1、BRITISH STANDARDBS EN 15004-10:2008Fixed firefighting systems Gas extinguishing systems Part 10: Physical properties and system design of gas extinguishing systems for IG-541 extinguishantICS 13.220.20g49g50g3g38g50g51g60g44g49g42g3g58g44g55g43g50g56g55g3g37g54g44g3g51g40g53g48g44g54g54g44g50g49g3g4
2、0g59g38g40g51g55g3g36g54g3g51g40g53g48g44g55g55g40g39g3g37g60g3g38g50g51g60g53g44g42g43g55g3g47g36g58BS EN 15004-10:2008This British Standard was published under the authority of the Standards Policy and Strategy Committee on 31 October 2008 BSI 2008ISBN 978 0 580 59951 4National forewordThis Britis
3、h Standard is the UK implementation of EN 15004-10:2008. It supersedes BS ISO 14520-15:2005 which is withdrawn. The UK participation in its preparation was entrusted by Technical Committee FSH/18, Fixed firefighting systems, to Subcommittee FSH/18/6, Gaseous extinguishing media and systems.A list of
4、 organizations represented on this committee can be obtained on request to its secretary.This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application.Compliance with a British Standard cannot confer immunity from legal obl
5、igations.Amendments/corrigenda issued since publicationDate CommentsEUROPEAN STANDARDNORME EUROPENNEEUROPISCHE NORMEN 15004-10June 2008ICS 13.220.20English VersionFixed firefighting systems - Gas extinguishing systems - Part 10:Physical properties and system design of gas extinguishingsystems for IG
6、-541 extinguishant (ISO 14520-15:2005, modified)Installations fixes de lutte contre lincendie - Installationsdextinction gaz - Partie 10 : Proprits physiques etconception des systmes pour agent extincteur IG-541(ISO 14520-15:2005, modifie)Ortsfeste Brandbekmpfungsanlagen - Lschanlagen mitgasfrmigen
7、Lschmitteln - Teil 10: PhysikalischeEigenschaften und Anlagenauslegung fr FeuerlschmittelIG-541 (ISO 14520-15:2005, modifiziert)This European Standard was approved by CEN on 26 April 2008.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giv
8、ing this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the CEN Management Centre or to any CEN member.This European Standard exists in three official versi
9、ons (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as theofficial versions.CEN members are the national standards bodies of Austria, Belgium, Bu
10、lgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDI
11、ZATIONCOMIT EUROPEN DE NORMALISATIONEUROPISCHES KOMITEE FR NORMUNGManagement Centre: rue de Stassart, 36 B-1050 Brussels 2008 CEN All rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 15004-10:2008: EEN 15004-10:2008 (E) 2 Contents Page Forewo
12、rd3 Foreword of ISO 14520-15:2005 5 1 Scope 6 2 Normative references 6 3 Terms and definitions .6 4 Characteristics and uses 6 4.1 General6 4.2 Use of IG-541 systems 7 5 Safety of personnel9 6 System design10 6.1 Fill pressure10 6.2 Superpressurization 14 6.3 Extinguishant quantity 14 BS EN 15004-10
13、:2008EN 15004-10:2008 (E) 3 Foreword This document (EN 15004-10:2008) has been prepared by Technical Committee CEN/TC 191 “Fixed firefighting systems”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identi
14、cal text or by endorsement, at the latest by December 2008, and conflicting national standards shall be withdrawn at the latest by December 2008. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held
15、 responsible for identifying any or all such patent rights. The text of the International Standard ISO 14520-15:2005 from Technical Committee ISO/TC 21 “Equipment for fire protection and fire fighting“ of the International Organization for Standardization (ISO) has been taken over as a European Stan
16、dard by Technical Committee CEN/TC 191 “Fixed firefighting systems“, the secretariat of which is held by BSI, with common modifications which are indicated by a straight line in the margin of the text. This European Standard will consist of the following parts, under the general title Fixed firefigh
17、ting systems Gas extinguishing systems: Part 1: Design, installation and maintenance (ISO 14520-1, modified) Part 2: Physical properties and system design of gas extinguishing systems for FK-5-1-12 extinguishant (ISO 14520-5, modified) Part 3: Physical properties and system design of gas extinguishi
18、ng systems for HCFC Blend A extinguishant (ISO 14520-6, modified) Part 4: Physical properties and system design of gas extinguishing systems for HFC 125 extinguishant (ISO 14520-8, modified) Part 5: Physical properties and system design of gas extinguishing systems for HFC 227ea extinguishant (ISO 1
19、4520-9, modified) Part 6: Physical properties and system design of gas extinguishing systems for HFC 23 extinguishant (ISO 14520-10, modified) Part 7: Physical properties and system design of gas extinguishing systems for IG-01 extinguishant (ISO 14520-12, modified) Part 8: Physical properties and s
20、ystem design of gas extinguishing systems for IG-100 extinguishant (ISO 14520-13, modified) Part 9: Physical properties and system design of gas extinguishing systems for IG-55 extinguishant (ISO 14520-14, modified) Part 10: Physical properties and system design of gas extinguishing systems for IG-5
21、41 extinguishant (ISO 14520-15, modified) The International Standards ISO 14520-2 and ISO 14520-11, which dealt with CF3I and HFC 236fa extinguishants, respectively, have not been implemented by CEN, as CF3I extinguishant is only valid for local BS EN 15004-10:2008EN 15004-10:2008 (E) 4 application
22、and HFC 236fa extinguishant is only applicable for portable fire extinguishers and local application, respectively, which is not covered by the scope. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this Europe
23、an Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United K
24、ingdom. BS EN 15004-10:2008EN 15004-10:2008 (E) 5 Foreword of ISO 14520-15:2005 ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies (ISO member bodies). The work of preparing International Standards is normally carried out through ISO techn
25、ical committees. Each member body interested in a subject for which a technical committee has been established has the right to be represented on that committee. International organizations, governmental and non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely
26、with the International Electrotechnical Commission (IEC) on all matters of electrotechnical standardization. International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 2. The main task of technical committees is to prepare International Standards. Draft In
27、ternational Standards adopted by the technical committees are circulated to the member bodies for voting. Publication as an International Standard requires approval by at least 75 % of the member bodies casting a vote. Attention is drawn to the possibility that some of the elements of this document
28、may be the subject of patent rights. ISO shall not be held responsible for identifying any or all such patent rights. ISO 14520-15 was prepared by Technical Committee ISO/TC 21, Equipment for fire protection and fire fighting, Subcommittee SC 8, Gaseous media and firefighting systems using gas. This
29、 second edition cancels and replaces the first edition (ISO 14520-15:2000), which has been technically revised. ISO 14520 consists of the following parts, under the general title Gaseous media fire extinguishing systems Physical properties and system design: Part 1: General requirements Part 2: CF3I
30、 extinguishant Part 5: FK-5-1-12 extinguishant Part 6: HCFC Blend A extinguishant Part 8: HFC 125 extinguishant Part 9: HFC 227ea extinguishant Part 10: HFC 23 extinguishant Part 11: HFC 236fa extinguishant Part 12: IG-01 extinguishant Part 13: IG-100 extinguishant Part 14: IG-55 extinguishant Part
31、15: IG-541 extinguishant Parts 3, 4 and 7, which dealt with FC-2-1-8, FC-3-1-10 and HCFC 124 extinguishants, respectively, have been withdrawn, as these types are no longer manufactured. BS EN 15004-10:2008EN 15004-10:2008 (E) 6 1 Scope This document gives specific requirements for gaseous fire-exti
32、nguishing systems, with respect to the IG-541 extinguishant. It includes details of physical properties, specification, usage and safety aspects and is applicable to systems operating at nominal pressure of 150 bar, 200 bar and 300 bar at 15 C. This does not preclude the use of other systems; howeve
33、r, design data for other pressures were not available at time of publication. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the refe
34、renced document (including any amendments) applies. EN 15004-1:2008, Fixed firefighting systems Gas extinguishing systems - Design, installation and maintenance (ISO 14520-1, modified) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 15004-1:2008 apply
35、. 4 Characteristics and uses 4.1 General Extinguishant IG-541 shall comply with the specification according to Table 1. IG-541 is a colourless, odourless, electrically non-conductive gas with a density approximately the same as that of air. It is an inert gas mixture consisting nominally of 52 % nit
36、rogen, 40 % argon and 8 % carbon dioxide, with the following mixture specification (based on 8 % carbon dioxide with tolerance of 5 %): a) Carbon dioxide: range of 7,6 % to 8,4 %; b) Argon: range of 37,2 % to 42,8 %; c) Nitrogen: range of 48,8 % to 55,2 %. NOTE Individual container or batch analysis
37、 is based on carbon dioxide measurement only. The physical properties are given in Table 2. IG-541 extinguishes fires by a reduction of the oxygen concentration in the atmosphere of the hazard enclosure. BS EN 15004-10:2008EN 15004-10:2008 (E) 7 Table 1 Specification for IG-541 Property Requirement
38、Argon Nitrogen Carbon dioxide Purity 99,997 % by volume, min. 99,99 % by volume, min. 99,5 % by volume, min. Water content 4 106by mass, max. 5 106by mass, max. 10 106by mass, max. Oxygen 3 106by mass, max. 3 106by mass, max. 10 106by mass, max. Only principal contaminants are shown. Other measureme
39、nts may include hydrocarbons, CO, NO, NO2. Most are 20 106. Table 2 Physical properties of IG-541 Property Unit Value Molecular mass 34,0 Boiling point at 1,013 bar (absolute) aC 196 Freezing point C 78,5 Critical temperature C Critical pressure bar abs a Critical volume cm3/mol Critical density kg/
40、m3 Vapour pressure 20 C bar abs a152 Liquid density 20 C kg/m3 Saturated vapour density 20 C kg/m3Specific volume of superheated vapour at 1,013 bar and 20 C m3/kg 0,697 N252 % by volume Ar 40 % by volume Chemical formulas CO28 % by volume Nitrogen Argon Chemical names Cabon dioxide a1 bar = 0,1 MPa
41、 = 105Pa; 1 MPa = 1 N/mm2. 4.2 Use of IG-541 systems IG-541 total flooding systems may be used for extinguishing fires of all classes within the limits specified in EN 15004-1:2008, Clause 4. The extinguishant requirements per volume of protected space are shown in Table 3 for various levels of conc
42、entration. These are based on methods given in EN 15004-1:2008, 7.6. The extinguishing concentrations and design concentrations for n-heptane and Surface Class A hazards are given in Table 4. BS EN 15004-10:2008EN 15004-10:2008 (E) 8 Table 3 IG-541 total flooding quantity IG-541 volume requirements
43、per unit volume of protected space, V/V (m3/m3) This information refers only to IG-541, and may not represent any other products containing argon, nitrogen or carbon dioxide as components. Temperature T Specific vapour volume S Design concentration (by volume) C m3/kg 34 % 38 % 42 % 46 % 50 % 54 % 5
44、8 % 62 % 40 0,5624 0,521 0,600 0,684 0,773 0,870 0,975 1,089 1,214 35 0,5743 0,511 0,587 0,669 0,757 0,852 0,954 1,066 1,189 30 0,5863 0,500 0,575 0,656 0,742 0,834 0,935 1,044 1,165 25 0,5982 0,490 0,564 0,643 0,727 0,818 0,916 1,023 1,142 20 0,6102 0,481 0,553 0,630 0,713 0,802 0,898 1,003 1,119 1
45、5 0,6221 0,471 0,542 0,618 0,699 0,786 0,881 0,984 1,098 10 0,6341 0,463 0,532 0,606 0,686 0,772 0,864 0,966 1,077 5 0,6460 0,454 0,522 0,595 0,673 0,757 0,848 0,948 1,057 0 0,6580 0,446 0,513 0,584 0,661 0,744 0,833 0,931 1,038 5 0,6699 0,438 0,504 0,574 0,649 0,730 0,818 0,914 1,019 10 0,6819 0,43
46、0 0,495 0,564 0,638 0,717 0,804 0,898 1,001 15 0,6938 0,423 0,486 0,554 0,627 0,705 0,790 0,882 0,984 20 0,7058 0,416 0,478 0,545 0,616 0,693 0,777 0,868 0,968 25 0,7177 0,409 0,470 0,536 0,606 0,682 0,764 0,853 0,951 30 0,7297 0,402 0,462 0,527 0,596 0,670 0,751 0,839 0,936 35 0,7416 0,395 0,455 0,
47、518 0,586 0,660 0,739 0,826 0,921 40 0,7536 0,389 0,448 0,510 0,577 0,649 0,727 0,812 0,906 45 0,7655 0,383 0,441 0,502 0,568 0,639 0,716 0,800 0,892 50 0,7775 0,377 0,434 0,494 0,559 0,629 0,705 0,787 0,878 55 0,7894 0,371 0,427 0,487 0,551 0,620 0,694 0,776 0,865 60 0,8014 0,366 0,421 0,480 0,543
48、0,610 0,684 0,764 0,852 65 0,8133 0,361 0,415 0,473 0,535 0,601 0,674 0,753 0,840 70 0,8253 0,355 0,409 0,466 0,527 0,593 0,664 0,742 0,827 75 0,8372 0,350 0,403 0,459 0,519 0,584 0,655 0,731 0,816 80 0,8492 0,345 0,397 0,453 0,512 0,576 0,645 0,721 0,804 85 0,8611 0,341 0,392 0,446 0,505 0,568 0,63
49、6 0,711 0,793 90 0,8731 0,336 0,386 0,440 0,498 0,560 0,628 0,701 0,782 95 0,8850 0,331 0,381 0,434 0,491 0,553 0,619 0,692 0,772 100 0,8970 0,327 0,376 0,429 0,485 0,545 0,611 0,683 0,761 V/V is the agent volume requirement (in cubic metres per cubic metre); i.e. the quantity Q (in cubic metres) of agent required at a reference temperature of 20 C and a pressure of 1,013 bar per cubic metre of protected volume to produce the indicated concentration at