1、AMSC N/A FSC 5925 W-C-375/6D 14 May 2009 SUPERSEDING W-C-375/6C 04 August 2004 FEDERAL SPECIFICATION SHEET CIRCUIT BREAKERS, MOLDED CASE, BRANCH CIRCUIT AND SERVICE, TYPE I, SERIES TRIP, TWO POLE (15 THROUGH 125 AMPERES) The General Services Administration has authorized the use of this federal spec

2、ification sheet by all federal agencies. The complete requirements for procuring circuit breakers described herein shall consist of this document and the latest issue in effect of W-C-375. FIGURE 1. Interface and physical dimensions (15 through 70 amperes). INCH-POUND Provided by IHSNot for ResaleNo

3、 reproduction or networking permitted without license from IHS-,-,-W-C-375/6D 2 Inches mm Inches mm Inches mm Inches mm Inches mm .003 .08 .031 .79 .235 5.97 .562 14.27 1.478 37.54 .008 .20 .070 1.78 .243 6.17 .565 14.35 1.480 37.59 .010 .25 .110 2.79 .250 6.35 .594 15.09 2.187 55.55 .013 .33 .125 3

4、.18 .280 7.11 .70 17.8 2.312 58.72 .015 .38 .130 3.30 .290 7.37 .700 17.78 2.402 61.01 .016 .41 .140 3.56 .320 8.13 .719 18.26 2.500 63.50 .02 .5 .141 3.58 .375 9.52 .950 24.13 2.59 65.8 .020 .51 .187 4.75 .424 10.77 .952 24.18 3.000 76.20 .03 .8 .218 5.54 .429 10.90 1.17 29.7 3.045 77.34 .030 .76 .

5、230 5.84 .495 12.57 1.128 28.65 NOTES: 1. Dimensions are in inches. 2. Metric equivalents are given for general information only. 3. Unless otherwise specified, tolerances are 0.01 (0.25 mm) for two-place decimals and 0.005 (0.13 mm) for three-place decimals and 1 on angles. 4. Load terminals shall

6、be suitable for copper (CU) and aluminum (AL) wire. FIGURE 1. Interface and physical dimensions (80 through 125 amperes) - Continued. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-W-C-375/6D 3 REQUIREMENTS: Interface and physical dimensions: See fi

7、gure 1 and 2. Trip indication: See figure 1 and 2. Common trip: All poles shall make and break simultaneously when operated manually or automatically. Electrical: Interrupting current rating: 10,000 amperes. Voltage rating: 120/240 V ac. Currency rating: See table I. Frequency: 60 hertz. Calibration

8、: At +40C, 3C Enclosure for overload, endurance, and short circuit tests: Cutler Hammer catalog number CH2L70FP (15-70 amperes) and CH2L125FP (80-125 amperes). Supersession and cross reference: See table II. TABLE I. Part or Identifying Numbers (PINs) and current rating. Government PIN Current ratin

9、g Commercial superseded PIN CAGE 56365 WC375/06-001 15 See figure 1 WC375/06-002 20 See figure 1 WC375/06-003 25 See figure 1 WC375/06-004 30 See figure 1 WC375/06-005 40 See figure 1 WC375/06-006 50 See figure 1 WC375/06-007 60 See figure 1 WC375/06-008 70 See figure 1 WC375/06-009 80 See figure 2

10、WC375/06-010 90 See figure 2 WC375/06-011 100 See figure 2 WC375/06-012 125 See figure 2 WC375/06-013 35 See figure 1 WC375/06-014 45 See figure 1 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-W-C-375/6D 4 TABLE II. Supersession and cross reference

11、. Government PIN 1/ Commercial superseded PIN CAGE 27191 WC365/06-001 CH215 WC365/06-002 220 WC365/06-003 225 WC365/06-004 230 WC365/06-005 240 WC365/06-006 250 WC365/06-007 260 WC365/06-008 270 WC365/06-009 280 WC365/06-010 290 WC365/06-011 2100 WC365/06-012 2125 WC365/06-013 235 WC365/06-014 245 1

12、/ Replace CH type with sandalwood handles (5,000 AIC) and red handles (10,000 AIC). The margins of this specification sheet are marked with vertical lines to indicate where changes from the previous issue were made. This was done as a convenience only and the Government assumes no liability whatsoev

13、er for any inaccuracies in these notations. Bidders and contractors are cautioned to evaluate the requirements of this document based on the entire content irrespective of the marginal notations and relationship to the last previous issue. MILITARY INTERESTS: CIVIL AGENCY COORDINATING ACTIVITY: Cust

14、odians: GSA - FSS Navy - YD Air Force - 85 Preparing activity: DLA - CC DLA - CC Review Activities: (Project 5925-2009-018) Navy - MC, OS, SH Air Force - 99 NOTE: The activities listed above were interested in this document as of the date of this document. Since organizations and responsibilities can change, you should verify the currency of the information above using the ASSIST Online database at http:/assist.daps.dla.mil. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-