1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared by UL LLC. It is normative for the applicable ULProduct Certification Program(
2、s); however, it is currently not part of the UL Standard(s) referencedbelow.Product Category (CCN): AWSX, DWTT, EBGV, FKAV, FKAV7, ILNR, DXAS, PJOX,PPYT, PXJV, QCRV, QPOZ, TYZX, UBWEStandard Number: UL 514BStandard Title: Standard for Conduit, Tubing, and Cable FittingsEdition Date: July 13, 2012Edi
3、tion Number: 6Section / Paragraph Reference: 1.7, 3.13, 4.5, 7.11.2, 7.11.3, 8.1.7, 8.40 and Table 19Subject: Male Threaded Fittings provided with a LOCKNUT and also intended forsecurement to: Enclosures with threaded entries, or Fittings with internalfemale threads (e.g., HUBs, conduit bodies, coup
4、lings).DECISION:1.7 In addition to covering male threaded FITTINGS for use with cable and conduit, these requirementsalso cover male threaded FITTINGS for use with or without a locknut and intended for securement toenclosures:a) having threaded openings or knockouts, orb) fittings with internal fema
5、le threads (e.g., HUBs, conduit bodies, couplings).4.5 In addition to complying with requirements specific to its intended use with conduit, cable, and tubing,a male threaded fitting shall also comply with performance, environmental and marking requirements forits connection to any of the following
6、additional uses as identified by the manufacturer:a) an enclosure with threaded knockouts,b) an enclosure with removable knockouts, orc) fittings with internal female threads (e.g. HUBS, conduit bodies, couplings).7.11 FITTINGS for threaded HUBS7.11.2 Marking on Fitting- A FITTING provided with a LO
7、CKNUT and intended for securement to boxeswith threaded entries or fittings with internal female threads (e.g., HUBs, conduit bodies, couplings) shallbe marked to identify its type of external threads, such as NPS, NPT, metric, “Straight, “S”, Tapered, T”“Fine”, “Course” or with equivalent wording.7
8、.11.3 Marking on Carton- A FITTING provided with a LOCKNUT and additionally evaluated forsecurement to boxes with threaded entries or fittings with internal female threads (e.g., HUBs, conduitbodies, couplings) shall have a marking on the smallest unit shipping carton For securement to a_+_ only or
9、with equivalent wording.+ Blank to be filled in with the type of internal thread: “NPT”, “NPS” “metric”, “Straight” “,Tapered” or “Straight and Tapered”, orequivalent. Type of thread shall be in accordance with NMX-J-554-ANCE,ANSI/ASME B1.20, or ANSI/ASME B1.16M.UL COPYRIGHTED MATERIAL NOT AUTHORIZE
10、D FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL8.1.7 A FITTING provided with a LOCKNUT and also intended for securement to enclosures with threadedentries or fittings with internal female threads (e.g., HUBs, conduit bodies, couplings) shall comply with:a) the applicable require
11、ments for that fitting when assembled to the intended conduit, cable ortubing, as specified in Clause 8.1.5, andb) the applicable performance and environmental requirements for that fitting when assembledto the threaded entry identified by the manufacturer. See Clauses 4.5, 7.11.2, 7.11.3 and 8.40.1
12、8.40 Tests on Male Threaded Fittings provided with a LOCKNUT and also intended for securement toenclosures with threaded entries or fittings with internal female threads (e.g., HUBs, conduit bodies,couplings)8.40.1 Male threaded fittings shall:a) comply with all applicable requirements for securing
13、conduit, cable, or tubing to an enclosure,box, raceway system, or another FITTING with the locknut as part of the male threaded fitting,and,b) comply with the applicable requirements associated with that fittings performance and usageclaims when assembling the secured conduit cable or tubing to one
14、or more of the followingassemblies based on the intended use as specified by the manufacturer:1) an enclosure with threaded knockouts,2) an enclosure with removable knockouts,3) fittings with internal female threads (e.g. HUBS, conduit bodies, couplings).8.40.2 Six samples of each trade size of a ma
15、le threaded fitting when assembled to any of the productsidentified in 8.40.1 (b1), (b2) or (b3) shall comply with:a) assembly test, Clause 8.11.3, followed by,b) resistance test, Clause 8.11.4, followed by,c) pull test, Clause 8.11.7.The same samples shall be used throughout the test sequence.8.40.
16、3 Three samples of each trade size of a male threaded fitting when assembled to any of the productsidentified in 8.40.1 (b1), (b2) or (b3) shall comply with the Current Test Clause 8.10.8.40.4 A male threaded fitting when assembled to any of the products identified in 8.40.1 (b1), (b2) or (b3)intend
17、ed for use in wet locations and marked for use in wet locations shall comply with the requirementsin Clause 8.7. See Clauses 7.1.5, 7.3.2, and Table 19.8.40.5 A FITTING that has tapered external threads, provided with a locknut and is intended for assemblythreaded inlets as identified in 8.40.1 (b1)
18、, (b2) or (b3) does not need to be subjected to the requirementsof 8.40.2, 8.40.3 and 8.40.3 if:a) it is provided with tapered threads having both thread form and thread length complying withNMX-J-554-ANCE or ANSI/ASME B1.20, and,STANDARD NUMBER: UL 514B -2-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR
19、 FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULb) is identified for use only with fittings with straight internal threads that comply with NMX-J-554-ANCE, CSA C22.2 No. 0.5, or ANSI/ASME B1.20.1 and use National Standard Straight(NPS).Table 19Carton markings(See Clauses 7.1.5, 7.1.7,
20、 8.7.1, 8.11.9.1, and 8.11.9.2.)Item Condition of use or installation Carton markinga1 For use in poured concrete Concrete-tight or Concrete-tight when taped2 For use with unthreaded rigid or intermediatemetal conduitUnthreaded for _bconduit3 For use with threaded rigid or intermediate metalconduitU
21、nthreaded for threaded _bconduit4 For liquid-tight applications Liquid-tight5 For use with steel (FE) EMT For EMT or EMT or Electrical Metallic Tubing6 For use with steel (FE) or aluminum (AL) EMT For (FE or STEEL or AL) EMT or ElectricalMetallic Tubing7 For use in dry locations Dry locations8 For u
22、se in wet locations Wet locations9 For use in wet locations only with a separategasket installed between the box and FITTINGIn wet locations, use _dbetween box andFITTING10 For use with specific type of rigid nonmetallicconduit above or below groundFor _crigid nonmetallic conduit11 For use in COUPLI
23、NG cable and/or conduit todifferent raceway systemsFor _eand rigid metal conduit, IMCe, and EMTor Electrical Metallic TubingComplete Abbreviated12 For use with all types of FMC (flexible metalconduit)For FMC FMC13 For use with steel (FE) or aluminum (AL) FMConlyFor FE FMC FEFMCFor STEEL FMC STEELFMC
24、For AL FMC ALFMCFor ALUM FMC ALUMFMCFor ALUMINUM FMC ALUMINUMFMC14 For use with reduced-wall FMC only For RWFMC RWFMC15 For use with reduced-wall steel (FE) oraluminum (AL) FMC onlyFor FE RWFMC FERWFMCFor STEEL RWFMC STEELRWFMCFor AL RWFMC ALRWFMCFor ALUM RWFMC ALUMRWFMCFor ALUMINUMRWFMCALUMINUMRWFM
25、C16 For use with extra reduced-wall FMC only For XRWFMC XRWFMC17 For use with extra reduced-wall steel (FE) oraluminum (AL) FMC onlyFor STEEL XRWFMC STEELXRWFMCSTANDARD NUMBER: UL 514B -3-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULTable 1
26、9 ContinuedItem Condition of use or installation Carton markinga18 A FITTING provided with a LOCKNUT and alsointended for securement to boxes with threadedentries or fittings with internal female threads(e.g., HUBs, conduit bodies, couplings)For securement to a/n(enclosure withthreaded knockouts) (a
27、nenclosure withremovable knockouts),or (fittings with internalfemale threads (e.g.HUBS, conduit bodies,couplings)fwith threadtype _gorwith equivalent wording.Secure to a/n(enclosure withthreaded knockouts) (anenclosure withremovable knockouts),or (fittings with internalfemale threads (e.g.HUBS, cond
28、uit bodies,couplings)fwith threadtype _gorwith equivalent wording.aThe carton marking specified above shall be prefixed by Intended for instead of For or shall use the word only.bBlank to be filled in with rigid,intermediate, or a combination of the two, followed by the material type FE (or STEEL )
29、orAL (or ALUM or ALUMINUM).cBlank to be filled in with the use of the intended type of conduit, such as PVC underground, as required or applicable.dBlank to be filled in with specific identification of the component to be used, including the part number, to identify the gasket,seal or similar compon
30、ent that must be installed to provide a rain-tight connection.eBlank to be filled in with specific identification of the cable or conduit to be used, such as NM, NMD90, NMSC, AC, MC, orFMC.fBlank to be filled in with specific type of product with threaded inlet fitting has been evaluated to assemble
31、 to.gBlank to be filled in with specific identification of the thread type the fitting has been evaluated with, such as Straight, TaperedMPS, NPT or Metric.In Canada, IMC is not recognized.RATIONALE FOR DECISION:This Certification requirement addresses male threaded fittings provided with locknuts t
32、hat are alsointended for securement to boxes with threaded entries, HUBs or fittings with internal female threads (e.g.conduit bodies, couplings). The requirements employ existing UL 514B requirements combined with newmarking requirements. The performance requirements are intended to be applied to t
33、he assembly of themale threaded fitting to an internally threaded mating product. The new markings ensure thatmanufacturers can properly identify the intended use of the externally threaded fittings and to provideinstallers and AHJs with the necessary information to easily determine the acceptabilit
34、y of assemblies.Copyright 2018 UL LLCUL LLC, in performing its functions in accordance with its objectives, does not guarantee or warrant thecorrectness of Certification Requirement Decisions it may issue or that they will be recognized or adoptedby anyone. Certification Requirement Decisions are th
35、e opinion of UL LLC. in practically applying therequirements of the standard. They do not represent formal interpretations of the standard underAmerican National Standards Institute (ANSI) processes. UL LLC shall not be responsible to anyone forthe use of or reliance upon Certification Requirement D
36、ecisions by anyone. UL LLC shall not incur anyobligation or liability for damages, including consequential damages, arising out of or in connection withthe use or reliance upon Certification Requirement Decisions. The electronic version of the CertificationRequirement Decision is the current version and previously printed copies may be outdated.This document is published as a service to ULs certification customersSTANDARD NUMBER: UL 514B -4-