NAVY UFGS-06 20 00-2012 FINISH CARPENTRY《整饰的木器》.pdf

上传人:medalangle361 文档编号:984714 上传时间:2019-03-12 格式:PDF 页数:25 大小:93.71KB
下载 相关 举报
NAVY UFGS-06 20 00-2012 FINISH CARPENTRY《整饰的木器》.pdf_第1页
第1页 / 共25页
NAVY UFGS-06 20 00-2012 FINISH CARPENTRY《整饰的木器》.pdf_第2页
第2页 / 共25页
NAVY UFGS-06 20 00-2012 FINISH CARPENTRY《整饰的木器》.pdf_第3页
第3页 / 共25页
NAVY UFGS-06 20 00-2012 FINISH CARPENTRY《整饰的木器》.pdf_第4页
第4页 / 共25页
NAVY UFGS-06 20 00-2012 FINISH CARPENTRY《整饰的木器》.pdf_第5页
第5页 / 共25页
点击查看更多>>
资源描述

1、*USACE / NAVFAC / AFCESA / NASA UFGS-06 20 00 (February 2012)-Preparing Activity: NAVFAC Superceding UFGS-06 20 00 (August 2008)UFGS-06 20 00 (April 2008)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated January 2012*SECTION TABLE OF CONTENTSDIVISION 06 - WOOD, PLAST

2、ICS, AND COMPOSITESSECTION 06 20 00FINISH CARPENTRY02/12PART 1 GENERAL1.1 REFERENCES1.2 SUBMITTALS1.3 DETAIL DRAWINGS1.4 CERTIFICATES1.5 DELIVERY, STORAGE, AND HANDLING1.6 QUALITY ASSURANCE1.6.1 Lumber1.6.2 Plywood1.6.3 Hardboard and Particleboard1.6.4 Pressure-Treated Lumber and Plywood1.6.5 Nonpre

3、ssure-Treated Woodwork and Millwork1.6.6 Fire-Retardant Treated LumberPART 2 PRODUCTS2.1 WOOD2.1.1 Sizes and Patterns of Wood Products2.1.2 Trim, Finish, and Frames2.1.3 Utility Shelving2.1.4 Softwood Plywood2.1.5 Hardwood Plywood2.1.6 Hardboard2.1.7 Particleboard2.1.8 Stairs2.1.9 Shoe Mold2.1.10 Wo

4、od Seats2.1.11 Wood Bumpers2.1.12 Catwalks2.1.13 Siding2.1.13.1 Horizontal Hardboard Siding2.1.13.2 Panel Hardboard Siding2.1.13.3 Horizontal Plywood SidingSECTION 06 20 00 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.1.13.4 Panel Plywood

5、Siding2.1.13.5 Horizontal Rated Siding2.1.13.6 Panel Rated Siding2.1.13.7 Wood Siding2.1.13.8 Wood Structural Panels2.1.13.9 Epoxy-Aggregate Panels2.2 SOFFITS2.2.1 Hardboard and Plywood2.3 FASCIAS AND TRIM2.3.1 Wood2.4 WOOD SHINGLES2.5 COUNTER TOPS2.5.1 Laminated Plastic2.5.1.1 Countertop Finish2.5.

6、1.2 Backing Sheet2.5.2 Solid Surface2.6 MOISTURE CONTENT OF WOOD PRODUCTS2.7 PRESERVATIVE TREATMENT OF WOOD PRODUCTS2.7.1 Nonpressure Treatment2.7.2 Pressure Treatment2.8 FIRE-RETARDANT TREATMENT2.8.1 Wood Products2.9 HARDWARE2.9.1 Wood Screws2.9.2 Bolts, Nuts, Lag Screws, and Studs2.9.3 Nails2.9.4

7、Adjustable Shelf Standards2.9.5 Vertical Slotted Shelf Standards2.9.6 Closet Hanger Rods2.10 FABRICATION2.10.1 Quality Standards (QS)2.10.2 Countertops2.10.3 Cabinets2.10.3.1 Cabinet Hardware2.10.3.2 Finish2.10.4 Workbenches2.10.5 Casework With Transparent Finish (CTF)2.10.5.1 AWI Quality Grade (CTF

8、)2.10.5.2 Construction (CTF)2.10.5.3 Exposed Parts2.10.5.4 Semi-Exposed Parts2.10.6 Casework With High Pressure Laminate Finish (CHPL)2.10.6.1 AWI Quality Grade (CHPL)2.10.6.2 Construction (CHPL)2.10.6.3 Exposed Surfaces2.10.6.4 Semi-Exposed SurfacesPART 3 EXECUTION3.1 FINISH WORK3.1.1 Exterior Fini

9、sh Work3.1.2 Interior Finish Work3.1.3 Door Frames3.1.4 Thresholds3.1.5 Window Stools and Aprons3.1.6 Bases3.1.7 Finish Stair Work3.2 SHELVING3.2.1 Linen ClosetsSECTION 06 20 00 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-3.2.2 Storage Room

10、s3.2.3 Room Closets3.2.4 Cleaning-Gear Closets3.3 CLOTHES HANGER RODS3.4 MISCELLANEOUS3.4.1 Counters3.4.2 Cabinets3.4.3 Workbenches3.4.4 Wood Seats3.4.5 Wood Bumpers3.4.6 Catwalks in Attic Spaces3.5 SIDING3.5.1 Installation of Siding3.5.2 Horizontal Siding3.5.3 Vertical Board Siding3.5.4 Vertical Bo

11、ard and Batten Siding3.5.5 Panel Siding3.5.6 Epoxy-Aggregate Coated Panels3.6 SOFFITS3.6.1 Wood3.7 FASCIAS AND EXTERIOR TRIM3.8 MOLDING AND INTERIOR TRIM3.9 WOOD SHINGLES- End of Section Table of Contents -SECTION 06 20 00 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted wi

12、thout license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-06 20 00 (February 2012)-Preparing Activity: NAVFAC Superceding UFGS-06 20 00 (August 2008)UFGS-06 20 00 (April 2008)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated January 2012*SECTION 06 20 00FINISH

13、CARPENTRY02/12*NOTE: This guide specification covers general exterior and interior finish carpentry.Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard when editing this guide specification or preparing new project specification sections. Edit this guide specificati

14、on for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brackets are present.Comments, suggestions and recommen

15、ded changes for this guide specification are welcome and should be submitted as a Criteria Change Request (CCR).*NOTE: On the drawings, show:1. Location, size, type, and thickness of materials;2. Size and spacing of fasteners;3. Details of millwork;4. Color and/or pattern of prefinished material;5.

16、Profile and size of trim; and6. Species of any wood that is to be stain, natural, or transparent finish.*SECTION 06 20 00 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-PART 1 GENERAL1.1 REFERENCES*NOTE: This paragraph is used to list the publ

17、ications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Sections Refere

18、nce Article to automatically place the reference in the Reference Article. Also use the Reference Wizards Check Reference feature to update the issue dates.References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile refere

19、nces in the publish print process.*The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.AMERICAN HARDBOARD ASSOCIATION (AHA)AHA A135.6 (1998; R 2006) Hardboard SidingAMERICAN LUMBER ST

20、ANDARDS COMMITTEE (ALSC)ALSC PS 20 (2010) American Softwood Lumber StandardAMERICAN WOOD PROTECTION ASSOCIATION (AWPA)AWPA C20 (2003) Structural Lumber Fire-Retardant Treatment by Pressure ProcessesAWPA C27 (2002) Plywood - Fire-Retardant Treatment by Pressure ProcessesAWPA M2 (2007) Standard for In

21、spection of Treated Wood ProductsAWPA M4 (2002) Standard for the Care of Preservative-Treated Wood ProductsAWPA P5 (2009) Standard for Waterborne PreservativesAPA - THE ENGINEERED WOOD ASSOCIATION (APA)APA E445 (2002) Performance Standards and Qualification Policy for Structural-Use Panels (APA PRP-

22、108)SECTION 06 20 00 Page 5Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-APA L870 (2010) Voluntary Product Standard, PS 1-09, Structural PlywoodAPA S350 (2011) Performance Standard for Wood-Based Structural-Use PanelsARCHITECTURAL WOODWORK INSTITUT

23、E (AWI)AWI Qual Stds (8th Edition) AWI Quality StandardsASME INTERNATIONAL (ASME)ASME B18.2.1 (2010) Square and Hex Bolts and Screws (Inch Series)ASME B18.2.2 (2010) Standard for Square and Hex NutsASME B18.6.1 (1981; R 2008) Wood Screws (Inch Series)ASTM INTERNATIONAL (ASTM)ASTM D2898 (2010) Accele

24、rated Weathering of Fire-Retardant-Treated Wood for Fire TestingASTM F 547 (2006) Nails for Use with Wood and Wood-Base MaterialsBUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)ANSI/BHMA A156.9 (2010) Cabinet HardwareCOMPOSITE PANEL ASSOCIATION (CPA)CPA A208.1 (2009) Medium Density Fiberboard (MDF

25、) For Interior ApplicationsHARDWOOD PLYWOOD AND VENEER ASSOCIATION (HPVA)HPVA HP-1 (2009) American National Standard for Hardwood and Decorative PlywoodNATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)ANSI/NEMA LD 3 (2005) Standard for High-Pressure Decorative LaminatesNATIONAL HARDWOOD LUMBER AS

26、SOCIATION (NHLA)NHLA Rules (2007) Rules for the Measurement “DO“ for District Office (Engineering Division or other organization in the District Office); “AO“ for Area Office; “RO“ for Resident Office; and “PO“ for Project Office. Codes SECTION 06 20 00 Page 7Provided by IHSNot for ResaleNo reproduc

27、tion or networking permitted without license from IHS-,-,-following the “G“ typically are not used for Navy, Air Force, and NASA projects.Choose the first bracketed item for Navy, Air Force and NASA projects, or choose the second bracketed item for Army projects.*Government approval is required for

28、submittals with a “G“ designation; submittals not having a “G“ designation are for Contractor Quality Control approval. information only. When used, a designation following the “G“ designation identifies the office that will review the submittal for the Government. The following shall be submitted i

29、n accordance with Section 01 33 00 SUBMITTAL PROCEDURES:SD-02 Shop DrawingsDetail DrawingsSD-03 Product DataSiding; _, _Epoxy-Aggregate Panels; _, _Manufacturers printed data, showing texture, density, catalog cuts, and installation instructions.Wood Items, Siding, and Trim; _, _Manufacturers printe

30、d data indicating the usage of engineered or recycled wood products, and environmentally safe preservatives.SD-04 SamplesSiding; _, _Wood Shingles; _, _Moldings; _, _Fascias and Trim; _, _Samples shall be of sufficient size to show patterns, color ranges, and types, as applicable, of the material pr

31、oposed to be used.SD-07 CertificatesCertificates of gradeCertificates of compliance1.3 DETAIL DRAWINGSThe Contractor shall submit detail drawings showing fabricated items and special mill and woodwork items. Drawings shall indicate materials and details of construction, methods of fastening, erectio

32、n, and installation.SECTION 06 20 00 Page 8Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-1.4 CERTIFICATESProvide certificates of grade from the grading agency on graded but unmarked lumber or plywood attesting that materials meet the grade requirem

33、ents specified herein.Provide certificates of compliance unless materials bear certification markings or statements.1.5 DELIVERY, STORAGE, AND HANDLINGDeliver lumber, plywood, trim, and millwork to job site in an undamaged condition. Stack materials to ensure ventilation and drainage. Protect agains

34、t dampness before and after delivery. Store materials under cover in a well-ventilated enclosure and protect against extreme changes in temperature and humidity. Do not store products in building until wet trade materials are dry.1.6 QUALITY ASSURANCE1.6.1 LumberIdentify each piece or each bundle of

35、 lumber, millwork, and trim by the grade mark of a recognized association or independent inspection agency that is certified by the Board of Review, American Lumber Standards Committee, to grade the species.1.6.2 PlywoodEach sheet of plywood shall bear the mark of a recognized association or indepen

36、dent inspection agency that maintains continuing control over quality of the plywood. Mark shall identify plywood by species group or span rating, and shall show exposure durability classification, grade, and compliance with APA L870.1.6.3 Hardboard and ParticleboardMaterials shall bear a marking or

37、 statement identifying the producer and the applicable standard.1.6.4 Pressure-Treated Lumber and PlywoodEach treated piece shall be inspected in accordance with AWPA M2.1.6.5 Nonpressure-Treated Woodwork and MillworkMark, stamp, or label, indicating compliance with WDMA I.S. 4.1.6.6 Fire-Retardant

38、Treated LumberEach piece to bear Underwriters Laboratories label or the label of another nationally recognized independent testing laboratory.SECTION 06 20 00 Page 9Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-PART 2 PRODUCTS2.1 WOOD2.1.1 Sizes an

39、d Patterns of Wood ProductsYard and board lumber sizes shall conform to ALSC PS 20. Provide shaped lumber and millwork in the patterns indicated and standard patterns of the association covering the species. Size references, unless otherwise specified, are nominal sizes, and actual sizes shall be wi

40、thin manufacturing tolerances allowed by the applicable standard.2.1.2 Trim, Finish, and FramesProvide species and grades listed for materials to be paint finished. Provide materials that are to be stain, natural, or transparent finished one grade higher than that listed. Provide species indicated f

41、or materials to be transparent finished. Run trim, except window stools and aprons with hollow backs.*NOTE: Edit table to delete unsuitable species. For small projects, species that are not readily available locally may be deleted.*TABLE OF GRADES FOR WOOD TO RECEIVE PAINT FINISHGrading Rules Specie

42、s Exterior and Interior Trim, Finish, and FramesWWPA G-5 standard grading rulesAspen, Douglas Fir-Larch, Douglas Fir South, Engelmann Spruce-Lodgepole Pine, Engelmann Spruce, Hem-Fir, Idaho White Pine, Lodgepole Pine, Mountain Hemlock, Mountain Hemlock-Hem-Fir, Ponderosa Pine-Sugar Pine, (Ponderosa

43、Pine-Lodgepole Pine,) White Woods, (Western Woods,) Western Cedars, Western HemlockAll Species: C or plywood, interior type, Grade A-B, 13 mm 1/2 inch thick, any species group.2.1.4 Softwood PlywoodAPA L870, thicknesses as indicated.a. Plywood for Soffits: Exterior type, B-B medium density overlay.b

44、. Plywood for Shelving: Interior type, A-B B-B Grade, any species group.c. Plywood for Countertops: Exterior type, A-C Grade.2.1.5 Hardwood Plywood*NOTE: Retain bracketed option describing core construction if only hardwood veneer or lumber core construction is acceptable.*HPVA HP-1, Type Technical (Exterior) I (Exterior) II (Interior) III (Interior), Premium (A) Good (1) Sound (2) Utility (3) Backing SECTION 06 20 00 Page 11Provi

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > 其他

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1