UL 1310 CRD-2014 UL Standard for Safety Class 2 Power Units - Section Paragraph Reference 81 C 89 (New) Subject Flush Device Cover Plate with Integral Power Supply with Class 2 Ou.pdf

上传人:figureissue185 文档编号:1067425 上传时间:2019-04-02 格式:PDF 页数:6 大小:105.25KB
下载 相关 举报
UL 1310 CRD-2014 UL Standard for Safety Class 2 Power Units - Section  Paragraph Reference 81 C 89 (New) Subject Flush Device Cover Plate with Integral Power Supply with Class 2 Ou.pdf_第1页
第1页 / 共6页
UL 1310 CRD-2014 UL Standard for Safety Class 2 Power Units - Section  Paragraph Reference 81 C 89 (New) Subject Flush Device Cover Plate with Integral Power Supply with Class 2 Ou.pdf_第2页
第2页 / 共6页
UL 1310 CRD-2014 UL Standard for Safety Class 2 Power Units - Section  Paragraph Reference 81 C 89 (New) Subject Flush Device Cover Plate with Integral Power Supply with Class 2 Ou.pdf_第3页
第3页 / 共6页
UL 1310 CRD-2014 UL Standard for Safety Class 2 Power Units - Section  Paragraph Reference 81 C 89 (New) Subject Flush Device Cover Plate with Integral Power Supply with Class 2 Ou.pdf_第4页
第4页 / 共6页
UL 1310 CRD-2014 UL Standard for Safety Class 2 Power Units - Section  Paragraph Reference 81 C 89 (New) Subject Flush Device Cover Plate with Integral Power Supply with Class 2 Ou.pdf_第5页
第5页 / 共6页
点击查看更多>>
资源描述

1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a

2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): EPBUStandard Number: UL 1310Standard Title: Standard for Class 2 Power UnitsEdition Date: August 26, 2011Edition Number: 6Section / Paragraph Reference: 81 8

3、9 (New)Subject: Flush Device Cover Plate with Integral Power Supply with Class 2 OutputConnector(s) with or without a Night LightDECISION:(NEW SECTIONS)81 General81.1 Requirements in Sections 81 through 90 apply to a flush device cover plate with integral powersupply with Class 2 output connector(s)

4、 with or without a night light.81.2 These requirements are applicable to flush-type, parallel blade construction of the ANSI/NEMA1-15R or 5-15R configurations only. These requirements do not cover products incorporating a flushdevice cover plate with connection means other than plug blades.81.3 Thes

5、e requirements are applicable only to non-metallic flush device cover plates. They are intendedfor indoor use only.81.4 These devices shall comply with the applicable requirements of this Standard, UL 1310, except asmodified by these requirements.Construction:82 General82.1 In addition to the constr

6、uction, performance and marking requirements contained in this Standard, aflush device cover plate with integral power supply with one or more Class 2 output low-voltageconnectors with our without a night light shall comply with the applicable requirements of the Standard forCover Plates for Flush-M

7、ounted Wiring Devices, UL 514D.82.2 The flush device cover plate profile shall not hinder the complete seating of an attachment plug ofthe type intended for use with the receptacle.82.3 A flush device cover plate with integral power supply with one or more Class 2 output low-voltageconnectors with a

8、 night light shall also comply with the applicable requirements of the Standard for DirectPlug-In Nightlights, UL 1786.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL82.4 The Class 2 low-voltage output connectors of a flush device cover plate

9、 with integral power supplywith one or more Class 2 output low-voltage connectors with or without a night light shall be insulated andextend beyond the plane of the receptacle mounting yoke and be accessible when the cover plate isinstalled as intended.82.5 The Class 2 low-voltage power supply shall

10、 be configured for supply from a single branch circuitreceptacle.82.6 A flush device cover plate with integral power supply with one or more Class 2 output low-voltageconnectors with or without a night light intended for installation requiring the removal of a receptacle coverplate shall comply with

11、 the following:a) The device shall be able to be fully inserted in the outlets; andb) The device shall be able to be fully seated against the wall such that the outlet box openingin the wall is completely covered.83 Polymeric Enclosure83.1 In addition to the insulating material requirements of the S

12、tandard for Cover Plates for Flush-MountedWiring Devices, UL 514D, a polymeric material used to enclose the power unit circuitry shall have a flamerating not less than 5V, in accordance with the Standard for Tests for Flammability of Plastic Materials forParts in Devices and Appliances, UL 94, or co

13、mply with the 127 mm Flame Test specified in the Standardfor Polymeric Material - Use in Electrical Equipment Evaluations, UL 746C.84 Spacings84.1 A flush device cover plate with integral power supply with one or more Class 2 output low-voltageconnectors shall maintain a minimum of a 1/4 inch (6.35

14、mm) separation of branch circuit wiring and Class2 connections after installation. Compliance is checked my measurement and if necessary, assembly testas identified in Section 87.84.2 Class 2 output low-voltage connectors shall be located as to prevent a line blade of an attachmentplug from being im

15、properly inserted into the Class 2 output low-voltage connector (i.e. USB) slot and theline contacts of a receptacle. Compliance is checked by inspection and if necessary, the assembly testdescribed in Section 87.85 Configurations85.1 The device shall comply with the cover plate dimensions as specif

16、ied in the ANSI/NEMA WD6Standard Wiring Devices Dimensional Specifications intended to accommodate the intendedflush-mounted wiring device.85.2 The blade portion of the device shall comply with the ANSI/NEMA 1-15P or 5-15P blade dimensionsspecified in the ANSI/NEMA WD6 Standard Wiring Devices Dimens

17、ional Specifications.PERFORMANCE86 Class 2 Output Power SupplySTANDARD NUMBER: UL 1310 -2-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL86.1 For all testing to this Standard, except for the Assembly Test in Section 87, the device is to beene

18、rgized from a duplex receptacle wired to a source of supply as intended. The duplex receptacle is tobe mounted in a non-metallic outlet box test wall according to Figure 86.1. The outlet box shall bemounted in a vertical wall section as follows:a) With plywood or gypsum wallboard surfaces; andb) Loo

19、sely filled with fiberglass or equivalent thermal insulation.86.2 Under any condition of low voltage output loading, individually or collectively, tests shall beconducted to represent the worst case of:a) No load on the branch circuit receptacle outlet; andb) Full load from the branch circuit recept

20、acle outlet.This is generated text for figtxt.87 ASSEMBLY TEST87.1 A flush device cover plate with integral power supply with one or more Class 2 output low-voltageconnectors with or without a night light shall comply with all of the following:a) Maintain a minimum of a 1/4 inch (6.35 mm) separation

21、 of branch circuit wiring and Class 2connections;Figure 86.1Test setupNOTE Duplex receptacle shall be wired as intended and installed into the outlet box.STANDARD NUMBER: UL 1310 -3-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULb) Not permit

22、 contact to be made between the probes shown in Figure 16.1, Figure 16.2, orFigure 16.4 and any live part through the Class 2 output connectors or through any opening orjoint surrounding the installed device; andc) Not permit contact to be made between the Class 2 output connector and receptacle lin

23、econtacts with an ANSI/NEMA 1-15P attachment plug.87.2 The device shall be checked for compliance with 87.1(a). Following assembly to the test setup FigureSA6.1, the device shall be checked for compliance with 87.1(b). The probes of Figure 16.1, 16.2 and 16.4are to be applied to any opening or joint

24、 surrounding the Class 2 output and through the Class 2 outputconnector slot openings with a force of 8 ounces (2.2 N) in attempt to contact live parts. A suitableindicating device (such as an ohmmeter, battery-and-buzzer combination, or similar device) is to beconnected between the probe and the wi

25、ring terminal of the receptacle to determine whether contact ismade. The probes are to be inserted in the Class 2 output connector slot opening successively in threedirections in any orientation that may permit access to contact live parts. The probes are to be applied forapproximately 5 seconds in

26、each of the three directions. During each application, the probes shall not bemoved or rotated and shall be withdrawn when moving from one direction to the next.87.3 The same representative assembly as described in 87.2 shall be checked for compliance with87.1(c), using an ANSI/NEMA 1-15P polarized

27、attachment plug. One blade shall be inserted into the slotopenings of the Class 2 output connector and the other blade into the slot openings of the receptaclecontacts with a force of 10 pounds (45 N) in an attempt to contact live parts. A suitable indicating device(such as an ohmmeter, battery-and-

28、buzzer combination, or similar device) is to be connected between theClass 2 output connector and the contacts of the receptacle to determine whether contact is made. Theattachment plug is to be manipulated in any direction or orientation that may permit access to contact liveparts. The attachment p

29、lug is applied for approximately 5 seconds in each direction.88 Installation Instructions88.1 Installation instructions shall appear on the device, on the smallest unit container, or on a separateinstruction sheet provided with each device. If the installation instructions are provided on the smalle

30、st unitcontainer or on a separate sheet, they shall be attached to the device in such a manner that they areunable to become detached during normal conditions of handling and storage prior to initial installation orusage. The use of an individual carton, blister pack, or equivalent securing of the d

31、evice to theinstructions, meets the intent of the requirement. However, friction attachment shall not be employed.88.2 A device intended for installation with receptacle cover plate or cover plate screw removed shall beprovided with detailed installation instructions to enable proper installation of

32、 the device with the coverplate removed. The inclusion of a pictorial representation is optional.88.3 A device intended for installation over receptacle cover plates of specific dimensions shall beprovided with installation instructions that describe the maximum overall dimensions of the receptaclec

33、over plate with which the device is intended to be used.88.4 A device having blade spacing not in accordance with Standard for Current Taps and Adapters, UL498A, Figure 9.1, shall be provided with installation instructions that specify, by catalog number orequivalent designation, the receptacles wit

34、h which the device is to be used.88.5 Instructions shall include information to alert the user that a single branch circuit shall supply thedevice. The instructions shall include a pictorial or photograph illustrating proper installation.89 MarkingsSTANDARD NUMBER: UL 1310 -4-UL COPYRIGHTED MATERIAL

35、 NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL89.1 The output Class 2 connectors shall be marked as being “Class 2” and marked with the outputelectrical rating. These markings shall be permanently marked and visible after installation.RATIONALE FOR DECISION:A UL 1

36、310 power supply may be included within a flush device cover plate with or without a night light.To address this construction, this CRD supplements UL 1310 with requirements to address the flush coverdevice, (referencing UL 514D, the Standard for Cover Plates for Flush-Mounted Wiring Devices), and t

37、oaddress the inclusion of a night light, (referencing UL 1786, the Standard for Direct Plug-In Nightlights).Copyright 2014 Underwriters Laboratories Inc.UL, in performing its functions in accordance with its objectives, does not guarantee or warrant thecorrectness of Certification Requirement Decisi

38、ons it may issue or that they will be recognized or adoptedby anyone. Certification Requirement Decisions are the opinion of Underwriters Laboratories Inc. inpractically applying the requirements of the standard. They do not represent formal interpretations of thestandard under American National Sta

39、ndards Institute (ANSI) processes. UL shall not be responsible toanyone for the use of or reliance upon Certification Requirement Decisions by anyone. UL shall not incurany obligation or liability for damages, including consequential damages, arising out of or in connectionwith the use or reliance u

40、pon Certification Requirement Decisions. The electronic version of theCertification Requirement Decision is the current version and previously printed copies may be outdated.This document is published as a service to ULs certification customersSTANDARD NUMBER: UL 1310 -5-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULSTANDARD NUMBER: UL 1310 -6-No Text on This Page

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > 其他

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1