资源描述

1、03-04M 08725-1 SECTION 08725 LOW ENERGY POWER ASSIST DOOR OPERATORS SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies equipment,

2、 controls and accessories required to provide low energy power assisted automatic operation of swing doors. The door operator system shall be complete including operator, controls, door arm and operator enclosure (header and cover). 1.2 RELATED WORK A. Masonry; Section 04200, UNIT MASONRY. B. Sealan

3、ts; Section 07920, SEALANTS AND CAULKING C. Steel doors; Section 08110, STEEL DOORS AND FRAMES. D. Wood doors; Section 08201, WOOD DOORS AND FRAMES. E. Aluminum frames entrance work; Section 08410, ALUMINUM ENTRANCES AND STORE FRONTS. F. Door hardware; Section 08710, BUILDERS HARDWARE. G. Glass and

4、glazing of doors and frames; Section 08810, GLASS AND GLAZING. H. Finish Color, Section 09050, INTERIOR/ EXTERIOR FINISHES, MATERIALS AND FINISH SCHEDULE. I. Smoke detectors for control of fire/smoke doors to be wired per Section 13850, FIRE ALARM SYSTEMS. J. Electric general wiring, connections and

5、 equipment requirements; Division 16, ELECTRICAL. 1.3 MANUFACTURERS QUALIFICATIONS A. Power assisted door operators, controls and other equipment shall be products of a manufacturer regularly engaged in manufacturing such equipment for a minimum of three years. B. One manufacturer of automatic door

6、equipment shall be used throughout the building / project /. 1.4 GUARANTEE Power assisted door operators, controls and other related equipment shall be subject to the terms of the “Guaranty“ Article of Section Provided by IHSNot for ResaleNo reproduction or networking permitted without license from

7、IHS-,-,-03-04M 08725-2 01001, GENERAL CONDITIONS, except that the Guaranty period shall be two years in lieu of one year. 1.5 MAINTENANCE MANUALS In accordance with section 01010, GENERAL REQUIREMENTS Article titled “INSTRUCTIONS,“ furnish / two / three / copies of maintenance manuals and instructio

8、ns on automatic door operators. 1.6 SUBMITTALS A. Submit in accordance with Section 01340, SAMPLES AND SHOP DRAWINGS. B. Manufacturers literature and data describing operators, power units, controls, door hardware and safety devices. C. Shop Drawings: Showing location of controls and safety devices

9、in relationship to each automatically operated door. This includes templates, wiring diagrams, fabrication details, anchorage and other information to providers of related work to coordinate the proper installation of the door operators. 1.7 DESIGN CRITERIA A. Power assisted automatic door equipment

10、 shall accommodate normal traffic as well as the weight of the doors. B. Equipment: UL approved and comply with applicable codes. Motors shall be rated minimum one-quarter horsepower and shall be single phase and 115 volts. C. Electrical Wiring; Provide wiring so that only a single power supply is r

11、equired. Equipment and wiring shall be as specified in Division 16, ELECTRICAL. 1.8 APPLICABLE PUBLICATIONS SPEC WRITER NOTE: Make material and product requirements agree with applicable requirements specified in the referenced Applicable Publications. Update and specify only that which applies to t

12、he project. A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. B. American National Standards Institute (ANSI): Provided by IHSNot for ResaleNo reproduction or networking permitted wi

13、thout license from IHS-,-,-03-04M 08725-3 A117.1-98.Guideline for Accessible and Usable Buildings and Facilities-Providing Accessibility and Usability for Physically Handicapped People B. Builders Hardware Manufacturers Association, Inc. (BHMA): 156.19-02.Power Assist and Low Energy Power Operated D

14、oors C. National Fire Protection Association (NFPA): 80-99.Fire Doors and Windows 101-03Life Safety Code PART 2 - PRODUCTS SPEC WRITERS NOTE: Low energy automatic door operators are not recommended for high traffic doors. Coordinate door locations and operations with VAMC staff. Doors shall have har

15、dware for manual operation in event of power failure. Door hardware and door operators shall be by manufacturer of existing products where possible. Discuss with the VAMC staff for emergency power requirement. 2.1 OPERATORS A. Automatic door operators shall be for institutional doors and shall be el

16、ectromechanical and surface mounted above the door to the header or transom bar. The opening force shall be generated by a permanent magnet DC motor driving a combination spiral bevel/spur gear reducer and transmitted to the door through an arm linkage. Opening speed shall be adjustable and feature

17、dual backcheck control allowing adjustment of backcheck speed and position. Closing shall be by spring force generated by a metal compression spring. The spring shall reduce manual opening force to not more than 67 N (15 lbf). The minimum diameter of spring wire shall be .007mm (172 in.). Under the

18、specified design load of the door, the spring shall be capable of performing 2,000,000 cycles before fracture. Adjustable closing speed and fixed latch speed shall control the door in the closing cycle. The doors shall be operated manually at any time without damage to the operator or components. B.

19、 All operators shall have checking mechanism providing cushioning action at last part of door travel, in both opening and closing cycle. Operators shall recycle doors instantaneously to full open position from any point in closing cycle when control switch is reactivated. Provided by IHSNot for Resa

20、leNo reproduction or networking permitted without license from IHS-,-,-03-04M 08725-4 C. Operator shall be swinging type enclosed in housing. Operator shall open door by energizing motor and shall stop by electrically reducing voltage and stalling motor against mechanical stop. Door shall close by m

21、eans of spring energy, and close force shall be controlled by gear system and motor being used as dynamic break without power. System shall operate as manual door control in event of power failure. Opening and closing speeds shall be adjustable. 1. Swing Operator Housing: Housing shall be 140 mm (5-

22、1/2 inches) wide by 150 mm (6 inches) high aluminum extrusions with enclosed end caps for application to 100 mm (4 inch) and larger frame systems. All structural sections shall have a minimum thickness of 3.7 mm (0.146 inch) and be fabricated of 6063-T5 aluminum alloy. 2. Swing Power Operator: Compl

23、etely assembled and sealed unit which shall include helical gear drive transmission, mechanical spring and bearings, all located in cast aluminum case and filled with special lubricant for extreme temperature conditions. A “DC“ shunt-wound permanent magnet motor with sealed ball bearings shall be at

24、tached to transmission system. Complete unit shall be rubber mounted with provisions for easy maintenance and replacement, without removing door from pivots or frame. 3. Connecting hardware for swing overhead concealed type power operator shall have drive arm attached to door with a pin linkage rota

25、ting in a self-lubricating bearing and adjustable slide block, traveling in an interconnected track and top pivot assembly. Top track and pivot assembly shall be fabricated of steel. Door shall not pivot on shaft of operator. 4. Electrical Control: Operator shall have a self contained electrical con

26、trol unit, including necessary transformers, relays, rectifiers, and other electronic components for proper operation and switching of power operator. Relays shall be plug-in type for individual replacement and all connecting harnesses shall have interlocking plugs. Control shall also include time d

27、elay for normal cycle. Swing door control shall include safe-swing circuit with optional switching which automatically limits power and slows door when approached from the doors swing area. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-03-04M 08725

28、-5 5. On pairs of doors, operators shall allow either door to be opened manually without the other door opening. 2.2 MICROPROCESSOR CONTROLS A. The system shall include a multi-function microprocessor control providing adjustable hold open time (1 30 sec.), LED indications for actual position unknow

29、n, system status, open obstruction shutdown, activation signal, safety mat/sensor signal, Stop-and-Hold signal, and mode selector switches providing a means for easy field selection of the following functions: push-to-operate, latch assist and stack pressure. Control shall be capable of receiving ac

30、tivation signals from any device with normally open dry contact output. 1. With push-to-operate function enabled, the control shall provide a means of initiating a self-start activation circuit by slightly pushing the door open at any point in the door swing. 2. Latch Assist shall provide a two seco

31、nd impulse in the close direction to overcome restrictions with locking devices of pressure differentials, allowing the unit to operate in standard time delay mode, and permitting the door to close from the full open position after the hold time is satisfied. All activation modes shall provide fully

32、 adjustable opening speed. B. The door shall be held open by low voltage applied to the continuous duty motor. The control shall include an adjustable safety circuit that monitors door operation and shuts the motor off if an open obstruction is sensed. The control shall include a recycle feature the

33、 reopens the door if an obstruction is sensed at any point during its closing cycle. The control shall include a standard three position toggle switch with functions for ON, OFF, and HOLD OPEN. 2.3 ENCLOSURE Operator shall be completely self-contained within an extruded aluminum housing (alloy 6063-

34、T6) to conceal operator mechanism and mounting brackets and with removable access cover with an overall maximum size of 140 mm (5-1/2 inches) wide by 150 mm (6 inches) deep. Header color shall be integral color anodized/painted to match adjacent storefront/frame finish. Provided by IHSNot for Resale

35、No reproduction or networking permitted without license from IHS-,-,-03-04M 08725-6 2.4 ACTIVATION DEVICES A. Automatic: Opening cycle shall be activated by pressing switches with international symbol of accessibility and “PRESS TO OPERATE DOOR“ engraved on the faceplate. Switches shall be installed

36、 in a standard 2-gang electrical wall box and placed in a location in compliance with ANSI A117.1. Switches may be wall mounted or mounted on a free standing post or guard rail. B. Manual: Push-to-operate; manually pushing the door shall activate the automatic opening cycle. Door shall automatically

37、 close after timer delay expires. C. Opening and closing force, measured 25 mm (1 inch) out from the lock stile of the door, shall not exceed 67 N (15 lbf) to stop the door when operating in either direction or cycle. D. Opening Time Doors shall be field adjusted so that opening time to back check o

38、r 80 degrees, whichever occurs first, shall be 3 seconds or longer as required in Table 1. Backcheck shall not occur before 60 degrees opening. Total opening time to fully open shall be as in Table II. E. Closing Time: Doors shall be field adjusted to close from 90 degrees to 10 degrees in 3 seconds

39、 or longer as required in Table 1. 1. Doors shall be field adjusted to close from 10 degrees to fully close position in not less than 1.5 seconds. 2. Doors shall be field adjusted to remain fully open for not less than 5 seconds. 3. Table 1 provides speed settings for various widths and weights of d

40、oors for obtaining results complying with this paragraph. F. Cycle Tests: 1. Low Energy Power Operated, Low Energy Power Open and Power Assist Operators shall be cycle tested for 300,000 cycles. 2. Use the widest and heaviest door specified as a test specimen. Narrower or lighter doors of the same c

41、onfigurations shall then be considered to meet the cycle test requirements. SPEC WRITERS NOTE: Check requirements of NFPA-101 for clear width requirements in means of egress. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-03-04M 08725-7 Table 1 Mini

42、mum Opening Time to Backcheck or 80 degrees, which ever occurs first and the Minimum Closing Time from 90 degrees to Latch Check or 10 degrees. “D“ Door Leaf Width- mm (inches) “W“ Door Weight in kg (pounds) Matrix Values are in seconds (100) 45.4 (56.7) 125 (68.0) 150 (79.4) 175 (90.7) 200 (762) 30

43、 3.0 3.0 3.0 3.0 3.5 (914) 36 3.0 3.5 3.5 4.0 4.0 (1067) 42 3.5 4.0 4.0 4.5 4.5 (1219) 48 4.0 4.5 4.5 5.0 5.5 Doors of other weights and widths can be calculated using the formula; T = DvW/133 in US units T = DvW/2260 in SI (metric) units Where: T= Time, seconds D= Door width, mm (inches) W= Door we

44、ight, kg (lbs) The values for “T“ time have been rounded up to the nearest half second. These values are based on a kinetic energy of (1.25 lbf-ft). Table II Total Opening Time to Full Open Position Backcheck at 60 degrees Backcheck at 70 degrees Backcheck at 80 degrees Table 1 plus 2 seconds Table

45、1 plus 1.5 seconds Table 1 plus 1 second Note: To determine maximum times from close to full open, the operator shall be adjusted as shown in the chart. Backcheck occurring at a point between positions in Table II shall use the lowest setting. For example, if the backcheck occurs at 75 degrees, the

46、full open shall be the time shown in Table 1 plus 1.5 seconds. 2.5 POWER UNITS Provide separate self-contained electric circuits for automatic operators located on each floor of the building. Interruption or failure Provided by IHSNot for ResaleNo reproduction or networking permitted without license

47、 from IHS-,-,-03-04M 08725-8 of power circuits for operators located on one floor of the building shall not interfere with continuous performance of automatic operated doors located on other floors. Capacity and size of power circuits shall be in accordance with automatic operator manufacturers spec

48、ifications. 2.6 SAFETY DEVICES A. Time delay switches shall be adjustable between 5 to 60 seconds and shall control closing cycle of doors. B. Decals with sign “In“ or “Do Not Enter“ shall be installed on both faces of each door where shown and shall conform to the requirements of ANSI/BHMA A156.19-

49、2002. C. Each swing door shall have installed a motion sensor to detect any person standing in the door swing path and prevent the door from opening. D. Motion sensors shall consist of detection modules, factory prepared to be attached to each side of the lock/strike stile, an armored flex link power cable and bracket assembly, factory prepared for attachment to the pivot stile; a logic board and a position encoder which shall mount