1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationBS EN 50379-3:2012Specification for portableelectrical apparatus designedto measure combustion fluegas parameters of heatingappliances -Part 3: Performance requirements forappara
2、tus used in non-statutory servicing ofgas fired heating appliancesBS EN 50379-3:2012 BRITISH STANDARDNational forewordThis British Standard is the UK implementation of EN 50379-3:2012.It supersedes BS EN 50379-3:2004 which is withdrawn.The UK participation in its preparation was entrusted to Technic
3、alCommittee EXL/31/1, Gas detectors.A list of organizations represented on this committee can beobtained on request to its secretary.This publication does not purport to include all the necessaryprovisions of a contract. Users are responsible for its correctapplication. The British Standards Institu
4、tion 2012. Published by BSI StandardsLimited 2012ISBN 978 0 580 74638 3ICS 13.040.40; 91.140.10Compliance with a British Standard cannot confer immunity fromlegal obligations.This British Standard was published under the authority of theStandards Policy and Strategy Committee on 30 April 2012.Amendm
5、ents issued since publicationDate Text affectedBS EN 50379-3:2012EUROPEAN STANDARD EN 50379-3 NORME EUROPENNE EUROPISCHE NORM April 2012 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Ma
6、nagement Centre: Avenue Marnix 17, B - 1000 Brussels 2012 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 50379-3:2012 E ICS 13.320 Supersedes EN 50379-3:2004English version Specification for portable electrical apparatus designed
7、 to measure combustion flue gas parameters of heating appliances - Part 3: Performance requirements for apparatus used in non-statutory servicing of gas fired heating appliances Spcification pour les appareils lectriques portatifs conus pour mesurer les paramtres des gaz de combustion dans les condu
8、its dvacuation des appareils de chauffage - Partie 3: Prescriptions des caractristiques des appareils utiliss dans le service aprs-vente hors champ rglementaire des appareils de chauffage gaz Anforderungen an tragbare elektrische Gerte zur Messung von Verbrennungsparametern von Heizungsanlagen - Tei
9、l 3: Anforderungen an das Betriebsverhalten von Gerten fr den Einsatz im nicht-geregelten Bereich bei Wartungen von gasbefeuerten Heizungsanlagen This European Standard was approved by CENELEC on 2012-03-19. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulat
10、e the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CENELEC member. This European
11、Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CENELEC members
12、 are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia,
13、Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. BS EN 50379-3:2012EN 50379-3:2012 2 Contents Foreword 3Introduction. 41 Scope . 52 Normative references . 53 Terms and definitions . 54 General requirements . 65 Test methods and performance requirements . 65.1 General requirements
14、 for tests 65.2 Normal conditions for tests 65.3 Mechanical tests . 65.4 Electrical and software tests 75.5 Tests with test gases . 75.6 Tests with real flue gases 85.7 Calculated values 95.8 Temperature 95.9 Pressure . 10Bibliography 11BS EN 50379-3:2012 3 EN 50379-3:2012 Foreword This document (EN
15、 50379-3:2012) has been prepared by CLC/TC 216 “Gas detectors“. The following dates are fixed: latest date by which this document has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2013-03-19 latest date by which the national standards co
16、nflicting with this document have to be withdrawn (dow) 2015-03-19 This document supersedes EN 50379-3:2004. EN 50379-3:2012 includes the following significant technical changes with respect to EN 50379-3:2004: 5.5.7 considers calibration curves for sensors with nonlinear signal; 5.5.8 considers inf
17、luence of pressure variations; 5.5.9 considers the influence of water vapour on the gas signal; 5.7.2 for calculated values was amended; 5.9.1 was amended to cover measurement at the circular orifice. Attention is drawn to the possibility that some of the elements of this document may be the subject
18、 of patent rights. CENELEC and/or CEN shall not be held responsible for identifying any or all such patent rights. _ BS EN 50379-3:2012EN 50379-3:2012 4 Introduction This European Standard covers apparatus for measuring gas concentrations and other combustion parameters, as used in the installation
19、and maintenance of heating appliances. It forms a specification for portable electrical apparatus designed to measure combustion flue gas parameters of heating appliances, and includes the following parts under the generic title Specification for portable electrical apparatus designed to measure com
20、bustion flue gas parameters of heating appliances: Part 1: General requirements and test methods; Part 2: Performance requirements for apparatus used in statutory inspections and assessments; Part 3: Performance requirements for apparatus used in non-statutory servicing of gas fired heating applianc
21、es. EN 50379-1 specifies general requirements for the construction, testing and performance of portable spot reading apparatus, designed to give an assessment of specific combustion flue gas parameters such as concentration of gaseous compounds, temperature and/or pressure, to check the combustion p
22、erformance of heating appliances for domestic residential and commercial applications using commercially available fuels. EN 50379-2 is for apparatus intended to be used for statutory measurement. In several European countries, legal requirements exist for the performance of heating appliances. Auth
23、orised inspectors use these apparatus to measure the flue gas parameters, in order to test the compliance with national regulations. Due to the legal consequences resulting from the measurement there are strict requirements regarding the measuring uncertainty of these apparatus. Therefore EN 50379-2
24、 includes maximum values for measuring uncertainty of the apparatus. Tests with real flue gases form a key part of the verification of the performance of the apparatus for statutory measurement. The measuring uncertainty has to be justified by internationally accepted methods over the whole measurin
25、g range. EN 50379-3 is for apparatus intended to be used for non-statutory applications. There are reduced performance requirements, because the apparatus are designed to decide whether maintenance for a gas fired appliance is required, and for adjusting the appliance during maintenance. There will
26、be no determination of the measuring uncertainty for the apparatus. BS EN 50379-3:2012 5 EN 50379-3:2012 1 Scope This European Standard covers apparatus designed for checking the performance of heating appliances by measuring flue gas parameters of gas fired heating appliances for domestic residenti
27、al and commercial applications. The apparatus may consist of different functional modules which may be tested separately for complying with this standard, and will be combined in different ways according to the different applications. Part 1 of EN 50379 specifies the general requirements and is supp
28、lemented by the requirements in EN 50379-2 and/or EN 50379-3. This European Standard specifies the performance requirements of portable spot reading apparatus designed to detect specific combustion flue gas parameters, such as concentration of gaseous compounds, temperature and/or pressure, to be us
29、ed to decide if maintenance for the appliance is required and for adjusting the appliance during maintenance. This European Standard excludes apparatus for checking appliances using fuels other than gas, continuous emission, safety monitoring and control, and use in vessels with an international loa
30、d line. NOTE 1 When this apparatus is used in industrial premises, national regulations should be observed. NOTE 2 Apparatus may contain functional modules which are not covered by this standard e.g. measurement of smoke spot number (see EN 267:2009+A1:2011, Annex A) and/or measurement of indoor amb
31、ient air (see EN 50543). 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced docu
32、ment (including any amendments) applies. EN 50270:2006, Electromagnetic compatibility Electrical apparatus for the detection and measurement of combustible gases, toxic gases or oxygen EN 50271:2010, Electrical apparatus for the detection and measurement of combustible gases, toxic gases or oxygen R
33、equirements and tests for apparatus using software and/or digital technologies EN 50379-1:2012, Specification for portable electrical apparatus designed to measure combustion flue gas parameters of heating appliances Part 1: General requirements and test methods EN 60335-1:2002, Safety of household
34、and similar electrical appliances Part 1: General requirements (IEC 60335-1:2001, mod.) EN 60529:1991, Degrees of protection provided by enclosures (IP Code) (IEC 60529:1989) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 50379-1:2012 apply. BS EN 50
35、379-3:2012EN 50379-3:2012 6 4 General requirements Unless otherwise stated, the general requirements of EN 50379-1:2012 are applicable and shall be checked by visual inspection. 5 Test methods and performance requirements 5.1 General requirements for tests 5.1.1 General The requirements specified in
36、 EN 50379-1:2012, 5.1.1 are applicable. 5.1.2 Samples and sequence of tests For the purposes of type testing, for each sample the first test to be carried out shall be the initial performance test (5.5.3). One sample of the apparatus shall be subjected to the relevant tests given in 5.3 and 5.4. The
37、 mechanical tests of 5.3 shall be carried out before the tests of 5.4 to 5.9. After finishing the mechanical tests of 5.3 the initial performance test (5.5.3) shall be repeated at room temperature. NOTE Due to the use of different calibration gases at pre-calibration by the manufacturer and type tes
38、ting according to this standard the instruments may show a discrepancy. In this case, it is permissible to make minor adjustments to the apparatus during the initial performance test (5.5.3). The EMC testing according to 5.4.1 may be carried out independently from all other tests of the standard. Th
39、e tests within 5.3, 5.4 and 5.5 may be performed in any sequence, but 5.6 to 5.9 shall be performed in the sequence listed in this standard, where relevant. 5.1.3 Preparation of samples The requirements specified in EN 50379-1:2012, 5.1.3 are applicable. 5.1.4 Test facility The requirements specifie
40、d in EN 50379-1:2012, 5.1.4 are applicable. 5.2 Normal conditions for tests The requirements specified in EN 50379-1:2012, 5.2 are applicable. 5.3 Mechanical tests 5.3.1 General The requirements specified in EN 50379-1:2012, 5.3.1 are applicable 5.3.2 Degree of protection The enclosure of the appara
41、tus shall provide at least an IP40 degree of protection when all probes etc. are connected, in accordance with EN 60529:1991, Clauses 12 and 14. If an apparatus is designed for outdoor use it shall provide at least an IP42 degree of protection when connected similarly. 5.3.3 Impact strength The appa
42、ratus shall meet the requirements specified in EN 60335-1:2002, Clause 21, as modified by EN 50379-1:2012, 5.3.3. The function of the apparatus shall not be affected after the test. Visible damage to parts of the housing are acceptable, providing the functionality remains unimpaired. BS EN 50379-3:2
43、012 7 EN 50379-3:2012 5.3.4 Vibration The function of the apparatus shall not be affected after the test. Visible damage to parts of the housing are acceptable, providing the functionality remains unimpaired. 5.3.5 Drop The function of the apparatus shall not be affected after the test. Visible dama
44、ge to parts of the housing are acceptable, providing the functionality remains unimpaired. 5.3.6 Flow indicator (if fitted) If an apparatus is fitted with an integral flow proving device, after the simulation of the blockage function of the integral flow indicator shall be checked by visual inspecti
45、on. 5.3.7 Dust filter and water trap After measuring times of 1 h the dust filter shall still be usable, as specified in the manufacturers instruction manual, and the maximum level of the condensate separator shall not be reached. The flow of the apparatus shall continuously be above the minimum flo
46、w, specified by the manufacturer, within the 1 h testing period. 5.4 Electrical and software tests 5.4.1 Electromagnetic Compatibility (EMC) The apparatus, including the probe and any interconnecting wiring and tubing, shall meet the requirements for electromagnetic compatibility in accordance with
47、EN 50270 for Type 1 (domestic) and shall meet the requirements of EN 50270:2006, Table 5. 5.4.2 Supply voltage variations (not applicable to battery powered apparatus) The apparatus shall meet the requirements for accuracy listed in EN 50379-1:2012, Table 1. 5.4.3 Battery fault condition (applicable
48、 only to battery powered apparatus) The apparatus shall meet the requirements for accuracy listed in EN 50379-1:2012, Table 1. 5.4.4 Battery reversal (applicable only to battery powered apparatus) The apparatus shall meet the requirements for accuracy listed in EN 50379-1:2012, Table 1. 5.4.5 Softwa
49、re and digital techniques The requirements specified in EN 50379-1:2012, 5.4.5 are applicable. 5.5 Tests with test gases 5.5.1 General The requirements specified in EN 50379-1:2012, 5.5.1 are applicable. 5.5.2 Unpowered storage The apparatus shall meet the requirements for accuracy listed in EN 50379-1:2012, Table 1. BS EN 50379-3:2012EN 50379-3:2012 8 5.5.3 Initial performance test The apparatus shall meet the requirements for accuracy list