured from a rectangular or square tube in compliance with EN 10219-2 or EN 10210-2. The “rectangular“ type can also be cast, fabricated or machined. Other commonly used types are the following: “adapter flange”: generally manu
41、factured as one piece from casting, forging, plate or bar. It shall be provided with a suitable venting device; “spool type“: generally manufactured from two flanges that correspond to the mating faces of valve and actuator, connected together by a piece of tube. The assembly is welded together to f
42、orm a spool piece. The “spool“ type can also be in one piece: cast, forged or machined. The spool shall be provided with a suitable venting device and/or with a suitable opening to visualise the coupling position. Other types of intermediate support may be used provided they meet the requirements of
43、 this European Standard. 4.6 Coupling The design of the coupling shall ensure the maximum transmissible torque (as specified in EN ISO 5211), can be delivered to the valve shaft. The coupling performance class shall be specified by the purchaser in accordance with Table 2. The design of both couplin
44、g ends (driven/driving) shall avoid any contact between moving and fixed parts. Table 2 Coupling performance classes Coupling tolerances driven end / driving end Performance designation Examples of material types Minimum yield strength type N/mm2Class 1 Class 2 Group A Austenitic stainless steels, n
45、ickel based alloys, carbon steel 200 g9 / H10 g6 / H7 Group B Duplex steels, martensitic stainless steels 450 g9 / H10 g6 / H7 4.7 Designation Mounting kits shall be designated as follows: a) mounting kit style: adaptor flange (AF), bracket (BR), spool (SP) or other (OT) followed by the intermediate
46、 support material as per 4.2 (CI, CS or SS); b) flange designations according to EN ISO 5211 (actuator flange type/valve flange type); c) coupling drive identification (first for the actuator and second for the valve): DIN EN 15081:2008-03 :EN 15081:2007 (E) 8 coupling driven (actuator side) diagona
47、l square “D” designation, as per EN ISO 5211, followed by dimension saas per Table 4; coupling driving (valve side) designation either to Clause 6 of EN ISO 5211:2001 (additional capital letters with actual dimensions d7or s) or to specified / agreed dimensions, followed by actual dimensions l8and l
48、7in mm (see Figure A.1); d) environmental corrosion category as per Table 1; e) performance group/class as per Table 2. EXAMPLE EN 15081 - BR/CI - F07/F05 - D 14/H 11-11-24 - C3 - B1. NOTE The designation is not a marking requirement. 4.8 Position indicator The coupling design shall have a provision
49、 for a clear and permanently marked indicator to show whether the valve is open or closed: special attention, during the assembly, should be taken when installing square drive couplings. 4.9 Buried service When buried service is required, design details and corrosion protection shall be agreed between the purchaser and manufacturer/supplier. 4.10 Safety requirement (mechanical/thermal protection) The adapter flange or the spool shall have a provision for venting any leakage that may occur through the stem seal of the valve