1、4 June 2018 Product STD22967E IEEE Std 1547 -2018 (Revision of IEEE Std 1547-2003) Errata to IEEE Standards Coordinating Committee 21 Sponsored by the IEEE Standards Coordinating Committee 21 on Fuel Cells, Photovoltaics, Dispersed Generation, and Energy Storage Correction Sheet 4 June 2018 Copyrigh
2、t 2018 by the Institute of Electrical and Electronics Engineers. Inc. All rights reserved. Published 2018 Printed in the United States of America. This correction sheet may be freely reproduced and distributed in order to maintain the utility and currency of the underlying Standard. This correction
3、sheet may not be sold, licensed or otherwise distributed for any commercial purposes whatsoever. The content of this correction sheet may not be modified. 4 June 2018 Product STD22967E Replace Table 23 with the following (please note that a subtraction symbol now replaces an erroneous addition symbo
4、l in the operation for high-frequency conditions equation): Operation for low-frequency conditions Operation for high-frequency conditions UFUFp r e a v l60UF60m i n ;60f d bdb fp p pk OFOFp r e m i n60OF60m a x ;60f d bf dbp p pkChange the following in the variable list that follows Table 23: where
5、 p is the active power output,1 in p.u. of the DER nameplate active power rating f is the disturbed system frequency in Hz pavl is the available active power, in p.u. of the DER rating ppre is the pre-disturbance active power output, defined by the active power output at the point of time the freque
6、ncy exceeds the deadband, in p.u. of the DER rating pmin is the minimum active power output due to DER prime mover constraints, in p.u. of the DER active power rating in kW dbOF is a single-sided deadband value for high-frequency and low-frequency, respectively, in Hz dbUF is a single-sided deadband
7、 value for high-frequency and low-frequency, respectively, in Hz kOF is the per-unit frequency change corresponding to 1 per-unit power output change (frequency droop), unitless kUF is the per-unit frequency change corresponding to 1 per-unit power output change (frequency droop), unitless 1 Includes positive and negative active power for Energy Storage DER during low- and high-frequency conditions respectively. Use of alternate control means to meet this requirement is permitted.