SAE AIR 1209-1974 Construction and Calibration of Parallel Plate Transmission Line for Electromagnetic Interference Susceptibility Testing《用于电磁干扰敏感性测试的平行板传输线的建造和校准》.pdf

上传人:diecharacter305 文档编号:1019985 上传时间:2019-03-21 格式:PDF 页数:15 大小:362.02KB
下载 相关 举报
SAE AIR 1209-1974 Construction and Calibration of Parallel Plate Transmission Line for Electromagnetic Interference Susceptibility Testing《用于电磁干扰敏感性测试的平行板传输线的建造和校准》.pdf_第1页
第1页 / 共15页
SAE AIR 1209-1974 Construction and Calibration of Parallel Plate Transmission Line for Electromagnetic Interference Susceptibility Testing《用于电磁干扰敏感性测试的平行板传输线的建造和校准》.pdf_第2页
第2页 / 共15页
SAE AIR 1209-1974 Construction and Calibration of Parallel Plate Transmission Line for Electromagnetic Interference Susceptibility Testing《用于电磁干扰敏感性测试的平行板传输线的建造和校准》.pdf_第3页
第3页 / 共15页
SAE AIR 1209-1974 Construction and Calibration of Parallel Plate Transmission Line for Electromagnetic Interference Susceptibility Testing《用于电磁干扰敏感性测试的平行板传输线的建造和校准》.pdf_第4页
第4页 / 共15页
SAE AIR 1209-1974 Construction and Calibration of Parallel Plate Transmission Line for Electromagnetic Interference Susceptibility Testing《用于电磁干扰敏感性测试的平行板传输线的建造和校准》.pdf_第5页
第5页 / 共15页
点击查看更多>>
资源描述

1、SAE Technical Standards Board Rules provide that: “This report is published by SAE to advance the state of technical and engineering sciences. The use of this report is entirelyvoluntary, and its applicability and suitability for any particular use, including any patent infringement arising therefro

2、m, is the sole responsibility of the user.”SAE reviews each technical report at least every five years at which time it may be reaffirmed, revised, or cancelled. SAE invites your written comments and suggestions.Copyright 2004 SAE InternationalAll rights reserved. No part of this publication may be

3、reproduced, stored in a retrieval system or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without the prior written permission of SAE.TO PLACE A DOCUMENT ORDER: Tel: 877-606-7323 (inside USA and Canada)Tel: 724-776-4970 (outside USA)Fax: 724

4、-776-0790Email: custsvcsae.orgSAE WEB ADDRESS: http:/www.sae.orgAEROSPACE INFORMATION REPORTAIR1209Issued 1974-03Reaffirmed 2004-08Construction and Calibration of Parallel Plate Transmission Linefor Electromagnetic Interference Susceptibility TestingFOREWORDChanges in this reaffirm are format/editor

5、ial only.1. SCOPE:This Aerospace Information Report (AIR) is intended to provide information relating to the construction, calibration, and usage of parallel plate transmission lines in electromagnetic compatibility susceptibility testing.2. REFERENCE DOCUMENTS:2.1 MIL-STD-462, Electromagnetic Inter

6、ference Characteristics, Measurement of2.2 AFSC-DESIGN HANDBOOK DH 1-4, “ELECTROMAGNETIC COMPATIBILITY”, Design Note 6B-1.2.3 A Parallel-Strip Line for Testing RF Susceptibility, B. E. Roseberry and R. B. Schulz, Presented at the 6th National Symposium on EMC, Los Angeles, California, June 1964.2.4

7、Parallel Strip-Line Calibration, B. E. Roseberry, Motorola, Inc., Scottsdale, Arizona, December 12, 1968.SAE AIR1209 - 2 -3. GENERAL CHARACTERISTICS:The Parallel Plate Transmission Line (PPL) is a versatile item of test equipment. It may be used to generate low impedance magnetic fields, high impeda

8、nce electric fields, and plane waves for environmental or electromagnetic compatibility testing of electronic equipment. The PPL will produce these fields efficiently, since the electric field component is essentially contained between the parallel plates. The line response is uniform from DC to an

9、upper frequency limit of 25 MHz or more, depending upon its physical size and the terminating impedance. The direction and magnitude of the E and H field vectors, and the direction of propagation of the plane wave are known. Its response as a receiving transducer or antenna is uniform and essentiall

10、y limited to energy emanating from within the confines of the line, with respect to the E field.4. CONFIGURATIONS AND USAGE:The PPL may be used in three ways:a. Unterminated - In this configuration the PPL is a parallel plate capacitor antenna rather than a transmission line. It produces an E field

11、of high impedance. Only a vestige of H field is present, caused by the displacement current flowing in the capacitor.b. Terminated in its characteristic impedance - This configuration produces a unidirectional plane wave, with the E field vector normal to the conductive plates and the H field normal

12、 to the E field and to the direction of propagation.c. Terminated in zero impedance - The short circuited line is a single turn loop or magnetic dipole of extremely low impedance. The only E field exhibited by this configuration is that caused by the IR drop in the conductors. Thus the field produce

13、d has an impedance approaching zero ohms. This usage of the line would require the construction of a termination with the conductive elements replaced by a metallic conductor.The PPL is also eminently suited for quantitative measurements of energy radiated from equipment enclosures, since its respon

14、se is uniform from zero frequency to the upper frequency limit determined by its physical size. It may be used without a shielded enclosure in many instances, since it is relatively insensitive to E field or plane wave energy originating outside of the line, up to its operational frequency limit. It

15、s use provides significant advantages for use in a shielded enclosure as well, since its coupling factor to space is much lower than that of conventional antennas. The anomalies caused by reflection of energy from the interior surfaces of the enclosure are essentially eliminated.SAE AIR1209 - 3 -4.1

16、 AFSC DH 1-4 Line:Figures 1, 2, and 3 show construction of a parallel plate line incorporating the following features and improvements:a. The longitudinal slots in the parallel plates prevent transverse current and help to maintain the TEM mode of propagation.b. The termination reduces coupling betw

17、een the end of the line and the shielded room wall. Each layer of conductive plastic (377 ohms/square) reduces the energy passing through by 6 dB/layer so that coupling is reduced by 36 dB (18 dB outgoing and 18 dB reflected back in) for the three layers.c. The input is designed as a wave launcher r

18、ather than a matching section. The shape of the launcher has been determined empirically to minimize variations of wave front homogeneity at the sending end. The input is suitable for low-impedance (4 ohms) spike generators or conventional 50-ohm signal sources.4.1.1 Grounding: Investigations have i

19、ndicated that for this configuration grounding the bottom plate to the ground plane on one side along its entire length creates a non-uniform field, concentrated along the grounded side. It is recommended that the bottom plate be grounded only at the termination, over the entire width of the bottom

20、plate.4.1.2 RF Power: The parallel plate line termination will accept 250 watts continuously. Figure 4 indicates the typical RF power required to generate a 10 V/meter field. Each line should be calibrated individually.4.1.3 Line Characteristic Impedance: The characteristic impedance of a line havin

21、g a height-to-width ratio of unity has been determined by bridge measurements of the open- and short-circuited line to be approximately 118 ohms. A distributed load of 40 ohms, consisting of three sheets of conductive plastic having a resistance of 120 ohms per square connected in parallel a voltage

22、 (V) to power (W) ratio that was independent of frequency up to the upper frequency limit of the line. The Figure 4 curve was produced from data taken on a line with one metre strip width and one metre separation between the strips. These data correlate well with other data taken on other lines of u

23、nity height-to-width ratio with conductor widths and separations of 10, 30, 60 and 76 centimetres. The upper frequency limit of these lines varies as the inverse of the width and spacing.4.1.4 Placement in Shielded Enclosure: The line should not be located adjacent to a shielded room wall or other c

24、onductive surface. Separation between the sides of the line and the shield room wall should be at least 1.5 times the strip separation to avoid distortion of the field within the line. The line should be grounded to the ground plane or wall at the load end with a ground strap of the same width as th

25、e line.SAE AIR1209 - 4 -4.1.5 Line Usage:a. Frequency Range0 Hz to 20 MHz with +29 dBm.20 MHz to 50 MHz with +38 dBm.b. Spacing from enclosure wall1.5 times strip separation.c. H/W RatioUnityd. Maximum Test Sample SizeMaximum test sample size shall not exceed 0.75 times strip separation4.2 MIL-STD-4

26、62 Type Line:This line differs from the previous line in that it utilizes H/W ratios other than unity, discrete load resistors, and different grounding requirements. Figure 5 shows a typical line based onMIL-STD-462 construction but with slightly larger dimensions.4.2.1 Line Grounding: The shield ro

27、om, copper top, work bench may be used as the line ground plane, provided that it is wide enough and is bonded to the shield room wall in the usual manner. The top plate of the line should be kept at least one foot from the shield room wall to minimize field distortion in the line. If the entire lin

28、e is constructed as a separate assembly, grounding has not proven to be critical, i.e., load end versus source end, provided that the line is at least one foot from the shield room wall.4.2.2 Characteristic Impedance: It is recommended that the characteristic impedance of the line be determined init

29、ially by bridge measurement. The following are typical for three commonly used height-to-width ratios:12 inch/24 inch Zo= 80 ohms18 inch/24 inch Zo= 83 ohms24 inch/36 inch Zo= 105 ohms4.2.3 Line Usage: The normally used frequency range is 14 KHz to 30 MHz. Test sample size should be limited to 3/4 t

30、he plate spacing. In actual use, the upper conductor could be made to pivot from the wall or hang from the ceiling, thus facilitating removal of the line when not in use.SAE AIR1209 - 5 -5. CALIBRATION:The electric field intensity in the line is equal to the voltage across the load divided by the li

31、ne spacing in metres. For optimum accuracy, the impedance match of the load should be confirmed by monitoring the power required to maintain a constant load voltage versus frequency. With the line terminated in its characteristic impedance only the TEM mode appears in the line. Therefore, the electr

32、ic field and the magnetic field are related by E/H = 377 ohms. Note that the field impedance in the line and the line characteristic impedance are not the same. However, varying the line load will change the E/H ratio in the line. Use of a calibrated loop probe to determine the magnetic field is nec

33、essary if an accurate value of the line field impedance is desired.A small, shielded loop probe (Figure 6) is used as the field sensing device. Using the standard calibration arrangement setup, shown in Figure 7, the probe was calibrated in terms of output voltage, as a function of magnetic field in

34、tensity at 2, 10, 20, and 30 MHz.The length of coaxial cable between the probe and meter is kept as short as possible because long cables result in calibration curves that are nonlinear and at frequencies above 10 MHz meter readings may vary with the physical location of longer cables. The calibrati

35、on field is established by a 0.25 metre diameter loop. The capacitance of the calibration loop feed line is minimized by use of one foot long open wire line with the conductors 0.5 inch apart.The loop configuration exhibits a linearly decreasing loop current as frequency increases, indicating that t

36、he loop and feed line are not resonating. The calibration loop current is determined by measuring the voltage drop across a 10 ohm deposited carbon precision resistor which is placed in series with, and as close to, the loop as possible. The field at the center of the loop is given by the expression

37、:where,I = loop current in rms amperesD = loop diameter in metresMoving the shielded probe from the center of the loop by an amount equal to the radius of the probe produces a negligible change in induced voltage. This indicates that the field at the center of the calibration loop is essentially con

38、stant over the probe area.During calibration, the probe output voltage is measured by the substitution method through use of an accurately metered signal generator. Although, because of losses, the probe output voltage does not increase linearly with frequency, the calibration curves are straight li

39、nes for each frequency. The nonlinearity is of no consequence in obtaining the final calibration curve for the transmission line. Typical probe calibration curves are shown in Figure 8.HID- ampsmetres-=SAE AIR1209 - 6 -5. (Continued):The required value of load resistance is determined by measuring t

40、he open-circuit capacitance and short-circuit inductance of the line and applying the expressionwhere,1 = short-circuit inductancec = open-circuit capacitanceCalibration measurements are made after the line is properly loaded. The resulting calibration curve allows the user to establish a known fiel

41、d by measuring only the current in the line. To calibrate the line, the probe is centrally located between the conductors so that the plane of the probe is perpendicular to the lower strip.The probe cable is brought out to the field intensity meter in a position as far from the line as the 5 ft cabl

42、e will allow. To determine the current in the line a high impedance RF voltmeter is connected across one of the load resistors. Stray pickup can be eliminated by taping the meter leads to the ground plane and positioning the meter on the ground plane as far from the load as possible.Probe output vol

43、tage is recorded for each value of line current. Starting with a line current of 2 ma, data is taken until the output voltage corresponds to a field of approximately 0.03 a/m as shown on the probe calibration curve for the frequency in use. Probe output voltage measurements are made by the substitut

44、ion method as for probe calibration.The curves of probe output voltage versus line current, and probe output voltage versus field intensity are combined, for each frequency, to obtain line calibration curves of field intensity as a function of line current. The resulting calibration curves should de

45、viate from one another by no more than 8 percent. Although the curves should coincide this result would be difficult to obtain. A typical calibration curve is shown in Figure 9.The simplicity of the line allows it to be dismantled and rebuilt without invalidating the calibration curve. Typically, da

46、ta obtained after a period of 6 months, with different instrumentation and in a different shield room, is within 5% of original measurements. The values of field intensities on the curve are those which exist at the center of the line.PREPARED BY SAE SUBCOMMITTEE AE-4B.4, ELECTROMAGNETIC COMPATIBILI

47、TYZo1c-=SAE AIR1209 - 7 -FIGURE 1 - Parallel Plate LineSAE AIR1209 - 8 -FIGURE 2 - Wave Launcher DetailSAE AIR1209 - 9 -FIGURE 3 - Termination DetailSAE AIR1209 - 10 -FIGURE 4 - RF Power Required to Generate a 10 V/mField in Parallel Plate Line ModelSAE AIR1209 - 11 -FIGURE 5 - MIL-STD-462 Type LineSAE AIR1209 - 12 -FIGURE 6 - Loop ProbeSAE AIR1209 - 13 -FIGURE 7 - Probe Calibration SetupSAE AIR1209 - 14 -FIGURE 8 - Probe Calibration Curves (Typical)SAE AIR1209 - 15 -FIGURE 9 - Line Calibration Curve (Typical)

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > 其他

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1