1、 FECDS F-6 Engineering CAD & Drafting Standards Ford Proprietary and/or Confidential Information - Do not distribute to others w/o prior written authorization. Version 28 TOC Original Issue: 19960419 Copyright, Ford Motor Company. Latest Re-issue: None F61 Printed copies are uncontrolled.MANUFACTURI
2、NG PLANT LAYOUT DRAWINGS 1 INTRODUCTION Plant Layout Drawings (i.e. Facility drawings) are used to show information relevant to the manufacturing equipment location and power services as it relates to the overall layout of a plant. This includes, but is not limited to drawings that represent machine
3、 cells, templates, duct layouts, and erecting plans. 2 DEFINITIONS (RESERVED) 3 REQUIREMENTS (RESERVED) 3.1 MACHINE TEMPLATES 3.1.1 Solid lines shall be used for Machine perimeter lines Interior lines of machine template Electric panels Hydraulic tanks 3.1.2 The following information shall be includ
4、ed when applicable Direction of part flow Machine work station center lines Part load position (x) Machine utility connection A = Air CW = City Water IW = Industrial Water S = Steam C = Coolant E = Electrical H = Hydraulic G = Gas L = Lubrication P = Pneumatic D = Duct Load/Unload elevation from fin
5、ish floor to top of equipment that the part is resting on (rails, rollers, etc.) Centerline on all transfer machine stations All machine station numbers All clearances for swing guards, panel door openings, rotating or swiveling heads and moving components Clearance for door swings, guards, etc. sha
6、ll be a dash-dot line Lines indicating items that are connected to machines such as wire drums, feeders, panels, filters, etc Identification of machine conveyance method, walking beam, pallet, shuttle, etc. ENGINEERING CAD & DRAFTING STANDARDS Return to TOC Original Issue: 19960419 Copyright, Ford M
7、otor Company. Latest Re-issue: None F62 Printed copies are uncontrolled. Chip Discharge (CD), Filter Media input/output, and Tool Change Locations Relationship to machine hydraulic tanks, lubricators, electric panel(s), etc., not attached to the machine Wire duct way, connecting machine with remote (not attached) electric panels 4 SPECIFICATIONS (RESERVED) 5 ADDENDUM (RESERVED)