1、September 2014Translation by DIN-Sprachendienst.English price group 26No part of this translation may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).I
2、CS 13.220.20!%:B“2239831www.din.deDDIN EN 54-3Fire detection and fire alarm systems Part 3: Fire alarm devices Sounders;English version EN 54-3:2014,English translation of DIN EN 54-3:2014-09Brandmeldeanlagen Teil 3: Feueralarmeinrichtungen Akustische Signalgeber;Englische Fassung EN 54-3:2014,Engli
3、sche bersetzung von DIN EN 54-3:2014-09Systmes de dtection et dalarme incendie Partie 3: Dispositifs sonores dalarme feu;Version anglaise EN 54-3:2014,Traduction anglaise de DIN EN 54-3:2014-09SupersedesDIN EN 54-3:2006-08See start of applicationwww.beuth.deIn case of doubt, the German-language orig
4、inal shall be considered authoritative.Document comprises 76 pages08.14 DIN EN 54-3:2014-09 2 A comma is used as the decimal marker. Start of application It should be noted that, in Germany, CE conformity marking of construction products will be permitted once this standard has been listed in the Of
5、ficial Journal of the European Union and/or the Bundesanzeiger (German Federal Gazette) and from the date given therein. For further information, users of this standard should refer to the websites of the European Commission or of the relevant building authority. The standard which this document rep
6、laces, DIN EN 54-3:2006-08, may be used in parallel with this standard during a specified transition period where such has been laid down in the Official Journal of the European Union and/or the Bundesanzeiger (German Federal Gazette). DIN EN 54-3:2014-09 3 National foreword This document (EN 54-3:2
7、014) has been prepared by Technical Committee CEN/TC 72 “Fire detection and fire alarm systems” (Secretariat: BSI, United Kingdom). The responsible German body involved in its preparation was the DIN-Normenausschuss Feuerwehrwesen (DIN Standards Committee Firefighting and Fire Protection), Working G
8、roup NA 031-02-01-14 AK Signalgeber of Working Committee NA 031-02-01 AA Brandmelde- und Feueralarmanlagen. The requirements for the construction and use of fire alarm sounders and voice sounders according to DIN EN 54-3 intended for use in fire detection and fire alarm systems in buildings are spec
9、ified in national Standards DIN 14675 and DIN VDE 0833-2 (VDE 0833-2) (see National Annex NA). General information on auditory alarm devices is given in DIN 33404-3 and DIN EN ISO 7731 (see National Annex NA). Certification of conformity of these products with the requirements specified in this Euro
10、pean Standard is based on conformity evaluation of the products carried out by “Notified Bodies” in accordance with the EU Directive No. 305/2011 (see Annex ZA). Amendments This standard differs from DIN EN 54-3:2006-08 as follows: a) normative references have been updated; b) structure and drafting
11、 of terms and definitions have been revised; c) the standard has been editorially revised; d) requirements have been revised; e) testing, assessment and sampling methods have been revised; f) all annexes have been revised; g) references to national regulations have been supplemented; h) the standard
12、 has been brought in line with EU Construction Products Regulation No. 305/2011. Previous editions DIN EN 54-3: 2001-10, 2006-08 DIN EN 54-3/A1: 2002-09 DIN EN 54-3:2014-09 4 National Annex NA (informative) Bibliography DIN 14675, Fire detection and fire alarm systems Design and operation DIN 33404-
13、3, Danger signals for workplaces Auditory danger signals Unified emergency signal; technical requirements of safety, testing DIN EN ISO 7731, Ergonomics Danger signals for public and work areas Auditory danger signals DIN VDE 0833-2 (VDE 0833-2), Alarm systems for fire, intrusion and hold up Part 2:
14、 Requirements for fire alarm systems EUV 305/2011, Regulation (EU) No 305/2011 of the European Parliament and of the Council of 9 March 2011 laying down harmonised conditions for the marketing of construction products and repealing Council Directive 89/106/EEC ISO 8201, Acoustics Audible emergency e
15、vacuation signal EN 54-3July 2014 ICS 13.220.20 Supersedes EN 54-3:2001English Version Fire detection and fire alarm systems - Part 3: Fire alarm devices -Sounders Systmes de dtection et dalarme incendie - Partie 3: Dispositifs sonores dalarme feu Brandmeldeanlagen - Teil 3: Feueralarmeinrichtungen
16、Akustische Signalgeber This European Standard was approved by CEN on 8 May 2014. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and b
17、ibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the res
18、ponsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav R
19、epublic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey andUnited Kingdom. CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Bru
20、ssels 2014 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 54-3:2014 EEUROPEAN COMMITTEE FOR STANDARDIZATIONCOMIT EUROPEN DE NORMALISATIONEUROPISCHES KOMITEE FR NORMUNGEUROPEAN STANDARDNORME EUROPENNEEUROPISCHE NORMEN 54-3:2014 (E)
21、 2 Contents PageForeword 5 Introduction .7 1 Scope 8 2 Normative references 8 3 Terms, definitions and abbreviations 9 3.1 Definitions 9 3.2 Abbreviations 11 4 Requirements 11 4.1 Compliance 11 4.2 Operational reliability . 11 4.2.1 Duration of operation . 11 4.2.2 Provision for external conductors
22、11 4.2.3 Flammability of materials . 11 4.2.4 Enclosure protection 12 4.2.5 Access . 12 4.2.6 Manufacturers adjustment 12 4.2.7 On-site adjustment of the operation mode 12 4.2.8 Software controlled sounders . 13 4.3 Performance parameters under fire conditions 14 4.3.1 Sound pressure level . 14 4.3.
23、2 Frequencies and sound pattern 14 4.3.3 Synchronisation 14 4.3.4 Performance of voice sounders 15 4.3.5 Voice sounders sequence timing 15 4.4 Durability of performance parameters under fire conditions 15 4.4.1 Temperature resistance . 15 4.4.2 Humidity resistance 15 4.4.3 Shock and vibration resist
24、ance . 16 4.4.4 Corrosion resistance 16 4.4.5 Electrical stability . 16 5 Testing, assessment and sampling methods 16 5.1 General . 16 5.1.1 Atmospheric conditions for tests . 16 5.1.2 Operating conditions for tests 17 5.1.3 Mounting arrangements . 17 5.1.4 Tolerances . 17 5.1.5 Provision for tests
25、17 5.1.6 Test schedule 18 5.1.7 Reproducibility 19 5.2 Operational reliability . 20 5.2.1 Duration of operation . 20 5.2.2 Provision for external conductors 20 5.2.3 Flammability of materials . 20 5.2.4 Enclosure protection 21 5.2.5 Access . 22 5.2.6 Manufacturers adjustments 22 5.2.7 On site adjust
26、ments of the operating mode 22 5.2.8 Requirements for software controlled devices . 22 DIN EN 54-3:2014-09EN 54-3:2014 (E) 3 5.3 Performance parameters under fire conditions . 22 5.3.1 Sound pressure level 22 5.3.2 Frequencies and sound patterns . 23 5.3.3 Synchronisation 23 5.3.4 Performance of voi
27、ce sounders . 24 5.3.5 Voice sounder sequence timing 25 5.4 Durability of performance parameters under fire conditions . 26 5.4.1 Heat resistance 26 5.4.2 Humidity resistance 29 5.4.3 Shock and vibration resistance . 31 5.4.4 Corrosion resistance, SO2corrosion (endurance) . 35 5.4.5 Electrical stabi
28、lity 36 6 Assessment and verification of constancy of performance (AVCP) . 37 6.1 General . 37 6.2 Type testing . 37 6.2.1 General . 37 6.2.2 Test samples, testing and compliance criteria 38 6.2.3 Test reports 38 6.3 Factory production control (FPC) 38 6.3.1 General . 38 6.3.2 Requirements . 39 6.3.
29、3 Product specific requirements . 41 6.3.4 Initial inspection of factory and FPC . 42 6.3.5 Continuous surveillance of FPC 42 6.3.6 Procedure for modifications. 43 6.3.7 One-off products, pre-production products, (e.g. prototypes) and products produced in very low quantities 43 7 Classification and
30、designation 44 8 Marking, labelling and packaging 44 Annex A (normative) Sound pressure level for fire alarm sounders . 45 A.1 General . 45 A.2 Mounting arrangements 45 A.3 Instrumentation . 45 A.4 Background noise level 45 A.5 Measurement of sound pressure level 45 Annex B (normative) Comparative s
31、ound pressure level test during environmental conditioning . 49 B.1 General . 49 B.2 Test chamber . 49 B.2.1 Size 49 B.2.2 Shape 49 B.2.3 Rigidity 50 B.2.4 Surface treatment 50 B.3 Mounting arrangements 50 B.4 Instrumentation . 50 B.5 Background noise level 50 B.6 Test procedure . 50 DIN EN 54-3:201
32、4-09EN 54-3:2014 (E) 4 B.6.1 Number and positioning of microphones 50 B.6.2 Measurement of sound pressure level . 51 Annex C (informative) Data supplied with sounders 54 Annex D (informative) Sound patterns used in some European countries 55 D.1 Introduction . 55 D.2 Standards references . 55 D.3 In
33、formation on sound patterns 56 D.3.1 Introduction . 56 D.3.2 ISO 8201 Evacuate signal 56 D.3.3 DIN 33404-3 Unified emergency signal . 56 D.3.4 BS 5839-1 Evacuate signal 57 D.3.5 BS 5839-1 Alert signal 57 D.3.6 NF S32-001 Evacuate signal 57 D.3.7 NEN 2575 Evacuate signal . 58 Annex E (informative) Co
34、mparison of flammability test requirements in various standards 59 E.1 Introduction . 59 E.2 Relevant standards . 59 E.3 Vertical burning tests . 59 E.4 Horizontal burning tests 60 E.4.1 ISO 1210, IEC 60695-11-10 and UL 94 . 60 E.4.2 ISO 10351, IEC 60695-11-20 and UL 94 . 61 Annex ZA (informative) C
35、lauses of this European Standard addressing the provisions of the EU Construction Products Regulation . 62 ZA.1 Scope and relevant characteristics 62 ZA.2 Procedure for assessment and verification of constancy of performance (AVCP) of sounders 63 ZA.2.1 System of AVCP 63 ZA.2.2 Declaration of perfor
36、mance (DoP) 64 ZA.2.2.1 General . 64 ZA.2.2.2 Content . 64 ZA.2.2.3 Example of DoP . 65 ZA.3 CE marking and labelling . 68 Bibliography . 72 DIN EN 54-3:2014-09EN 54-3:2014 (E) 5 Foreword This document (EN 54-3:2014) has been prepared by Technical Committee CEN/TC 72 “Fire detection and fire alarm s
37、ystems”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by January 2015, and conflicting national standards shall be withdrawn at the latest by April 2016. A
38、ttention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 54-3:2001. This document has been prepared under a mandate
39、given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document. EN 54-3 has been revised so as to align with the secon
40、d answer of CEN/TC 72 to Mandate M/109. EN 54-3 includes new clauses and annexes as follows: Requirements for software controlled devices (5.2.8); Clause 6 Assessment and verification of constancy of performance (AVCP); Clause 7 Classification and designation; Clause 8 Marking, labelling and packagi
41、ng; Annex C Data supplied with sounders; Annex D (informative) Sound patterns used in some European countries; Annex E (informative) Comparison of flammability test requirements in various standards. The previous Annex C dealt with the requirements and test methods for voice sounders. The content of
42、 this annex has been integrated in the main body of the standard, specifically under 4.3.3, 4.3.4, 4.3.5, 5.3.3. 5.3.4 and 5.3.5. In addition, Annex ZA has been revised to align with the Construction Products Regulation (CPR). EN 54, Fire detection and fire alarm systems, consists of the following p
43、arts: Part 1: Introduction Part 2: Control and indicating equipment Part 3: Fire alarm devices Sounders Part 4: Power supply equipment Part 5: Heat detectors Point detectors Part 7: Smoke detectors Point detectors using scattered light, transmitted light or ionization Part 10: Flame detector Point d
44、etectors DIN EN 54-3:2014-09EN 54-3:2014 (E) 6 Part 11: Manual call points Part 12: Smoke detectors Line detector using an optical light beam Part 13: Compatibility assessment of system components Part 14: Guidelines for planning, design, installation, commissioning, use and maintenance Part 15: Poi
45、nt detectors using a combination of detected phenomena Part 16: Voice alarm control and indicating equipment Part 17: Short circuit isolators Part 18: Input/output devices Part 20: Aspirating smoke detectors Part 21: Alarm transmission and fault warning routine equipment Part 22: Line-type heat dete
46、ctors Part 23: Fire alarm devices Visual alarms Part 24: Components of voice alarm systems Loudspeakers Part 25: Components using radio links and system requirements Part 26: Carbon monoxide detectors Point detectors Part 27: Duct smoke detectors Part 28: Non-resettable (digital) line type heat dete
47、ctors Part 29: Multi-sensor fire detectors - Point detectors using a combination of smoke and heat sensors Part 30: Multi-sensor fire detectors - Point detectors using a combination of carbon monoxide and heat sensors Part 31: Multi-sensor detector Point detectors using a combination of smoke, carbo
48、n monoxide and optionally heat sensors Part 32: Guidelines for the planning, design, installation, commissioning, use and maintenance of voice alarm systems NOTE This list includes standards that are in preparation and other standards may be added. For current status of published standards refer to
49、www.cen.eu. According to the CEN-CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg,