1、*USACE / NAVFAC / AFCESA / NASA UFGS-28 31 02.00 20 (February 2010)-Preparing Activity: NAVFAC SupersedingUFGS-28 31 02.00 20 (November 2009)UFGS-28 31 02.00 20 (April 2006)UFGS-13854N (August 2000)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated April 2010*SECTION

2、TABLE OF CONTENTSDIVISION 28 - ELECTRONIC SAFETY AND SECURITYSECTION 28 31 02.00 20FIRE ALARM REPORTING SYSTEMS - DIGITAL COMMUNICATORS02/10PART 1 GENERAL1.1 REFERENCES1.2 RELATED REQUIREMENTS1.3 DESCRIPTION OF WORK1.4 SYSTEM DESCRIPTION1.4.1 SYSTEM DESIGN1.4.2 Power Calculations1.5 SUBMITTALS1.6 QU

3、ALITY ASSURANCE1.6.1 Qualifications of Installer1.6.2 Manufacturers Representative1.6.3 Qualifications of System Technician1.6.4 Regulatory Requirements1.6.5 Drawing Requirements1.6.5.1 System Floor Plans1.6.5.2 System Wiring Diagrams1.6.5.3 System As-built Drawings1.6.6 System UL Listing or FM Appr

4、oval1.7 MAINTENANCE1.7.1 Spare Parts1.7.2 ManualsPART 2 PRODUCTS2.1 DIGITAL ALARM COMMUNICATOR TRANSMITTER (DACT)2.1.1 Transmitter Identity Code2.1.2 Transmission Confirmation2.1.3 Automatic DACT Test2.1.4 Battery Supervision2.1.5 Trouble Supervision2.1.6 DACT Power Supplies2.1.6.1 Battery Power Sup

5、ply2.2 OVERVOLTAGE AND SURGE PROTECTIONSECTION 28 31 02.00 20 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.2.1 Power Line Surge Protection2.2.2 Communications Link Surge Protection2.2.3 Sensor Wiring Surge Protection2.3 DIGITAL ALARM COMMU

6、NICATOR RECEIVER (DACR)2.3.1 Display2.3.2 Memory2.3.3 Digital Clock2.3.4 Printers2.3.5 Audible Trouble and Alarm Devices2.3.6 Power Supplies2.3.7 Emergency Power Source2.3.7.1 Emergency Power Switchover2.3.8 Console Battery Charger2.3.9 Console Supervision2.3.10 Power Supervision2.3.11 Electrical Co

7、nnections2.4 CONDUIT2.4.1 Rigid Steel Conduit (Zinc-Coated)2.4.2 Intermediate Metal Conduit (IMC)2.4.3 Electrical Metallic Tubing (EMT)2.5 OUTLET BOXES2.6 WIRING2.7 GROUND RODSPART 3 EXECUTION3.1 INSTALLATION3.1.1 Continuity of Protection3.2 FIELD QUALITY CONTROL3.2.1 Preliminary Testing3.3 FINAL AC

8、CEPTANCE TEST3.4 ADDITIONAL TESTS3.5 MAINTENANCE INSTRUCTIONS3.6 INSTRUCTION OF GOVERNMENT PERSONNEL- End of Section Table of Contents -SECTION 28 31 02.00 20 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-

9、28 31 02.00 20 (February 2010)-Preparing Activity: NAVFAC SupersedingUFGS-28 31 02.00 20 (November 2009)UFGS-28 31 02.00 20 (April 2006)UFGS-13854N (August 2000)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated April 2010*SECTION 28 31 02.00 20FIRE ALARM REPORTING SY

10、STEMS - DIGITAL COMMUNICATORS02/10*NOTE: This guide specification covers the requirements for a complete base-wide municipal-type fire alarm system which provides reporting of fire alarms to a central location through the use of digital alarm communicator transmitters connected to various building i

11、nterior fire alarm systems.Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not b

12、rackets are present.Comments and suggestions on this guide specification are welcome and should be directed to the technical proponent of the specification. A listing of Technical Proponents, including their organization designation and telephone number, is on the Internet.Recommended changes to a U

13、FGS should be submitted as a Criteria Change Request (CCR).*NOTE: Interior building fire alarm systems are covered by Section 28 31 74.00 20 INTERIOR FIRE DETECTION AND ALARM SYSTEM.*NOTE: The following information shall be shown on the drawings:1. A complete layout of the fire alarm watch office sh

14、owing locations of new equipment and existing SECTION 28 31 02.00 20 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-equipment that is to remain. Show points of connection to power supplies.2. Locations of digital alarm communicator transmitter

15、s to be installed.3. Locations of local alarm systems and initiating devices to be connected to digital alarm communicator transmitters, and points of connection to AC power (Note: AC power shall be obtained ahead of the main disconnects).4. A table showing each transmitter location, phone number, a

16、nd the number of auxiliary zones to be connected and their descriptions (e.g., Bldg. 591, phone numbers: 555-1212, 555-1213; Zone 1 - FACP Zone 1; Zone 2 - FACP Zone 2; Zone 3 - Sprinkler Riser, etc.).*PART 1 GENERAL1.1 REFERENCES*NOTE: This paragraph is used to list the publications cited in the te

17、xt of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Sections Reference Article to automatic

18、ally place the reference in the Reference Article. Also use the Reference Wizards Check Reference feature to update the issue dates.References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish prin

19、t process.*The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.FM GLOBAL (FM)FM APP GUIDE (updated on-line) Approval Guide http:/ OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)IEEE C6

20、2.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power CircuitsIEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage SECTION 28 31 02.00 20 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without lic

21、ense from IHS-,-,-(1000 V and Less) AC Power CircuitsNATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)ANSI C80.1 (2005) American National Standard for Electrical Rigid Steel Conduit (ERSC)ANSI C80.3 (2005) American National Standard for Electrical Metallic Tubing (EMT)NATIONAL FIRE PROTECTION ASS

22、OCIATION (NFPA)NFPA 70 (2008; AMD 1 2008) National Electrical CodeNFPA 72 (2010; Am 10-2; Am 10-3; Proposed Am 971) National Fire Alarm and Signaling CodeUNDERWRITERS LABORATORIES (UL)UL 1242 (2006; R 2001 thru 2007) Standard for Electrical Intermediate Metal Conduit - SteelUL 467 (2007) Grounding a

23、nd Bonding EquipmentUL 514A (2004; R 2005 thru 2009) Metallic Outlet BoxesUL 514B (2004; R 2006 thru 2009) Conduit, Tubing and Cable FittingsUL Fire Prot Dir (2009) Fire Protection Equipment Directory1.2 RELATED REQUIREMENTSMaterials shall conform to Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS

24、 AND METHODS, with the additions and modifications specified herein1.3 DESCRIPTION OF WORKWork includes provision of labor, material, tools and equipment necessary for and incidental to the provision of a complete and usable base-wide digital alarm communicator fire alarm system. The system shall be

25、 in accordance with NFPA 72 and as specified herein. Materials and equipment furnished under this contract shall be the current products of one manufacturer regularly engaged in production of such equipment. Electronics shall be solid state. The system shall be listed by the Underwriters Laboratorie

26、s (UL) or approved by Factory Mutual Engineering and Research (FM) as a public fire reporting system, in accordance with NFPA 72. Equipment used to interconnect the system with local building fire alarm systems shall be UL listed or FM approved, in accordance with NFPA 72. As an alternate to the abo

27、ve listing requirements, all equipment shall be UL Fire Prot Dir listed or FM APP GUIDE approved as a proprietary protective signaling system in accordance with NFPA 72, provided the system meets the requirements as specified herein without violating such listing or approval. The system shall confor

28、m to the Federal Communications Commissions rules and regulations concerning connection of telephone equipment, systems, and protective apparatus to the public switched telephone network. In the National Fire Protection Association (NFPA) SECTION 28 31 02.00 20 Page 5Provided by IHSNot for ResaleNo

29、reproduction or networking permitted without license from IHS-,-,-publications referred to herein, the advisory provisions shall be considered mandatory, as though the word “shall“ had been substituted for “should“ wherever it appears; reference to the “authority having jurisdiction“ shall be interp

30、reted to mean the _ Division Engineering Field Activity _, Naval Facilities Engineering Command, Fire Protection Engineer1.4 SYSTEM DESCRIPTION*NOTE: Include all types of initiation devices/panels to which system shall be connected. A/E shall investigate existing systems in each building. In some ca

31、ses it may be necessary to replace old, unapproved “drill panels“ and shunt systems with new local energy panel/systems (refer to Section 28 31 74.00 20, INTERIOR FIRE DETECTION AND ALARM SYSTEM.*1.4.1 SYSTEM DESIGNSystem shall be a complete base-wide public fire reporting system, complying with NFP

32、A 72, except as modified herein. The exterior fire alarm reporting and receiving system shall comply with NFPA 72 2, 3, 4, 5-8-line Hunt Group. The system shall consist of digital alarm communicator transmitters (DACT) at each protected premise and digital alarm communicator receivers (DACR) at the

33、fire alarm receiving station located at _. The system shall be supervised such that any telephone line connected to a DACT which fails due to loss of line voltage shall be annunciated at the receiving station. The system shall be designed to operate from direct current supplied from a rectifier and

34、from storage batteries. The system shall be designed to record alarm and trouble information from each DACT as well as supervisory alarms received at the DACR. Provide spare DACRs in accordance with NFPA 72. Connect system to existing and new local building fire alarm systems, and sprinkler water fl

35、ow detectors and existing manual pull stations and existing extinguishing system control panels as shown to form auxiliary alarm systems in accordance with NFPA 72. New local energy fire alarm systems are specified in Section 28 31 74.00 20 INTERIOR FIRE DETECTION AND ALARM SYSTEM. System shall incl

36、ude street boxes and master boxes as specified herein and where shown, to allow manual initiation of fire alarm transmission by the general public.1.4.2 Power CalculationsSubmit design calculations to substantiate battery capacity exceeds supervisory and alarm power requirements for digital alarm co

37、mmunicator transmitters, receiving consoles and interface panels (if provided).1.5 SUBMITTALS*NOTE: Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list to reflect only the submittals required for the project. Submittals should be kept to

38、 the minimum required for adequate quality control.SECTION 28 31 02.00 20 Page 6Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A “G” following a submittal item indicates that the submittal requires Government approval. Some submittals are already ma

39、rked with a “G”. Only delete an existing “G” if the submittal item is not complex and can be reviewed through the Contractors Quality Control system. Only add a “G” if the submittal is sufficiently important or complex in context of the project.For submittals requiring Government approval on Army pr

40、ojects, a code of up to three characters within the submittal tags may be used following the “G“ designation to indicate the approving authority. Codes for Army projects using the Resident Management System (RMS) are: “AE“ for Architect-Engineer; “DO“ for District Office (Engineering Division or oth

41、er organization in the District Office); “AO“ for Area Office; “RO“ for Resident Office; and “PO“ for Project Office. Codes following the “G“ typically are not used for Navy, Air Force, and NASA projects.Choose the first bracketed item for Navy, Air Force and NASA projects, or choose the second brac

42、keted item for Army projects.*Government approval is required for submittals with a “G“ designation; submittals not having a “G“ designation are for Contractor Quality Control approval.for information only. When used, a designation following the “G“ designation identifies the office that will review

43、 the submittal for the Government. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:The Fire Protection Engineer, Naval Facilities Engineering Command, _ will review and approve all submittals in this section requiring Government approval.*NOTE: For projects

44、administered by PACNAVFACENGCOM, use the submittal paragraph below in lieu of the above paragraph. Delete the “G“ in the asterisk tokens after each submittal item, except under “SD-08, Statements.“*The Pacific Division, Naval Facilities Engineering Command delegates the authority for review and approval of all submi

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > 其他

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1