资源描述

1、11-11 11 53 23 - 1 SECTION 11 53 23 LABORATORY REFRIGERATORS SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. VA Standard equipment schedules and installation details may be shown on

2、architectural (Kitchen Consultant) drawings or on H (HVAC) drawings. PART 1 - GENERAL 1.1 DESCRIPTION A. Refrigerators for Laboratories. Refer to architectural drawings for dimensions and arrangement of units. B. Refer to the / H drawings / architectural drawings / for refrigeration equipment schedu

3、les and installation details. C. Refer to Section 23 23 00, REFRIGERANT PIPING, for piping and insulation. D. Refer to electrical drawings for lighting. 1.2 RELATED WORK A. Quarry tile floor: Section 09 30 13, CERAMIC TILING. B. Section 13 21 29, CONSTANT TEMPERATURE ROOMS. C. Section 23 05 11, COMM

4、ON WORK RESULTS FOR HVAC AND STEAM GENERATION. D. Section 23 23 00, REFRIGERANT PIPING. E. Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC. 1.3 QUALITY ASSURANCE Safety Standard: ASHRAE 15, describes requirements for refrigerant containing parts. 1.4 SUBMITTALS A. Submit in accordance with

5、Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Manufacturers Literature and Data: 1. Condensing units, with mounting rack where required. 2. Unit coolers. 3. Temperature controls and alarms. 4. Diagrams and details of piping, wiring and controls. C. Operating Test Data. D. Maintenanc

6、e and operating manuals in accordance with Section 01 00 00, GENERAL REQUIREMENTS. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 11 53 23 - 2 1.5 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to th

7、e extent referenced. The publications are referenced in the text by the basic designation only. B. Air-Conditioning and Refrigeration Institute (ARI): 420-00 . Unit Coolers for Refrigeration. 520-04 . Performance Rating of Positive Displacement Condensing Units. C. American Society of Heating, Refri

8、gerating and Air Conditioning Engineers (ASHRAE): 15-10 Safety Standards for Refrigeration Systems PART 2 - PRODUCTS 2.1 CONDENSING UNITS A. Comply with ARI Standard 520. Air cooled, water cooled or combination air/water cooled type as shown, motor driven integral compressor, motor starter, condense

9、r, receiver, common base, and safety/operational controls. Receiver capacity shall be not less than 125 percent of system refrigerant charge. For units racked one above the other and for units installed in a closet, provide a factory fabricated steel rack extending approximately 1150 mm (45 inches)

10、above the floor. For larger freezers provide two condensing units and unit coolers with independent refrigeration systems as shown. Do not locate compressors on top of refrigerator or freezers. B. Provide positive oil lubrication and oil level indicating device for each compressor. Provide water reg

11、ulating valve for water cooled unit. C. Compressor Motor: Squirrel cage induction type of ample size for continuous operating at maximum compressor performance indicated. Provide inherent (Klixon) protection, in compressor terminal box, for each phase of motor. D. Pressure Switches: Automatic reset

12、low pressure switch, and automatic or manual reset high pressure cutout. E. Air Cooled Condensing Units: 1. High efficiency type piped and automatically controlled to operate at lower head pressures during low ambient temperature conditions, designed and weather-proofed for outdoor installation, to

13、operate satisfactorily at winter ambient temperatures down to _ degrees C (F), and be provided with crankcase and receiver heaters. SPEC WRITER NOTE: Insert temperature of 6 degrees C (10 degrees) below the 99% column in ASHRAE Handbook weather data. Provided by IHSNot for ResaleNo reproduction or n

14、etworking permitted without license from IHS-,-,-11-11 11 53 23 - 3 2. The condenser fans shall be driven by permanent split capacitor motors. 2.2 UNIT COOLERS A. Comply with ARI Standard 420. Units shall be UL listed, forced-ventilation type integral defrosting, internal or external refrigerant dis

15、tributor, single or multiple fans and motors, drip-pan, deflectors, aluminum or baked-enamel steel housing, hangers, and all accessories. B. Motors: Permanent split capacitor type in accordance with Section 11 05 12, General Motor Requirements for Equipment. Provide motors with thermal overload prot

16、ection. Provide manual starting switch. C. Drain Pans: Galvanized sheet steel. Provide additional drain pans under uncovered refrigerant connections, and interconnect them with main drain pan. For freezer units provide electrically heated drain pan. D. Defrost Provision: 1. Refrigerators: Defrost sh

17、all occur during compressor off cycle with evaporator fan running continuously. 2.3 PIPING, PIPE INSULATION, AND REFRIGERANT AND OIL CHARGES Refer to Section 23 23 00, REFRIGERANT PIPING 2.4 EQUIPMENT IDENTIFICATION REQUIREMENTS A. Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC AND STEAM GE

18、NERATION. B. Identify all refrigeration equipment and alarm devices. SPEC WRITER NOTE: Where both, a freezer and a refrigerator is required, then the preferred configuration is as specified. The designer may modify to have separate entry to refrigerator and freezer, if so required by the user. PART

19、3 - EXECUTION 3.1 INSTALLATION A. Install refrigeration equipment as described in the respective manufacturers instructions. Make panel joints tight and seal all panel penetrations to prevent condensation or frosting. 1. Unit cooler: NSF approval requires that the unit be suspended at 90 mm (3-1/2 i

20、nches) minimum distance below the ceiling to allow cleaning the top of the unit cooler. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-11 11 53 23 - 4 2. To the extent feasible, mount pipe, conduit, and instrumentation on the exterior and pass th

21、ru neatly drilled penetrations to the lights or other devices. B. Piping, Pipe Insulation and Refrigerant: Provide in accordance with Section 23 23 00, REFRIGERANT PIPING. C. Controls Installation: As specified in Section 23 09 23, Direct-Digital Controls Systems for HVAC. 3.2 REFRIGERATOR START-UP,

22、 AND PERFORMANCE TESTS AND INSTRUCTIONS A. Start-up Temperature Reduction: On start-up, reset the room thermostats daily for a maximum temperature drop of 8 degrees, on C scale (15 degrees on F scale per day down to 2 degrees C (36 degrees F), and a maximum of 6 degrees on C scale, (10 degrees on F

23、scale) per day between 2 degrees C (36 degrees F) and final operating temperature. B. Perform test in accordance with Section 01 00 00, GENERAL REQUIREMENTS. Operate each system and record conditions hourly for eight hours. Submit the following information: 1. Station, Building and System Identifica

24、tion, Contractor, Date and Time. 2. Compressor nameplate data: Make, model, horsepower, RPM, refrigerant and charge in pounds. 3. Compressor operation: Approximate percentage running time, pressure gage readings, actual amps (starting and running), condenser water temperature in and out, or condense

25、r entering air temperature. 4. Room temperatures. 5. Defrost and drain functions of unit coolers. Demonstrate alarm functions. C. By arrangement with the Resident Engineer, 24 hours in advance, use the start-up and test period for required operation and maintenance instructions to VA personnel in accordance with Section 01 00 00, GENERAL REQUIREMENTS. - - - E N D - - - Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-

展开阅读全文
相关资源
猜你喜欢
  • GOST R 51325 2 3-2013 Appliance couplers for household and similar general purposes Part 2-3 Appliance couplers with a degree protection higher then IPX0《家用和类似一般用途的器具耦合器 第2-3部分 防护等.pdf GOST R 51325 2 3-2013 Appliance couplers for household and similar general purposes Part 2-3 Appliance couplers with a degree protection higher then IPX0《家用和类似一般用途的器具耦合器 第2-3部分 防护等.pdf
  • GOST R 51325 2 4-2013 Appliance couplers for household and similar general purposes Part 2-4 Couplers dependent on appliance weight for engagement《家用和类似一般用途的器具耦合器 第2-4部分 依靠器具重量啮合的耦.pdf GOST R 51325 2 4-2013 Appliance couplers for household and similar general purposes Part 2-4 Couplers dependent on appliance weight for engagement《家用和类似一般用途的器具耦合器 第2-4部分 依靠器具重量啮合的耦.pdf
  • GOST R 51326 1-1999 Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCB-s) Part 1 General requirements and test .pdf GOST R 51326 1-1999 Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCB-s) Part 1 General requirements and test .pdf
  • GOST R 51329-2013 Electromagnetic compatibility of technical equipment Residual current-operated protective devices (RCDs) for household and similar use Requirements and test metho.pdf GOST R 51329-2013 Electromagnetic compatibility of technical equipment Residual current-operated protective devices (RCDs) for household and similar use Requirements and test metho.pdf
  • GOST R 51334-1999 Safety of machinery Safety distances to prevent danger zones being reached by the upper limbs《机械安全性 防止上肢伸至危险区域的安全距离》.pdf GOST R 51334-1999 Safety of machinery Safety distances to prevent danger zones being reached by the upper limbs《机械安全性 防止上肢伸至危险区域的安全距离》.pdf
  • GOST R 51335-1999 Safety of machinery Minimum gaps to avoid crushing of parts of the human body《机械安全性 避免人体部位压破的最小间隙》.pdf GOST R 51335-1999 Safety of machinery Minimum gaps to avoid crushing of parts of the human body《机械安全性 避免人体部位压破的最小间隙》.pdf
  • GOST R 51336-1999 Safety of machinery Emergency stop equipment Functional aspects Principles for design《机械安全性 急停设备 功能性 设计原理》.pdf GOST R 51336-1999 Safety of machinery Emergency stop equipment Functional aspects Principles for design《机械安全性 急停设备 功能性 设计原理》.pdf
  • GOST R 51337-1999 Safety of machinery Temperatures of touchable surfaces Ergonomics data to establish temperature limit values for hot surfaces《机械安全性 触摸表面的温度 确定热表面温度限值的人体工效学数据》.pdf GOST R 51337-1999 Safety of machinery Temperatures of touchable surfaces Ergonomics data to establish temperature limit values for hot surfaces《机械安全性 触摸表面的温度 确定热表面温度限值的人体工效学数据》.pdf
  • GOST R 51338-1999 Safety of machinery Reduction of risk to health from hazardous substances emitted by machinery Part 1 Principles and specifications for machinery manufacturers《机械.pdf GOST R 51338-1999 Safety of machinery Reduction of risk to health from hazardous substances emitted by machinery Part 1 Principles and specifications for machinery manufacturers《机械.pdf
  • 相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > 其他

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1