1、BS EN 15269-7:2009ICS 13.220.50; 91.060.50NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBRITISH STANDARDExtended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardwar
2、e Part 7: Fire resistance for steel sliding doorsets This British Standard was published under the authority of the Standards Policy and Strategy Committee on 30 November 2009 BSI 2009ISBN 978 0 580 56359 1Amendments/corrigenda issued since publicationDate CommentsBS EN 15269-7:2009National foreword
3、This British Standard is the UK implementation of EN 15269-7:2009.The UK participation in its preparation was entrusted to TechnicalCommittee FSH/22/5, Test procedures for doors.A list of organizations represented on this committee can be obtained onrequest to its secretary.This publication does not
4、 purport to include all the necessary provisionsof a contract. Users are responsible for its correct application.Compliance with a British Standard cannot confer immunityfrom legal obligations.BS EN 15269-7:2009EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 15269-7 November 2009 ICS 13.220.50;
5、 91.060.50 English Version Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 7: Fire resistance for steel sliding doorsets Application largie des rsultats dessai en mati
6、re de rsistance au feu et dtanchit la fume des blocs-portes, blocs-fermetures et ouvrants de fentres, y compris les lments intgrs de quincaillerie de btiment - Partie 7: Rsistance au feu des blocs-portes coulissants en acierErweiterter Anwendungsbereich von Prfergebnissen zur Feuerwiderstandsfhigkei
7、t und/oder Rauchdichtigkeit von Tren, Toren und Fenstern einschlielich ihrer Baubeschlge - Teil 7: Feuerwiderstandsfhigkeit von Schiebetoren aus Stahl This European Standard was approved by CEN on 22 September 2009. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stip
8、ulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member. This European Standard
9、 exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions. CEN members are the national standa
10、rds bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United King
11、dom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2009 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 15269-7:2009: EBS E
12、N 15269-7:2009EN 15269-7:2009 (E) 2 Contents Page Foreword . 3Introduction . 41 Scope 52 Normative references 53 Terms and definitions . 64 Determination of the field of extended application 74.1 General . 74.2 Procedure for evaluation 74.3 Procedure for maximum field of extended application . 84.4
13、Interpretation of test results . 85 Extended application report . 86 Classification report 9Annex A (normative) Construction parameter variations 10Figures relating to Annex A . 64BS EN 15269-7:2009EN 15269-7:2009 (E) 3 Foreword This document (EN 15269-7:2009) has been prepared by Technical Committe
14、e CEN/TC 127 “Fire safety in buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by May 2010, and conflicting national standards shall be withdrawn at
15、 the latest by May 2010. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document has been prepared under a mandate given to CEN
16、by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgi
17、um, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. BS EN 15269-7:2009E
18、N 15269-7:2009 (E) 4 Introduction This European Standard is one of a series of standards listed below and intended to be used for the purpose of producing an extended application report based on the evaluation of one or more fire resistance and/or smoke control tests. These standards may also be use
19、d to identify the best selection of test specimens required to cover a wide range of product variations. The EN 15269 series currently consists of: prEN 15269, Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including th
20、eir elements of building hardware Part 1: General requirements Part 2: Fire resistance of hinged and pivoted steel doorsets Part 3: Fire resistance of hinged and pivoted timber doorsets and openable timber framed windows Part 5: Fire resistance of hinged and pivoted metal framed glazed doorsets and
21、openable windows Part 6: Fire resistance of sliding timber doorsets Part 10: Fire resistance of steel rolling shutters Part 11: Fire resistance of operable fabric curtains as well as EN 15269, Extended application of test results for fire resistance and/or smoke control for door, shutter and openabl
22、e window assemblies, including their elements of building hardware Part 7: Fire resistance for steel sliding doorsets Part 20: Smoke control for hinged and pivoted steel, timber and metal framed glazed doorsets Before there can be any consideration for extended application the doorset should have be
23、en tested in accordance with EN 1634-1 to achieve a test result which could generate a classification in accordance with EN 13501-2 at least equal to the classification subsequently required from extended application considerations. A review of the doorset construction parameters can indicate that o
24、ne or more characteristics may be improved by a particular parameter variation. All evaluations should be made on the basis of retaining the fire resistance classifications obtainable from testing to EN 1634-1, including those lower than the test duration. However, this should never lead to an incre
25、ased classification for any specific fire or smoke performance parameter beyond that achieved during any one test unless specifically identified in the relevant Construction Parameter Variation tables within this series of standards. The effect on the durability of self closing of the doorsets follo
26、wing an extended application process is not addressed in this series of standards. BS EN 15269-7:2009EN 15269-7:2009 (E) 5 1 Scope This European Standard, which should be read in conjunction with prEN 15269-1, covers the following types of steel based doorsets: horizontally sliding doorsets (single
27、and double), telescopic doorsets (single and double) and single vertically sliding doorsets. This document prescribes the methodology for extending the application of test results obtained from test(s) conducted in accordance with EN 1634-1. Subject to the completion of the appropriate test or tests
28、 selected from those identified in Clause 4 the extended application may cover all or some of the following non-exhaustive list: integrity only (E), radiation (EW) or insulated (EI1or EI2) classifications; door leaf; wall/ceiling fixed elements (frame/suspension system); glazing for door leaf; items
29、 of building hardware; decorative finishes; intumescent, smoke, draught or acoustic seals; alternative supporting construction(s). 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. F
30、or undated references, the latest edition of the referenced document (including any amendments) applies. EN 1363-1:1999, Fire resistance tests Part 1: General requirements EN 1634-1:2008, Fire resistance and smoke control tests for door, shutter and openable window assemblies and elements of buildin
31、g hardware Part 1: Fire resistance tests for doors, shutters and openable windows EN 1634-2:2008, Fire resistance and smoke control tests for door, shutter and openable window assemblies and elements of building hardware Part 2: Fire resistance characterisation test for elements of building hardware
32、 EN 13501-2:2007, Fire classification of construction products and building elements Part 2: Classification using data from fire resistance tests, excluding ventilation services EN 15254-4:2008, Extended application of results from fire resistance tests Non-loadbearing walls Part 4: Glazed construct
33、ions prEN 15269-1:2007, Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware Part 1: General requirements BS EN 15269-7:2009EN 15269-7:2009 (E) 6 prEN 15269-2, Extended applicatio
34、n of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware Part 2: Fire resistance of hinged and pivoted steel doorsets EN ISO 13943:2000, Fire safety Vocabulary (ISO 13943:2000) 3 Terms and definitions F
35、or the purposes of this document, the terms and definitions given in EN 1363-1:1999, EN ISO 13943:2000, EN 1634-1:2008, EN 1634-2:2008 and prEN 15269-1:2007 together with the following apply. 3.1 full scale test test of a full size doorset in accordance with EN 1634-1 3.2 leaf/element/panel differen
36、t parts of a doorset as indicated in Figures 1 and 2 below 123Key 1 panel 2 leaf 3 element Figure 1 Double leaf telescopic door BS EN 15269-7:2009EN 15269-7:2009 (E) 7 21Key 1 panel 2 leaf Figure 2 Double leaf sliding door 4 Determination of the field of extended application 4.1 General 4.1.1 Before
37、 there can be any consideration for extended application the doorset shall have been tested and classified in accordance with EN 1634-1 and EN 13501-2 respectively in order to establish a classification for the doorset. 4.1.2 A review of the doorset construction parameters can indicate that one or m
38、ore characteristics may be improved by a particular parameter variation. All evaluations shall be made on the basis of retaining the classifications obtainable from testing to EN 1634-1, including those lower than the test duration. However, this shall never lead to an increased classification for a
39、ny specific parameter beyond that achieved during any one test unless specifically identified in the relevant Construction Parameter Variation tables. 4.1.3 All evaluations shall be made on the basis of retaining the classification obtained from testing to EN 1634-1. 4.1.4 If, by following the ensui
40、ng procedure, any part of the classification cannot be achieved by extended application rules that part of classification shall be omitted from the subsequent extended application report and classification report. 4.2 Procedure for evaluation 4.2.1 Identify the variations from the original test spec
41、imen(s) which are required to be covered by an extended application report. 4.2.2 Locate the variations in the appropriate parameter variation by reference to columns (1) and (2) of Table A.1. 4.2.3 Review the type of classification to be retained from column (3) of Table A.1 and establish from the
42、contents of column (4) of Table A.1 whether any extended application is available without the need for further testing. 4.2.4 Where this is deemed to be possible this can be recorded in the extended application report together with any appropriate restrictions and the stated rules from column (4) in
43、 Table A.1. 4.2.5 Where the variations required can only be achieved from additional testing according to column (5) in Table A.1, the additional test can be made on a similar specimen type to the original test BS EN 15269-7:2009EN 15269-7:2009 (E) 8 against which the extended application is sought.
44、 Alternatively, column (5) in Table A.1 identifies an option for alternative testing and relevant test parameters. 4.3 Procedure for maximum field of extended application 4.3.1 It is possible to provide a limited field of extended application from the results of a single test. However, where a manuf
45、acturer intends to produce a range of doors incorporating single doors and also double doors, with or without glazing, with alternative elements of building hardware, etc., it is recommended that careful consideration is given to the complete range of doorset designs and options in order to minimise
46、 the testing required before testing commences. 4.3.2 Establish all the parameter variations which are required to be part of the product range. 4.3.3 Select specimen(s) for the first test(s) in the series to ensure that the most important parameter variations for the manufactured products are cover
47、ed. 4.3.4 Complete the first test or a series of tests and prepare a field of direct application and possibly a classification report from the results of the test(s). 4.3.5 Establish which of the original desired parameter variations have not been covered by the direct application and classification
48、 report. 4.3.6 Identify these parameter variations in Annex A and establish if any extended application is possible without further testing. 4.3.7 Record this for the extended application report together with any restrictions and rules given in column (5) in Table A.1. 4.3.8 Evaluate which, if any,
49、of the desired parameter variations have not been covered by the field of direct application or the initial field of extended application derived from 4.3.7 above. 4.3.9 Select the required outstanding parameter variations from column (1) and column (2) of Table A.1 and observe from column (5) of Table A.1 which are the most appropriate weakest specimen options for further testing. 4.3.10 If the complete selection of required parameter variations has not been covered by the t