资源描述

1、 This document is restricted and may not be sent outside Navistar, Inc. or reproduced without permission from Corporate Technical Standards. Suppliers are required to assume all patent liability. 2009 by Navistar, Inc. AUGUST 2009 Page 1 of 6 NAVISTAR, INC. CEMS (CORPORATE ENGINEERING MATERIAL SPECI

2、FICATION) NUMBER: CEMS BT-39 TITLE: Determination Of Nonabsorbable Gas In Air Conditioner Refrigerant CURRENT ISSUE DATE: August 2009 WRITTEN/REVIEWED BY: Materials Engineering APPROVED BY: Materials Engineering SUPERSEDES ISSUE OF: October 2001 PRINTED COPIES OF THIS DOCUMENT MUST BE VERIFIED FOR C

3、URRENT REVISION This specification may involve hazardous materials, equipment, and procedures. This specification does not purport to address all of the safety issues associated with its use. The user is responsible to consult appropriate safety and health practices and to determine the applicabilit

4、y of regulatory limits prior to use. Change Notice: Replaced “International Truck and Engine Corporation” with “Navistar, Inc.” per corporate directive. 1.0 SCOPE This is a method for determining the volume percentage of nonabsorbable gas in air conditioner refrigerant. (This method adapted from “De

5、termination of Nonabsorbable Gas in Fluorocarbon Products”, DuPont Test Method B-38.) 2.0 APPARATUS 2.1 Special absorption vessel, No. LG-11119, available from Labglass, Inc., Northwest Boulevard, Vineland, NJ 08360. (See Figure 1, page 4.) 2.2 250 milliliter leveling bulb. 2.3 Glass tee. 2.4 Pinch

6、clamp. 3.0 MATERIAL 3.1 Distilled water. 3.2 Tygon tubing. 3.3 Reagent grade perchloroethylene (tetrachloroethylene). 3.4 “Siliclad” (silicone concentrate) obtainable from the Scientific Glass Apparatus Company, Inc., 737 Broad Street, Bloomfield, NJ 07003. CAUTION: Perchloroethylene is toxic and Si

7、liclad is both toxic and flammable. These materials must be used in adequate ventilation. 4.0 PROCEDURE 4.1 Prepare the special absorption vessel as follows: 4.1.1 wash the vessel in soap and water, and rinse in clear distilled water; 4.1.2 prepare a solution of one part by volume “Siliclad” to 100

8、parts by volume distilled water; 4.1.3 swirl the “Siliclad” solution inside the absorption vessel, completely coating the inner surfaces, allow to stand for at least 5 minutes, and then discard the excess solution; 4.1.4 rinse the vessel with clear distilled water and dry at 212 + 3F (100 + 1C) for

9、at least ten minutes: 4.1.5 the absorption vessel must be re-treated in the foregoing manner when water begins to form droplets instead of a thin film on the vessel walls. Copyright Navistar International Corporation Provided by IHS under license with INTERNNot for ResaleNo reproduction or networkin

10、g permitted without license from IHS-,-,-NUMBER: CEMS BT-39 TITLE: Determination Of Nonabsorbable Gas In Air Conditioner Refrigerant CURRENT ISSUE DATE: August 2009 This document is restricted and may not be sent outside Navistar, Inc. or reproduced without permission from Corporate Technical Standa

11、rds. Suppliers are required to assume all patent liability. 2009 by Navistar, Inc. AUGUST 2009 Page 2 of 6 4.2 After cooling the vessel, attach it to the leveling bulb with tubing. Add 20 to 25 milliliters of distilled water to the bulb and allow it to flow into the vessel. Fill the bulb and vessel

12、with enough perchloroethylene previously saturated with both air and water to force the water in the vessel into the stopcock stem. Make certain that the water level reaches the top of the stopcock stem. Saturated perchloroethylene may be made by bubbling undried air through it. 4.3 Add sufficient w

13、ater to the leveling bulb to form a water seal in the bulb, also. See Figure 2, page 5. 4.4 Attach the absorption vessel-leveling bulb combination and the glass tee-pinch clamp combination to the sampling source with Tygon tubing as shown in Figure 2, page 5. 4.5 Close the stopcock on the absorption

14、 vessel, open the pinch clamp and purge the lines to remove residual air. Purging must be done with the sample container inverted; also, purging must be conducted at a rate slow enough to prevent the introduction of liquid refrigerant into the connecting tube. 4.6 Close the pinch clamp and then clos

15、e the valve on the sample source. Return the sample container to the upright position. Open the stopcock on the absorption vessel, and then open and adjust the valve on the sample source until the flow of gas is barely detectable. Care must be taken to avoid breaking the water seal when introducing

16、the sample. 4.7 Allow the vapor to displace the fluid in the absorption vessel to a volume slightly greater than 100 milliliters. Close the sampling valve and the stopcock, and detach the absorption vessel-leveling bulb combination from the system. 4.8 Adjust the volume of the sample to 100 + 1.0 mi

17、lliliters by quickly turning the stopcock to vent excess sample. This should be done under a slight positive pressure to avoid the entry of extraneous air. Positive pressure can be maintained by keeping the sample vessel slightly below the leveling bulb. Close the stopcock after adjusting the volume

18、 to 100 + 1.0 milliliters. 4.9 Tilt the vessel in such a way as to remove all of the water separating the perchloroethylene and refrigerant gas. See Figure 3, page 6. Do not allow any gas to escape into the lower chamber of the absorption vessel. 4.10 Allow the perchloroethylene to flow into the upp

19、er chamber and gently agitate the vessel to aid in the absorption of the sample gas. 4.11 After 80 to 90 percent of the gas has been absorbed, shake vigorously for 15 to 30 seconds. 4.12 Return the absorption vessel to an upright position and adjust the height of the absorption vessel and the leveli

20、ng bulb until both upper water layers are at the same level. 4.13 Read and record the volume of the vapor remaining in the absorption vessel to + 0.1 milliliter. 4.14 Open the stopcock and vent the remaining vapors. 4.15 Reconnect the absorption vessel-leveling bulb combination to the glass tee-pinc

21、h clamp-sampling source system. 4.16 Repeat steps 4.5 through 4.14, (pages 1 and above), except that in step 4.6 do not return the sample container to an upright position, i.e., draw this sample from the liquid phase in the container. This second run is to compensate for the air introduced by dissol

22、ution of the air that was in the air-saturated perchloroethylene. 4.17 Approximately 35 analyses can be performed with each charge of perchloroethylene; at that point, it should be replaced with freshly saturated perchloroethylene. Copyright Navistar International Corporation Provided by IHS under l

23、icense with INTERNNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-NUMBER: CEMS BT-39 TITLE: Determination Of Nonabsorbable Gas In Air Conditioner Refrigerant CURRENT ISSUE DATE: August 2009 This document is restricted and may not be sent outside Navistar, Inc. or r

24、eproduced without permission from Corporate Technical Standards. Suppliers are required to assume all patent liability. 2009 by Navistar, Inc. AUGUST 2009 Page 3 of 6 5.0 CALCULATIONS Calculate the percentage of nonabsorbable gas in 100 milliliters of sample from the following equation: Nonabsorbabl

25、e gas, % by weight = A-B where: A = volume of sample after absorption when sample is drawn from the vapor phase in the container, ml (first run) B = volume of sample after absorption when sample is drawn from the liquid phase in the container, ml (second run) Since the basis of both runs is 100 mill

26、iliters, the difference between A and B is also the quantity of nonabsorbable gas in percent. 6.0 REPORT Report the percentage by volume of nonabsorbable gas. Copyright Navistar International Corporation Provided by IHS under license with INTERNNot for ResaleNo reproduction or networking permitted w

27、ithout license from IHS-,-,-NUMBER: CEMS BT-39 TITLE: Determination Of Nonabsorbable Gas In Air Conditioner Refrigerant CURRENT ISSUE DATE: August 2009 This document is restricted and may not be sent outside Navistar, Inc. or reproduced without permission from Corporate Technical Standards. Supplier

28、s are required to assume all patent liability. 2009 by Navistar, Inc. AUGUST 2009 Page 4 of 6 Copyright Navistar International Corporation Provided by IHS under license with INTERNNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-NUMBER: CEMS BT-39 TITLE: Determinati

29、on Of Nonabsorbable Gas In Air Conditioner Refrigerant CURRENT ISSUE DATE: August 2009 This document is restricted and may not be sent outside Navistar, Inc. or reproduced without permission from Corporate Technical Standards. Suppliers are required to assume all patent liability. 2009 by Navistar,

30、Inc. AUGUST 2009 Page 5 of 6 Copyright Navistar International Corporation Provided by IHS under license with INTERNNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-NUMBER: CEMS BT-39 TITLE: Determination Of Nonabsorbable Gas In Air Conditioner Refrigerant CURRENT IS

31、SUE DATE: August 2009 This document is restricted and may not be sent outside Navistar, Inc. or reproduced without permission from Corporate Technical Standards. Suppliers are required to assume all patent liability. 2009 by Navistar, Inc. AUGUST 2009 Page 6 of 6 Fig. 3 Apparatus Arrangement for Absorption of Gases by Perchloroethylene Copyright Navistar International Corporation Provided by IHS under license with INTERNNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-

展开阅读全文
相关资源
猜你喜欢
  • ASTM D4440-2008 Standard Test Method for Plastics Dynamic Mechanical Properties Melt Rheology《塑料的标准试验方法 动力机械性能 熔体流变学》.pdf ASTM D4440-2008 Standard Test Method for Plastics Dynamic Mechanical Properties Melt Rheology《塑料的标准试验方法 动力机械性能 熔体流变学》.pdf
  • ASTM D4440-2015 Standard Test Method for Plastics Dynamic Mechanical Properties Melt Rheology《塑料的标准试验方法 动力机械性能熔体流变学》.pdf ASTM D4440-2015 Standard Test Method for Plastics Dynamic Mechanical Properties Melt Rheology《塑料的标准试验方法 动力机械性能熔体流变学》.pdf
  • ASTM D4441-2004 Standard Specification for Aqueous Dispersions of Polytetrafluoroethylene《聚四氟乙烯的水分散体的标准规范》.pdf ASTM D4441-2004 Standard Specification for Aqueous Dispersions of Polytetrafluoroethylene《聚四氟乙烯的水分散体的标准规范》.pdf
  • ASTM D4441-2004(2010) Standard Specification for Aqueous Dispersions of Polytetrafluoroethylene《聚四氟乙烯的水分散体的标准规范》.pdf ASTM D4441-2004(2010) Standard Specification for Aqueous Dispersions of Polytetrafluoroethylene《聚四氟乙烯的水分散体的标准规范》.pdf
  • ASTM D4441-2015 Standard Specification for Aqueous Dispersions of Polytetrafluoroethylene《聚四氟乙烯的水分散体的标准规格》.pdf ASTM D4441-2015 Standard Specification for Aqueous Dispersions of Polytetrafluoroethylene《聚四氟乙烯的水分散体的标准规格》.pdf
  • ASTM D4442-1992(2003) Standard Test Methods for Direct Moisture Content Measurement of Wood and Wood-Base Materials《木材和木基材料含水量的直接测量用试验方法》.pdf ASTM D4442-1992(2003) Standard Test Methods for Direct Moisture Content Measurement of Wood and Wood-Base Materials《木材和木基材料含水量的直接测量用试验方法》.pdf
  • ASTM D4442-2007 Standard Test Methods for Direct Moisture Content Measurement of Wood and Wood-Base Materials《木材和木基材料的直接水分测量用标准试验方法》.pdf ASTM D4442-2007 Standard Test Methods for Direct Moisture Content Measurement of Wood and Wood-Base Materials《木材和木基材料的直接水分测量用标准试验方法》.pdf
  • ASTM D4442-2015 Standard Test Methods for Direct Moisture Content Measurement of Wood and Wood-Based Materials《木材和木基材料含水量直接测量的标准试验方法》.pdf ASTM D4442-2015 Standard Test Methods for Direct Moisture Content Measurement of Wood and Wood-Based Materials《木材和木基材料含水量直接测量的标准试验方法》.pdf
  • ASTM D4442-2016 Standard Test Methods for Direct Moisture Content Measurement of Wood and Wood-Based Materials《木材和木基材料的直接水分测量用标准试验方法》.pdf ASTM D4442-2016 Standard Test Methods for Direct Moisture Content Measurement of Wood and Wood-Based Materials《木材和木基材料的直接水分测量用标准试验方法》.pdf
  • 相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > 其他

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1