EN 13141-7-2010 en Ventilation for buildings - Performance testing of components products for residential ventilation - Part 7 Performance testing of a mechanical supply and exhaus.pdf

上传人:eventdump275 文档编号:707322 上传时间:2019-01-03 格式:PDF 页数:40 大小:1.42MB
下载 相关 举报
EN 13141-7-2010 en Ventilation for buildings - Performance testing of components products for residential ventilation - Part 7 Performance testing of a mechanical supply and exhaus.pdf_第1页
第1页 / 共40页
EN 13141-7-2010 en Ventilation for buildings - Performance testing of components products for residential ventilation - Part 7 Performance testing of a mechanical supply and exhaus.pdf_第2页
第2页 / 共40页
EN 13141-7-2010 en Ventilation for buildings - Performance testing of components products for residential ventilation - Part 7 Performance testing of a mechanical supply and exhaus.pdf_第3页
第3页 / 共40页
EN 13141-7-2010 en Ventilation for buildings - Performance testing of components products for residential ventilation - Part 7 Performance testing of a mechanical supply and exhaus.pdf_第4页
第4页 / 共40页
EN 13141-7-2010 en Ventilation for buildings - Performance testing of components products for residential ventilation - Part 7 Performance testing of a mechanical supply and exhaus.pdf_第5页
第5页 / 共40页
点击查看更多>>
资源描述

1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationBS EN 13141-7:2010Ventilation for buildings Performance testing ofcomponents/products forresidential ventilationPart 7: Performance testing of a mechanicalsupply and exhaust vent

2、ilation units(including heat recovery) for mechanicalventilation systems intended for singlefamily dwellingBS EN 13141-7:2010 BRITISH STANDARDNational forewordThis British Standard is the UK implementation of EN 13141-7:2010.It supersedes BS EN 13141-7:2004 which is withdrawn.The UK participation in

3、 its preparation was entrusted to TechnicalCommittee RHE/2, Ventilation for buildings, heating and hot waterservices.A list of organizations represented on this committee can beobtained on request to its secretary.This publication does not purport to include all the necessaryprovisions of a contract

4、. Users are responsible for its correctapplication. BSI 2011ISBN 978 0 580 63430 7ICS 91.140.30Compliance with a British Standard cannot confer immunity fromlegal obligations.This British Standard was published under the authority of theStandards Policy and Strategy Committee on 28 February 2011.Ame

5、ndments issued since publicationDate Text affectedBS EN 13141-7:2010EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 13141-7 November 2010 ICS 91.140.30 Supersedes EN 13141-7:2004English Version Ventilation for buildings - Performance testing of components/products for residential ventilation -

6、Part 7: Performance testing of a mechanical supply and exhaust ventilation units (including heat recovery) for mechanical ventilation systems intended for single family dwellings Ventilation des btiments - Essais de performance des composants/produits pour la ventilation des logements - Partie 7: Es

7、sais de performance des centrales double flux (y compris la rcupration de chaleur) pour les systmes de ventilation mcaniques prvus pour des logements individuels Lftung von Gebuden - Leistungsprfungen von Bauteilen/Produkten fr die Lftung von Wohnungen - Teil 7: Leistungsprfung von mechanischen Zulu

8、ft- und Ablufteinheiten (einschlielich Wrmerckgewinnung) fr mechanische Lftungsanlagen in Wohneinheiten (Wohnung oder Einfamilienhaus) This European Standard was approved by CEN on 25 September 2010. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the condit

9、ions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member. This European Standard exists in three

10、 official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions. CEN members are the national standards bodies of Au

11、stria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EU

12、ROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2010 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 13141-7:2010: EBS EN 13141

13、-7:2010EN 13141-7:2010 (E) 2 Contents page Foreword 3Introduction . 51 Scope 52 Normative references 63 Terms, definitions and classification 63.1 Terms and definitions . 73.2 Categories of heat exchangers 84 Symbols and abbreviations 95 Requirements . 96 Test methods 106.1 General 106.2 Performance

14、 testing of aerodynamic characteristics 116.2.1 Leakages . 116.2.2 Air flow/pressure curve . 136.2.3 Filter bypass . 146.3 Performance testing of thermal characteristics . 146.3.1 General 146.3.2 Temperature and humidity ratios . 156.3.3 Heat pump performance . 186.3.4 Combined heat pump and air-to-

15、air heat exchanger performance 186.4 Performance testing of acoustic characteristics . 196.4.1 Noise radiated through the casing of the unit 196.4.2 Sound power level in duct connections of the unit . 206.5 Electric power input. 227 Test results . 237.1 Test report 237.2 Product specifications 237.3

16、 Leakages . 237.4 Air flow/pressure curve . 247.5 Heat pump exhaust air/outdoor air performances . 247.6 Temperature ratios 247.7 Acoustic characteristics . 257.8 Electric power input. 25Annex A (informative) Example of some possible arrangements of heat recovery heat exchanger and/or heat pumps for

17、 category I . 26Annex B (normative) Pressure leakage test method . 28B.1 External leakage. 28B.2 Internal leakage test 28Annex C (normative) Tracer gas test method 30C.1 General method for rating purposes . 30C.2 Augmented method for measuring instantaneous recirculation of ducted units under differ

18、ent operating conditions (optional) . 31C.3 Testing orders for tracer gas tests 32Bibliography 36BS EN 13141-7:2010EN 13141-7:2010 (E) 3 Foreword This document (EN 13141-7:2010) has been prepared by Technical Committee CEN/TC 156 “Ventilation for buildings”, the secretariat of which is held by BSI.

19、This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by May 2011, and conflicting national standards shall be withdrawn at the latest by May 2011. Attention is drawn to the possibility that some of the el

20、ements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 13141-7:2004. Compared to the 2004 version, changes have been made to the following (sub)clauses, tables and annexe

21、s: modification of the test temperatures to be similar to those of heat pump; possibility of measuring supply and exhaust ventilation and heat pump; suppression of reference to EN 308 for heat exchangers particular test conditions, this standard define its own conditions; introduction of tracer gas

22、method for leakages; dependence of leakages under/over pressure configurations on fan position in airflow; obligation of reporting the two temperature ratios (on exhaust and supply air); possibility of doing an optional test by measuring on the outdoor side of the building while the measure is made

23、on the inside side of the building in the mandatory test (exhaust and supply air flow rate); possibility of giving humidity ratios, like for PAC, this allowed to test enthalpy heat exchangers; review of value for balanced mass flows at 3 %, over 3% declaration of unbalanced unit and report of the di

24、sbalance value; setting of the declared maximum air volume flow at 50 Pa by default in lack of other declaration; addition of the declared minimum air volume flow at Ptud/2 and minimum setting; creation of a reference point at Ptud/2 and 70 % of declared maximum air volume flow; correction of the te

25、mperature ratios considering flow rate ratios. This standard is a part of a series of standards on residential ventilation. It has a parallel standard referring to the performance characteristics of the components/products for residential ventilation. The position of this standard in the field of st

26、andards for the mechanical building services is shown in Figure 1. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, E

27、stonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. BS EN 13141-7:2010EN 13141-7:2010 (E) 4 Mechanical Building Service

28、s Control systems Ventilation and air conditioning systems Heating systems Ductwork Air terminal devices Air handling units Mechanical and natural residential ventilation Design criteria for the indoor environment System performance Installation Components/products for residential ventilation Requir

29、ed and optional performance characteristics Performance testing of components/products for residential ventilation Simplified calculation methods for residential ventilation systems Design and dimensioning for residential ventilation systems Performance testing and installation checks for residentia

30、l ventilation systems Part 1: Externally and internally mounted air transfer devices Part 2: Exhaust and supply air terminal devices Part 3: Range hoods for residential use Part 4: Fans used in residential ventilation systems Part 5: Cowls and roof outlet terminal devices Part 6: Exhaust ventilation

31、 system packages used in a single dwelling Part 7: Mechanical supply and exhaust ventilation units (including heat recovery) for mechanical ventilation systems intended for single family dwellings Part 8: Performance testing of un-ducted mechanical supply and exhaust ventilation units (including hea

32、t recovery) for mechanical ventilation systems intended for a single room Part 9: Externally mounted humidity controlled air transfer device Part 10: Humidity controlled extract air terminal device Figure 1 Position of EN 13141-7 in the field of the mechanical building services BS EN 13141-7:2010EN

33、13141-7:2010 (E) 5 Introduction This European Standard specifies methods for the performance testing of components used in residential ventilation systems to establish the performance characteristics as identified in EN 13142. This European Standard does not contain any information on ductwork and f

34、ittings, which are covered by other European Standards. The standard can be used for the following applications: laboratory testing; attestation purposes. 1 Scope This part of EN 13141 specifies the laboratory test methods and test requirements for the testing of aerodynamic, thermal and acoustic pe

35、rformance, and the electrical performance characteristic of a mechanical supply and exhaust ventilation units used in a single dwelling. It covers unit that contain at least, within one or more casing: supply and exhaust air fans; air filters; air-to-air heat exchanger and/or Extract Air-to-Outdoor

36、Air heat pump for extract air heat recovery; control system. Such unit can be provided in more than one assembly, the separate assemblies of which are designed to be used together. The different possible arrangements of heat recovery heat exchangers and/or heat pumps are described in Annex A. This s

37、tandard does not deal with non-ducted units or reciprocating heat exchangers. This standard does not deal with units that supply several dwellings. This standard does not cover ventilation systems that may also provide water space heating and hot water. This standard does not cover units including c

38、ombustion engine driven compression heat pumps and absorption heat pumps. Electrical safety requirements are given in EN 60335-2-40 and EN 60335-2-80. BS EN 13141-7:2010EN 13141-7:2010 (E) 6 2 Normative references The following referenced documents are indispensable for the application of this Europ

39、ean Standard. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 306, Heat exchangers Methods of measuring the parameters necessary for establishing the performance EN 12792:2003, Ventilat

40、ion for buildings Symbols, terminology and graphical symbols EN 13141-4, Ventilation for buildings Performance testing of components/products for residential ventilation Part 4: Fans used in residential ventilation systems EN 14511-2, Air conditioners, liquid chilling packages and heat pumps with el

41、ectrically driven compressors for space heating and cooling Part 2: Test conditions EN 14511-3, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling Part 3: Test methods EN 14511-4, Air conditioners, liquid chilling packages and

42、 heat pumps with electrically driven compressors for space heating and cooling Part 4: Requirements EN ISO 3741, Acoustics Determination of sound power levels of noise sources using sound pressure Precision methods for reverberation rooms (ISO 3741:1999, including Cor 1:2001) EN ISO 3743-1, Acoustic

43、s Determination of sound power levels of noise sources Engineering methods for small, movable sources in reverberant fields Part 1: Comparison method for hard-walled test rooms (ISO 3743-1:1994) EN ISO 3743-2, Acoustics Determination of sound power levels of noise sources using sound pressure Engine

44、ering methods for small, movable sources in reverberant fields Part 2: Methods for special reverberation test rooms (ISO 3743-2:1994) EN ISO 3744, Acoustics Determination of sound power levels of noise sources using sound pressure Engineering method in an essentially free field over a reflecting pla

45、ne (ISO 3744:1994) EN ISO 3745, Acoustics Determination of sound power levels of noise sources using sound pressure Precision methods for anechoic and semi-anechoic rooms (ISO 3745:2003) EN ISO 5135, Acoustics Determination of sound power levels of noise from air-terminal devices, air-terminal units

46、, dampers and valves by measurement in a reverberation room (ISO 5135:1997) EN ISO 5136, Acoustics Determination of sound power radiated into a duct by fans and other air-moving devices In-duct method (ISO 5136:2003) EN ISO 9614-1, Acoustics Determination of sound power levels of noise sources using

47、 sound intensity Part 1: Measurement at discrete points (ISO 9614-1:1993) EN ISO 9614-2, Acoustics Determination of sound power levels of noise sources using sound intensity Part 2: Measurement by scanning (ISO 9614-2:1996) 3 Terms, definitions and classification For the purposes of this document, t

48、he terms and definitions given in EN 12792:2003 and the following apply. BS EN 13141-7:2010EN 13141-7:2010 (E) 7 3.1 Terms and definitions 3.1.1 external leakage leakage to or from the air flowing inside the casing of the unit to or from the surrounding air 3.1.2 internal leakage leakage inside the

49、unit between the exhaust and the supply air flows 3.1.3 filter bypass leakage air flow around filter cells 3.1.4 declared maximum air volume flow air volume flow corresponding to the declared total pressure of the unit at the maximum setting for standard air conditions (20 C, 101325 Pa) 3.1.5 declared minimum air vol