ETSI EN 300 019-1-3-2014 Environmental Engineering (EE) Environmental conditions and environmental tests for telecommunications equipment Part 1-3 Classification of environmental c_1.pdf

上传人:sofeeling205 文档编号:727706 上传时间:2019-01-09 格式:PDF 页数:21 大小:128.29KB
下载 相关 举报
ETSI EN 300 019-1-3-2014 Environmental Engineering (EE) Environmental conditions and environmental tests for telecommunications equipment Part 1-3 Classification of environmental c_1.pdf_第1页
第1页 / 共21页
ETSI EN 300 019-1-3-2014 Environmental Engineering (EE) Environmental conditions and environmental tests for telecommunications equipment Part 1-3 Classification of environmental c_1.pdf_第2页
第2页 / 共21页
ETSI EN 300 019-1-3-2014 Environmental Engineering (EE) Environmental conditions and environmental tests for telecommunications equipment Part 1-3 Classification of environmental c_1.pdf_第3页
第3页 / 共21页
ETSI EN 300 019-1-3-2014 Environmental Engineering (EE) Environmental conditions and environmental tests for telecommunications equipment Part 1-3 Classification of environmental c_1.pdf_第4页
第4页 / 共21页
ETSI EN 300 019-1-3-2014 Environmental Engineering (EE) Environmental conditions and environmental tests for telecommunications equipment Part 1-3 Classification of environmental c_1.pdf_第5页
第5页 / 共21页
点击查看更多>>
资源描述

1、 ETSI EN 300 019-1-3 V2.4.1 (2014-04) Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1-3: Classification of environmental conditions; Stationary use at weatherprotected locations European Standard ETSI ETSI EN 300 019-1-3 V2.4.

2、1 (2014-04)2Reference REN/EE-0155 Keywords environment, equipment practice, testing ETSI 650 Route des Lucioles F-06921 Sophia Antipolis Cedex - FRANCE Tel.: +33 4 92 94 42 00 Fax: +33 4 93 65 47 16 Siret N 348 623 562 00017 - NAF 742 C Association but non lucratif enregistre la Sous-Prfecture de Gr

3、asse (06) N 7803/88 Important notice The present document can be downloaded from: http:/www.etsi.org The present document may be made available in electronic versions and/or in print. The content of any electronic and/or print versions of the present document shall not be modified without the prior

4、written authorization of ETSI. In case of any existing or perceived difference in contents between such versions and/or in print, the only prevailing document is the print of the Portable Document Format (PDF) version kept on a specific network drive within ETSI Secretariat. Users of the present doc

5、ument should be aware that the document may be subject to revision or change of status. Information on the current status of this and other ETSI documents is available at http:/portal.etsi.org/tb/status/status.asp If you find errors in the present document, please send your comment to one of the fol

6、lowing services: http:/portal.etsi.org/chaircor/ETSI_support.asp Copyright Notification No part may be reproduced or utilized in any form or by any means, electronic or mechanical, including photocopying and microfilm except as authorized by written permission of ETSI. The content of the PDF version

7、 shall not be modified without the written authorization of ETSI. The copyright and the foregoing restriction extend to reproduction in all media. European Telecommunications Standards Institute 2014. All rights reserved. DECTTM, PLUGTESTSTM, UMTSTMand the ETSI logo are Trade Marks of ETSI registere

8、d for the benefit of its Members. 3GPPTM and LTE are Trade Marks of ETSI registered for the benefit of its Members and of the 3GPP Organizational Partners. GSM and the GSM logo are Trade Marks registered and owned by the GSM Association. ETSI ETSI EN 300 019-1-3 V2.4.1 (2014-04)3Contents Intellectua

9、l Property Rights 4g3Foreword . 4g31 Scope 5g32 References 5g32.1 Normative references . 5g32.2 Informative references 5g33 Definitions and abbreviations . 6g33.1 Definitions 6g33.2 Abbreviations . 6g34 Environmental classes 7g34.1 Class 3.1: Temperature-controlled locations 7g34.2 Class 3.2: Partly

10、 temperature-controlled locations . 8g34.3 Class 3.3: Not temperature-controlled locations 9g34.4 Class 3.4: Sites with heat-trap 10g34.5 Class 3.5: Sheltered locations . 11g34.6 Class 3.6: Telecommunication control room locations 12g35 Environmental conditions. 14g35.1 Climatic conditions. 14g35.2

11、Biological conditions 14g35.3 Chemically active substances . 15g35.4 Mechanically active substances 16g35.5 Mechanical conditions 17g35.6 Earthquake conditions 17g3Annex A (informative): Bibliography . 20g3History 21g3ETSI ETSI EN 300 019-1-3 V2.4.1 (2014-04)4Intellectual Property Rights IPRs essent

12、ial or potentially essential to the present document may have been declared to ETSI. The information pertaining to these essential IPRs, if any, is publicly available for ETSI members and non-members, and can be found in ETSI SR 000 314: “Intellectual Property Rights (IPRs); Essential, or potentiall

13、y Essential, IPRs notified to ETSI in respect of ETSI standards“, which is available from the ETSI Secretariat. Latest updates are available on the ETSI Web server (http:/ipr.etsi.org). Pursuant to the ETSI IPR Policy, no investigation, including IPR searches, has been carried out by ETSI. No guaran

14、tee can be given as to the existence of other IPRs not referenced in ETSI SR 000 314 (or the updates on the ETSI Web server) which are, or may be, or may become, essential to the present document. Foreword This European Standard (EN) has been produced by ETSI Technical Committee Environmental Engine

15、ering (EE). The present document is part 1, sub part 3 of a multi-part deliverable covering the classification of environmental conditions and environmental tests for telecommunications equipment, as identified below: Part 1: “Classification of environmental conditions“: (see note 1) Sub-part 0: “In

16、troduction“; Sub-part 1: “Storage“; Sub-part 2: “Transportation“; Sub-part 3: “Stationary use at weatherprotected locations“; Sub-part 4: “Stationary use at non-weatherprotected locations“; Sub-part 5: “Ground vehicle installations“; Sub-part 6: “Ship environments“; Sub-part 7: “Portable and non-sta

17、tionary use“; Sub-part 8: “Stationary use at underground locations“; Part 2: “Specification of environmental tests“ (see note 2). NOTE 1: Specifies different standardized environmental classes covering climatic and biological conditions, chemically and mechanically active substances and mechanical c

18、onditions during storage, transportation and in use. Sub-part 1-0 forms a general overview of part 1. NOTE 2: Specifies the recommended test severities and test methods for the different environmental classes. National transposition dates Date of adoption of this EN: 21 April 2014 Date of latest ann

19、ouncement of this EN (doa): 31 July 2014 Date of latest publication of new National Standard or endorsement of this EN (dop/e): 31 January 2015 Date of withdrawal of any conflicting National Standard (dow): 31 January 2015 ETSI ETSI EN 300 019-1-3 V2.4.1 (2014-04)51 Scope The present document define

20、s classes of environmental conditions and their severities to which telecommunication equipment may be exposed. The severities specified are those which will have a low probability of being exceeded; generally less than 1 %. The present document applies to equipment mounted for stationary use includ

21、ing periods of erection work, down time, maintenance and repair at weatherprotected locations defined in clause 5. 2 References References are either specific (identified by date of publication and/or edition number or version number) or non-specific. For specific references, only the cited version

22、applies. For non-specific references, the latest version of the reference document (including any amendments) applies. Referenced documents which are not found to be publicly available in the expected location might be found at http:/docbox.etsi.org/Reference. NOTE: While any hyperlinks included in

23、this clause were valid at the time of publication, ETSI cannot guarantee their long term validity. 2.1 Normative references The following referenced documents are necessary for the application of the present document. 1 IEC 60721-2-6:1990: “Classification of environmental conditions. Part 2: Environ

24、mental conditions appearing in nature. Earthquake vibration and shock“. 2.2 Informative references The following referenced documents are not necessary for the application of the present document but they assist the user with regard to a particular subject area. i.1 Void. i.2 IEC 60721-3-3:2002: “Cl

25、assification of environmental conditions - Part 3-3: Classification of groups of environmental parameters and their severities - Stationary use at weatherprotected locations“. i.3 IEC 60068-3-3:1991: “Environmental testing - Part 3: Guidance. Seismic test methods for equipment“. i.4 ETSI EN 300 019-

26、2-3 (2013): “Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 2-3: Specification of environmental tests; Stationary use at weatherprotected locations“. i.5 IEC 60068-2-27:2008: “Environmental Testing, Part 2-27: Test Ea and guida

27、nce: Shock“. ETSI ETSI EN 300 019-1-3 V2.4.1 (2014-04)63 Definitions and abbreviations 3.1 Definitions For the purposes of the present document, the following terms and definitions apply: absolute humidity: mass of water vapour in grams which is associated with one cubic metre of dry air in an air/w

28、ater vapour mixture air conditioning system: system that fully and automatically controls the climatic parameters air temperature and humidity by heating, cooling, humidifying and dehumidifying climate-controlling system: system that controls or influences climate, acting at least on one climatic pa

29、rameter in one direction cooling system: system that controls or influences climate by decreasing the air temperature only NOTE: This can decrease the absolute humidity. data centre: all buildings, facilities, offices and rooms which contain enterprise servers, server communication equipment, coolin

30、g equipment and power equipment, and provide some form of data service NOTE: E.g. large scale mission critical facilities all the way down to small server rooms located in office buildings. forced ventilation system: system that controls or influences climate by introducing outdoor air into the room

31、 or expelling air out of the room heating system: system that controls or influences climate by increasing the air temperature only NOTE: This can decrease the relative humidity. relative humidity: ratio of the partial pressure of the water vapour in moist air at a given temperature, to the partial

32、pressure of the water vapour in saturated air at the same temperature stationary use: use of equipment which is mounted firmly on a structure, or on mounting devices, or permanently placed at a certain site NOTE: It is not intended for portable use, but short periods of handling during erection work

33、s and for which down time, maintenance and repair at the location are included. weatherprotected location: location at which the equipment is protected from direct weather influences EXAMPLE 1: Totally weatherprotected location (enclosed location): direct weather influences are totally excluded. EXA

34、MPLE 2: Partly weatherprotected location (sheltered location): direct weather influences are not completely excluded. 3.2 Abbreviations For the purposes of the present document, the following abbreviations apply: RS Response Spectrum ZPA Zero Period Acceleration ETSI ETSI EN 300 019-1-3 V2.4.1 (2014

35、-04)74 Environmental classes The classes shown in parentheses, e.g. (3C1), may be selected for special applications. 4.1 Class 3.1: Temperature-controlled locations Class 3.1 is a combination of classes 3K3/3Z2/3Z4/3B1/3C2(3C1)/3S2/3M1 in IEC 60721-3-3 i.2. The climatogram is shown in figure 1. Seis

36、mic environment: zone 4 as defined in IEC 60721-2-6 1. Option zone 4 (modified Mercalli scale 9): if earthquake conditions are specified by the customer, the conditions stated in clause 5.6 apply. This class shall apply to a permanently temperature controlled enclosed location. Humidity is usually n

37、ot controlled. The climatogram is shown in figure 1. Heating, cooling, forced ventilation and humidification are used as necessary to maintain the required conditions - especially where there is a significant difference between the room environment and the external ambient. The climate-controlling s

38、ystems could be periodically switched on or off but extremely high or low temperatures are prevented. This class shall apply to locations: where installed equipment may be exposed to solar radiation and to heat radiation. It may also be exposed to movements of the surrounding air due to draughts in

39、buildings. They are not subjected to condensed water, precipitation, water from sources other than rain or icing; without particular risks of biological attacks. This includes protective measures, e.g. special product design, or installations at locations of such construction that mould growth and a

40、ttacks by animals, etc. are not probable; with normal levels of contaminants experienced in urban areas with industrial activities scattered over the whole area and/or with heavy traffic; without special precautions to minimize the presence of sand or dust, but which are not situated in proximity to

41、 sources of sand or dust; with insignificant vibration and shock. The conditions of this class may be found in: normal living or working areas, e.g. living rooms, rooms for general use (theatres, restaurants); offices; shops; workshops for electronic assemblies and other electrotechnical products; t

42、elecommunication centres; storage rooms for valuable and sensitive products; data centres; computer halls. ETSI ETSI EN 300 019-1-3 V2.4.1 (2014-04)8AirTemperatureCAbsoluteAir Humidityg/m-20 -10 0 10 20 30 40 50 0 10 20 30 40 50 60 70 80 9020 100 Relative Air Humidity % Normal Conditions Exceptional

43、 Conditions 25 1,5 1 Values outside this field have a probability of occurrence of less than 10 % (see IEC 60721-3-0). Exceptional climatic limits. Normal climatic limits: Values outside these limits have a probability of occurrence of less than 1 % . NOTE: Exceptional conditions may occur following

44、 the failure of the temperature controlling system. This is described as 3.1E in the tables but it should be noted that there is no separate class 3.1E. Figure 1: Climatogram for Class 3.1: Temperature-controlled locations 4.2 Class 3.2: Partly temperature-controlled locations This class is a combin

45、ation of classes 3K5/3Z2/3Z4/3B2/3C2(3C1)/3S3/3M2 in IEC 60721-3-3 i.2. Seismic environment: zone 4 as defined in IEC 60721-2-6 1. Option zone 4 (modified Mercalli scale 9): if earthquake conditions are specified by the customer, the conditions stated in clause 5.6 apply. This class applies to an en

46、closed location having neither temperature nor humidity control. The climatogram is shown in figure 2. Heating may be used to raise low temperatures especially where there is a significant difference between the conditions of this class and the open-air climate. Building construction is designed to

47、avoid extremely high temperatures. This class shall apply to locations: where installed equipment may be exposed to solar radiation and heat radiation. They may also be exposed to movements of the surrounding air due to draughts in buildings, e.g. through open windows. They may be subjected to conde

48、nsed water. They are not subjected to precipitation; where mould growth or attacks by animals, except termites, may occur; with normal levels of contaminants experienced in urban areas with industrial activities scattered over the whole area and/or with heavy traffic; in close proximity to sources o

49、f sand or dust; with vibration of low significance, e.g. for products fastened to light supporting structures subjected to negligible vibrations. ETSI ETSI EN 300 019-1-3 V2.4.1 (2014-04)9The conditions of this class may be found in: entrances and staircases of buildings; garages; cellars; certain workshops; buildings in factories and industrial process plants; unattended equipment stations; certain telecommunication buildings; ordinary storage rooms for frost resistant products and farm build