1、MIL-P-l5736D(SHIPS) 9 August 1965 SUPERSEDING MIL-P-l5736C(SHIPS) 9 July 1956 (See 6.4) MILITARY SPECIFICATION POWER SUPPLIES, METALLIC RECTIFIER, NAVAL SHIPBOARD 1. SCOPE 1.1 Scope - This specification covers general requirements for metallic rectifier type power supplies 1.2 Classification - Power

2、 supplies shall be of the following classes as specified (see 6.1): Class R - Regulated Class N R - Nonregulated - for naval shipboard use. 2. APPLICABLE DOCUMENTS 2.1 The following documents of the issue in effect on date of invitation for bids or request for proposal, form a part of the specificat

3、ion to the extent specified herein. SPECIFICATIONS FEDERAL FF-B-171 - Bearings, Ball, Annular (General Purpose) MILITARY MIL-(2-25 - Capacitors, Fixed, Paper-Dielectric, Direct-Current (Hermetically Sealed in MIL-C-62 - Capacitors, Fixed, Electrolytic (DC, Aluminum, Dry Electrolyte, Polarized) MIL-S

4、-901 - Shock Tests, H. I. (High Impact), Shipboard Machinery, Equipment and Systems, MIL-E-917 - Electric Power Equipment, Basic Requirements for (Naval Shipboard Use). MIL-D-963 - Drawings, Electrical, Hull and Mechanical Equipment for Naval Shipboard Use. MIL-I -1361 - Instruments, Electrical Meas

5、uring, Shunts, Resistors and Transformers (Ship MIL-R-2033 - Relays for Naval Shipboard Electrical Service. MIL-E-2036 - Enclosures for Electric and Electronic Equipment, Naval Shipboard. MIL-C-2174 - Controllers, Direct-Current, Naval Shipboard. MIL-(2-2212 - Controllers, Alternating-Current, Naval

6、 Shipboard. MIL-C-3965 - Capacitors, Fixed, Non-Solid Electrolytic, (Tantalum, Foil and Sintered-Slug), MIL-M-10304 - Meters, Electrical Indicating, Panel Type, Ruggedized, General Specification MIL-M-15071 - Manuals, Equipment and Systems. MIL-F -15160 - Fuses, Instrument, Power, and Telephone. MIL

7、-S -15291 - Switches, Rotary, Snap Action. MIL-L - 15719 - Lubricating Grease (High-Temperature, Electric Motor, Ball and Roller Metallic Cases), General Specification for. General Specification for. Requirements for. and Shore Use). General Specification for. for. Bearings). Provided by IHSNot for

8、ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-P-L533bD bl 999790b 008b520 T D MIL- P- 15736D(SHIPS) MIL-M- 16034 - Meters. Electrical-Indicating (Switchboard aiid Portable Types). MIL -0- 16485 - Ohmtr et er s Insulation - Resistanc e -1ndi cating, Portable. MIL-T-16

9、764 - Terminal Boards. MIL-E-17555 - Electronic and Electrical Equipment and Associated Repair Parts. Preparation MIL-S-18396 - Switches, Meter and Control. Naval Shipboard. MIL-R-19523 - Relays, Auxiliary, Naval Shipboard. MIL-C-19976 - Capacitors, Fixed. Plastic (or Paper-Plastic) Dielectric (Herm

10、etically Sealed MIL-F-21346 - Fuseholders. Block and Plug Type and Associated Electrical Clips. General MIL-S-21604 - Switches, Rotary. Multipole and Selector Type. 1 to 10 Amperes. MIL-C-26655 - Capacitors. Fixed. Solid Electrolyte. Tantalum. General Specification for. for Delivery of. in Metallic.

11、 Ceramic, or Glass Cases), General Specification for. Specification for. STAhDARDS MILITARY MIL-STD-108 - Definitions of and Basic Requirements for Enclosures for Electric and Electron- MIL-STD-167 - Mechanical Vibrations of Shipboard Equipment. MIL-STD-701 - Preferred and Guidance Lists of Semicond

12、uctor Devices. MIL-STD-740 - Noise Measurements of Shipboard Machinery and Equipment. MIL-STD-761 - Electric Power, Alternating Current for Shipboard Use, Characteristics and ic Equipment. Utilization of. DRAWINGS BUREAU OF SHIPS 9000-S6202-F-73907 - Light, Indicator, Switchboard, 2 Lamp-SPF, Types

13、B-27A Through B-27G. 9000-S6202-74228 9000-S6202-74229 9000-S6202-74230 - Fuse Holder, Double Dead Front Blown Fuse Indicator Type FHLlOG, - Fuse Holder, Single for I-1/4 Inch by 1 4 Inch Fuses with Blown Fuse - Fuse Holder, Single Dead Front, Blown Fuse Indicator Type FHLlZG, 30 Amp, 120V, i-1/4 In

14、ch by 1/4 Inch Fuse. Indicator, Type FHLllG. 450V, 1-3/32 Inch by 1-1,2 Inch Fuses. (See supplement 1 for list of applicable detail specifications. (Copies of specifications, standards, drawings, and publications required by suppliers in connection with specific procurement functions should be obtai

15、ned from the procuring activity or as directed by the contracting officer. ) 2.2 Other publications. - The following document forms a part of this specification to the extent speci- fied herein. Unless otherwise indicated, the issue in effect on date of invitation for bids or request for proposal sh

16、all apply. OFFICIAL CLASSIFICATIOK COMMITTEE Uniform Freight Classification Ratings, Rules and Regulations (Application for copies should be addressed to the Official Classification Committee, 1 Park Avenue at 33rd Street, New York, N.Y. 100016). 3. REQUIREMENTS 3.1 Detail requirements. - Detail req

17、uirements shall be as specified in the applicable detail specifi- cation. In the event of any conflict between the requirements of this specification and the individual detail specification, the latter shall govern (see 6. i). 2 Provided by IHSNot for ResaleNo reproduction or networking permitted wi

18、thout license from IHS-,-,-MIL-P-1573bD bl 979990b 00Bb521 L - MIL-P- 15736D(SHIPS) 3.2 Qualification. - The power supply furnished under this specification shall be a product which has been tested ana passed the qualification tests specified herein and has been listed on or approved for listing on

19、the applicable qualified products list. 3.3 General requirements. - The equipment shall comply with the requirements of MIL-E-917. except as specifiedherein or in the individual detail specification. Where a requirement of this specification conflicts with a requirement of MIL-E-917, the requirement

20、 of this specification shall govern. 3.4 Definitions. - The definitions specified in 3.4.1 through 3.4.7 shall apply to the various technical terms wherever such terms appear in this specification. 3.4.1 Rectifying element. - A rectifying element is a circuit element which conducts current effective

21、ly in one direction only. 3.4.2 Power su direct curreder. It does not include rotary machinery such as motor generators or dynamotors. For the purpose of this specification, a power supply shall be considered to be all the components, subas- semblies and assemblies necessary to give specified perfor

22、mance. 1 .-A power supply is an assembly used to convert alternating current (a.c.) power to 3.4.2.1 Power supply, regulated (class R.).-A regulated power supply is one which makes use of special components having the primary function of automatically controlling output voltage, current. or both. 3.

23、4.2.2 Power supply, nonregulated (class NR).- A nonregulated power supply is one which does not make use of any components having a primary function of automatically controlling output voltage, current, or both. Output regulation is entirely dependent on the inherent regulation of basic components o

24、f power transformers and power rectifying elements and the function of the dummy loads, if used. Class NR power supplies may contain magnetic amplifiers or silicon controlled rectifiers for adjustment of output voltage. 3.4.3 Battery charger. - A battery charger is a device consisting of one or more

25、 components utilizing an alternating current source to reactivate batteries in which reversible chemical reaction occurs. For purpose of this specification, a battery charger, using metallic rectifiers for converting a.c. power to d.c. power, is also a power supply. 3.4.4 fill-wave rectification. -

26、Full-wave rectification is rectification in which both halves of the a. c. cycle are transmitted as unidirectional current. 3.4.5 Ripple voltage. - The ripple voltage is the alternating component of a substantially unidirectional voltage. 3.4.6 Percent ripple voltage. - The percent ripple voltage is

27、 the ratio in percent of the effective (r. m. s) 3.4.7 Dummy load.-A dummy load is a component part of a power supply (usually a resistor) which is value of the ripple voltage in the pulsating voltage to the average value of the pulsating voltage. connected across the output circuit for the purpose

28、of partially loading the power supply to improve output performance (usually voltage stabiliw or regulation or both) over the rated load range. When resistive, it is frequently termed a bleeder resistor. 3.5 Design requirements. - 3.5.1 Operation. - Power supplies shall provide d. c. output as requi

29、red by the individual detail speci- fication. All power supplies shall have a transformer input so that the d. c. output circuit is isolated from the a.c. input. Rectification and control (that is, regulation) of any power handled by the equipment shall be accomplished by static components such as m

30、agnetic amplifiers, metallic rectifiers or silicon controlled rectifiers. Power-handling rectifier circuits shall provide full-wave rectification. 3.5.2 Electrical rating and performance. - 3.5.2.1 A. c. voltape. - Equipment shall be designed to operate from Type I power as described by MIL-STD-761.

31、 Input voltage (normally either 440 or 115 volts) shall be as ,specified in the individual 3 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-P-1573bD bl W 999990b 00b522 3 W detail specification (see 6.1). Equipment shall operate as specified wit

32、hout adjustment with variations of plus or minus 5 percent (average line-to-line, 3 phase) of rated voltage. Likewise, Performance shall not be affected by 3 percent unbalance between phase voltages. 3.5.2.1.1 A.C. input transients.-When the a.c. input supply voltage suffers a momentary (total dura-

33、 tion up to 2.0 seconds) rise or dropof up to 18 percent of the nominal value the power supply shall: (a) Be affected in neither calibration or adjustment, nor shall the life of any component be shortened. (b) Suffer a change of output voltage of a value not to exceed that of the a. c. input, percen

34、tage-wise. For example if the a. c. voltage changes by 10 percent, the d. c. output voltage shall not change by more than 10 percent. 3.5.2.2 Frequency.- Unless otherwise specified in the individual detail specification (see 6.1) equip- ment shall be designed to operate on a supply voltage with freq

35、uency of 60 cycles per second (cps). Equip- ment shall operate as specified (see 6.1), without adjustment, with variations of plus or minus 5 percent of rated frequency. 3.5.2.3 Phases and balances.- Equipment shall be designed for operation on a single phase or 3-phase, 3-wire ungrounded power sour

36、ce as specified in the individual detail specification. In case of a 3-phase, 3-wire ungrounded circuit. current consumed by the equipment shall be balanced to the extent that the current in any wire shall not differ by more than 10 percent from the average current in the three wires. 3.5.2.4 D.C. o

37、utput.-All equipment shall operate over the entire output range as specified (see 6.1) with variation of voltage, frequency and ambient as specified in 3.5.2.1, 3.5.2.2 and 3.5.3.2. This shall include any special output performance requirements such as voltage regulation and adjustment, current reg-

38、 ulation and adjustment, automatic voltage cutoff or transfer, current limiting, current overload, transient performance and ripple voltage content. By definition, class R power supplies shall always have automatic control of output voltage, current or both. 3.5.2.4.1 Remote sensing-Where remote sen

39、sing is required for operation, or is permitted or speci- fied by an individual detail specification, the power supply shall be fitted with terminals which may be con- nected at installation to a remote load point so that the power supply can compensate (or compound) for voltage drop between its out

40、put terminals and the load terminals. Current drawn by such a sensing circuit shall not exceed 1 ampere. (See 3.5.2.8 for required fail-safe features associated with remote sensing circuits). 3.5.2.5 Duty. - Unless otherwise specified in the individual detail specification, equipment shall be de- -

41、signed to operate continuously at the specified rating. If intermittent duty is specified. a clear description of the duty cycle shall be given. 3.5.2.6 Type of load.- The type of load may be battery charging, capacitive, inductive (including d.c. motor), resistive or any combination which may be sp

42、ecified in the individual detail specification. Unless otherwise specified, battery charging loads shall be considered to be lead-acid type batteries. Regardless of the type of load specified, equipment shall operate satisfactorily at rated output voltage and current when connected to any of the abo

43、ve types of load, without hunting or oscillation of output voltage. For purposes of this specification, oscillation shall be defined as any sustained variation of output voltage due to inter- action between power supply and load, for example, when the load is a regulated motor-generator. 3.5.2.7 Vol

44、tage ripple. - The maximum allowable voltage ripple in the output shall normally be speci- fied in terms of percent. Unless otherwise specified in the individual detail specification the meaning of percent value shall be a5 defined herein (see 3.4.6). The wave form of the a.c. component of the outpu

45、t voltage shall be such that the peak-to-peak value of voltage ripple shall not exceed three times the r.m.s. value when both quantities are measured in accordance with 4.5.10.6. 3.5.2.8 Circuit and component protection means. - The following safety and fail-safe design features shall be provided in

46、 all power supplies: 4 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-P-1573bD bL 9999YOb 00b5Z3 5 = MIL-P-l5?36D(SHIPS) (a) Circuits using ari,;:a:. ) All parts which require crrvicinl: repair, replacement, or periodic adjustment during the lif

47、e of the equipment are readily accessible. (c) All components are marked uith identifying symbols and these symbols agree with those used on the approved drawing; (d) All terminals of all components and terminal boards are marked with identifying letters and numbers. or both, and this identification

48、 agrees with those used on the approved drawing. (e) Wire used for interconnecting components is of the type shown on the approved drawing. (f ) All wiring is neatly formed into groups and laced with non-flammable glass cord and supported or clamped in a manner which will prevent chafing of the insu

49、lation due to vibration and shock. (g) Cable clamps used are of non-flammable material. (h) There are no splices in any of the wires. (i) Wire groups from hinged doors and panels are formed and clamped in a manner that sharp bends. do not occur with the panel or door in either the open or closed position. (j) Sufficient slack in wiring is allowed so that the weight of the harness is not supported by the terminal connections and so that at least two replacements can be made if lugs are clipped off at the