资源描述

1、_SAE Technical Standards Board Rules provide that: “This report is published by SAE to advance the state of technical and engineering sciences. The use of this report is entirely voluntary, and its applicability and suitability for any particular use, including any patent infringement arising theref

2、rom, is the sole responsibility of the user.” SAE reviews each technical report at least every five years at which time it may be reaffirmed, revised, or cancelled. SAE invites your written comments and suggestions. Copyright 2008 SAE International All rights reserved. No part of this publication ma

3、y be reproduced, stored in a retrieval system or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without the prior written permission of SAE. TO PLACE A DOCUMENT ORDER: Tel: 877-606-7323 (inside USA and Canada) Tel: 724-776-4970 (outside USA)

4、Fax: 724-776-0790 Email: CustomerServicesae.org SAE WEB ADDRESS: http:/www.sae.orgAIR4782A AEROSPACEINFORMATIONREPORTIssued 1994-02 Revised 2008-08 Superseding AIR4782 Hydrant Valve and Coupler Historical Background RATIONALEThis revision adds websites to some of the reference documents. 1. SCOPE Th

5、is SAE Aerospace Information Report (AIR) presents historical information and background data related to hydrant valves and couplers used in worldwide ground refueling of commercial aircraft (hereafter generically referred to as hydrant devices). Military hydrant devices are not included since their

6、 mission requirements demand approaches that may differ.1.1 Purpose The purpose of this document is to provide definitions, background and educational information for use by design engineers, users of the systems and other interested parties who are involved with hydrant devices and associated equip

7、ment.1.2 Field of Application Soon after World War II, the military techniques for underwing refueling of turbine-engined aircraft were adopted for use on commercial aircraft. Advantages include significantly improved safety, convenience and rapidity of refueling. Refueling systems for commercial ai

8、rcraft evolved to comprise five basic elements, as follows: a. Hydrant systems (or supply systems) b. Hydrant couplers (hydrant system to servicer systems) c. Servicer system (hydrant to aircraft) d. Aircraft couplings (service systems to aircraft fuel systems) e. Aircraft fuel systems Element (d),

9、the aircraft couplings, are now true worldwide standards, having been adopted for military and commercial aircraft of all countries, and controlled by international standard documents. SAE AIR4782A - 2 -This document applies to the hydrant valve portions element (a), the entire element (b) and appli

10、cable portions of element (c). Some references to other elements are included, where pertinent. 2. APPLICABLE DOCUMENTS The following publications form a part of this document to the extent specified herein. The latest issue of SAE publications shall apply. The applicable issue of other publications

11、 shall be the issue in effect on the date of the purchase order. In the event of conflict between the text of this document and references cited herein, the text of this document takes precedence. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exempti

12、on has been obtained. 2.1 API Publications Available from American Petroleum Institute, 1220 L Street, NW, Washington, DC 20005-4070, Tel: 202-682-8000, http:/api-ec.api.org.API Bulletin 1584API Standard for Four Inch Hydrant Systems Components and Arrangements 2.2 IP Publications Available from Lib

13、rary and Information Department, The Institute of Petroleum, 61 New Cavendish Street, London W1M 8AR, England, FAX 71 255 1472. No Number Aviation Hydrant Pit Systems - Recommended Arrangements for - Part I New Facilities, Part II Replacement of Obsolete Valves in Small Pit Boxes - August, 1990 2.3

14、Military Publications Available from the Document Automation and Production Service (DAPS), Building 4/D, 700 Robbins Avenue, Philadelphia, PA 19111-5094, Tel: 215-697-6257, http:/assist.daps.dla.mil/quicksearch/.MS24484 Adapter, Pressure Fuel Servicing, Nominal 2.5-inch Diameter MS29514 Flange, Ada

15、pter Locking, Pressure Fuel Servicing 2.4 ANSI Publications Available from ANSI, 25 West 43rd Street, New York, NY 10036-8002, Tel: 212-642-4900, www.ansi.org.ANSI B16.5 Pipe Flanges & Flanged Fittings 2.5 ISO Publications Available from American National Standards Institute, 25 West 43rd Street, Ne

16、w York, NY 10036-8002, Tel: 212-642-4900, www.ansi.org or from International Organization for Standardization, 1, rue de Varembe, Case postale 56, CH-1211 Geneva 20, Switzerland, Tel: +41-22-749-01-11, www.iso.org.ISO/DIS 45:1990 Aircraft Pressure Refueling Connections 2.6 Definitions AIRCRAFT REFUE

17、LING ADAPTER: A part of the aircraft fuel system, it is the mating portion of the quick disconnect by which the Hydrant Servicer (Nozzle) is connected to the aircraft. This connection is dimensionally in accordance with MS24484, MS29514, ISO 45, and NATO STANAG 3105. The latter two documents are int

18、ernational standards to assure interchangeability.SAE AIR4782A - 3 -DEADMAN CONTROL: The manual capability of open-close control of flow through the Hydrant System and Hydrant Servicer by an operator. This feature requires the operator to hold a switch or valve in a predetermined position to keep fl

19、ow through the system. The valve, being held by the operator, normally controls the application of an air reference pressure to the Deadman Control Valve. The switch may control a solenoid valve that releases the application of air pressure to the Deadman Control Valve. Release of the switch or valv

20、e will automatically stop flow. EXCESS-FLOW CONTROL: Some Hydrant Valves or Hydrant Couplers include a feature that will automatically stop flow through the system if the flow rate exceeds a predetermined value. Some such units have the capability of having two such settings, high and low settings,

21、to accommodate aircraft of different capacity. This is intended to prevent a major spill of fuel in case of an intake hose rupture and is sometimes used to supplement other emergency shut down devices such as deadman and lanyard operated controls. HOSE END CONTROL VALVE OR REGULATOR: A direct acting

22、 pressure control device that is mounted as an integral part of the Underwing Nozzle. HYDRANT COUPLER: The mechanical quick connection between the Hydrant Servicer and the Hydrant Valve. The Hydrant Coupler may include various control features or may be a simple quick coupling. HYDRANT PIT: A covere

23、d small chamber containing the hydrant system pipe terminus, hydrant valve, and associated equipment. The pit is strategically located to provide access to the aircraft underwing Refueling Adapter. HYDRANT SERVICER: Also called Hydrant Cart or Hydrant Dispenser. A vehicle, self-propelled or towable,

24、 that contains the necessary equipment to allow for connection to the Hydrant Valve and the aircraft refueling adapter. The Hydrant Servicer may include, but not be limited to, intake hose, outlet hoses, booster pumps, meters, filter separators or monitors, pressure control systems, and other equipm

25、ent necessary for effecting an accurate, safe and rapid refueling of the aircraft. HYDRANT SYSTEM (or AIRPORT FUEL SYSTEM): A Hydrant System consists of three basic elements: a. Tank farm or storage facility. b. Piping and controls required to connect the Tank Farm with the apron mounted hydrant val

26、ves. c. Hydrant pits and valves. The hydrant system provides a consistent source of fuel from a remotely located storage facility or tank farm to the refueling apron or parking positions of the various aircraft to be refueled. HYDRANT VALVE: The terminus of the hydrant system piping system that will

27、 provide as a minimum quick coupling capability with a hydrant coupler and may provide controls (pressure, on-off, excess-flow, etc.). NOZZLE or COUPLING: The quick connection utilized to attach the Hydrant Servicer outlet to the aircraft Refueling Adapter. There may be one or more normally no more

28、than four Nozzles per each Hydrant Servicer. The Nozzle may or may not have an integrally attached Hose End Control Valve. OVERSHOOT CONTROL: The capability of controlling the volume of fuel passing through the refueling system following the initiation of a Deadman Closure is Overshoot Control. PRES

29、SURE CONTROL: Aircraft refueling systems are designed to accept a safe pressure at the connection to the aircraft (Nozzle or Coupling). This pressure is automatically achieved by Pressure Control utilizing a number of different approaches. It may be accomplished by or combination of the Hydrant Pit

30、Valve, Hydrant Coupler, Line Mounted Pressure Control Valve, or by a Hose End Control Valve (mounted as a part of the Nozzle). SAE AIR4782A - 4 -PRESSURE CONTROL VALVE: Usually a line mounted valve that provides remote regulation of pressure and, as required, surge control, deadman control, and/or o

31、vershoot control. PRODUCT SELECTION: A design feature of the hydrant valve and coupler that keys the two units to mate only if both halves (hydrant valve and coupler) are the same. The API Bulletin 1584 specifies the type and control of dimensions to assure compatibility of all manufacturers coupler

32、s for the 4 in units. There are two different product selection methods available on the 2-1/2 in units, one used in the United States (and influenced areas) and one used in Europe (and influenced areas). They are not compatible with each other. PUMPS: Pumps are utilized in Hydrant Systems, normally

33、 at the tank farm pumping station to provide the pressure within the Hydrant System to move the fuel from the tank farm to the aircraft parking position. Pumps may also be used on Hydrant Servicers where the pressure inherently is too low to accomplish the refueling task in the appropriate manner. R

34、EFUELING TRUCK, REFUELER or FUELLER: A vehicle that is used to refuel an aircraft, normally self-propelled, that contains the same basic equipment as mentioned for HYDRANT SERVICER and the fuel supply is contained within an on-board tank. SURGE CONTROL: Airframe manufacturers limit the amount of tra

35、nsient peak fuel pressure measured at the Aircraft Refueling Adapter. Ground equipment also must anticipate the aircraft valving closures and also limit the amount of peak pressure buildup at the Aircraft Refueling Adapter. The capability to limit the magnitude of the peak pressure is Surge Control.

36、UPLIFT: The amount of fuel input into an aircraft at a single refueling operation. 3. HYDRANT VALVES 3.1 Background Some hydrant systems were developed, in the mid-1950s, for use in providing aviation gasoline or turbine fuels to propeller type aircraft. Some of the gasoline systems are still in use

37、 today, having been subsequently converted to turbine fuel application. However, the major development of hydrant systems followed the introduction of larger, jet-engined aircraft, and allowed the delivery of larger volumes of fuel to be accomplished relatively quickly. The turbine aircraft required

38、 uplift capacities that were greater than the capacity of a single refueling truck. Another compelling reason for the development of hydrant systems was the desire to limit the size of the vehicles parked around an aircraft during servicing. Safety was also a major consideration. A hydrant system is

39、 generally considered a safer method of refueling than is a refueling truck. Life cycle costs for hydrant systems may be lower than for refuelers depending upon the number of vehicles and size of the system. Valves utilized in hydrant systems throughout the world can be categorized by types and size

40、s. 3.1.1 Hydrant Valve Types There are three general types of hydrant valves that have been and/or are in service at the commercial airports of the world:a. Hydrant Valves with No Controls: These units, although utilized as hydrant valves, are essentially simple quick coupling adapters used only to

41、connect the hydrant pipe line terminus to the hydrant coupler. All controlling of flow, including deadman, is achieved elsewhere from the pit. In an emergency situation, this type of device, having no closure controls, can only be closed by a proper disconnect. This type, therefore, is considered le

42、ss safe than either of the other two and should not be utilized for any system design. SAE AIR4782A - 5 -b. Hydrant Valves with Minimum Controls (normally on/off shutoff) Located on the Actual Unit within the Pit: These types of valves can be air or lanyard operated or a combination of both. The oth

43、er major controls for the system (pressure and/or excess-flow control) are located external to the hydrant valve, normally within the mating coupler or further downstream in the line. c. Hydrant Valves with All Controls (pressure, deadman and/or excess-flow) Located on the Actual Unit within the Pit

44、: Since all controls are located within the hydrant pit valve, the mating coupler is a simple straight-through type unit with no controls other than the manual open and close handle. 3.1.2 Hydrant Valve Sizes There are three basic sizes (outlet connections) still in operation. The inlet size is norm

45、ally either 4 or 6 in bolt flanges tomate ANSI B16.5 type flanges. a. Bayonet type 2-1/2 in international aircraft adapter type connection. This size of hydrant valve has been furnished with all controls or with air or lanyard type shutoff controls only. This valve size is used where smaller, lighte

46、r servicer inlet components and hose are desired and flow rates are less than 750 U.S. gpm (2839 l/min). b. Reverse bayonet (slots in lieu of lugs) type 3-1/2 in connection (commonly called a 4 in unit). This type of hydrant valve, although still utilized in some parts of the world has been almost u

47、niversally replaced by the 4 in API size below.c. API 4 in connection in accordance with API Bulletin 1584. This is the most prevalent type of unit utilized today. It is available in either of the types noted in 3.1.1. 3.2 Hydrant Valve Functions and Configurations Hydrant valves and/or couplers ser

48、ve to provide various functions within the refueling system. The following discussion is divided into the two prevalent types of hydrant vales in use today. 3.2.1 Hydrant Valves with Integral Controls Hydrant valves with all controls located integrally with the valve usually will include such featur

49、es as pressure and deadman control and may include excess-flow control. This type of valve normally requires connection to a reference air pressure from the hydrant servicer to achieve the various control features. A fuel sense line, originating at the fuel sense point on the hydrant servicer, where remote sensing is utilized, will also be connected to the hydrant valve. The connection of these two lines will normally be accomplished by a