1、Designation: D6756 17Standard Test Method forDetermination of the Red Dye Concentration and Estimationof the ASTM Color of Diesel Fuel and Heating Oil Using aPortable Visible Spectrophotometer1This standard is issued under the fixed designation D6756; the number immediately following the designation
2、 indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This test method covers the determin
3、ation of the red dyeconcentration of diesel fuel and heating oil and the estimationof the ASTM color of undyed and red-dyed diesel fuel andheating oil. The test method is appropriate for use with dieselfuel and heating oil of Grades 1 and 2 described in Specifica-tions D396, D975, D2880, and D3699.
4、Red dye concentrationsare determined at levels equivalent to 0.1 mgL to 20 mgL ofSolvent Red 26 in samples withASTM colors ranging from 0.5to 5. The ASTM color of the base fuel of red-dyed sampleswith concentration levels equivalent to 0.1 mgLto 20 mgLofSolvent Red 26 is estimated for theASTM color
5、range from 0.5to 5. TheASTM color of undyed samples is estimated over theASTM color range of 0.5 to 5.1.2 The values stated in SI units are to be regarded asstandard. No other units of measurement are included in thisstandard.1.3 This standard does not purport to address all of thesafety concerns, i
6、f any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1.4 This international standard was developed in accor-dance with internationally recogni
7、zed principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM Standards:2D396 Specification for
8、Fuel OilsD975 Specification for Diesel Fuel OilsD1500 Test Method for ASTM Color of Petroleum Products(ASTM Color Scale)D2880 Specification for Gas Turbine Fuel OilsD3699 Specification for KerosineD4052 Test Method for Density, Relative Density, and APIGravity of Liquids by Digital Density MeterD405
9、7 Practice for Manual Sampling of Petroleum andPetroleum ProductsD4177 Practice for Automatic Sampling of Petroleum andPetroleum ProductsD6045 Test Method for Color of Petroleum Products by theAutomatic Tristimulus MethodD6708 Practice for Statistical Assessment and Improvementof Expected Agreement
10、Between Two Test Methods thatPurport to Measure the Same Property of a MaterialE203 Test Method for Water Using Volumetric Karl FischerTitrationE1655 Practices for Infrared Multivariate QuantitativeAnalysisE2056 Practice for Qualifying Spectrometers and Spectro-photometers for Use in Multivariate An
11、alyses, CalibratedUsing Surrogate Mixtures3. Terminology3.1 Definitions:3.1.1 ASTM color, nthe name of an empirical scale ofexpressing the color of a petroleum liquid darker than Saybolt1This test method is under the jurisdiction of ASTM Committee D02 onPetroleum Products, Liquid Fuels, and Lubrican
12、ts and is the direct responsibility ofSubcommittee D02.05 on Properties of Fuels, Petroleum Coke and Carbon Material.Current edition approved May 1, 2017. Published May 2017. Originallyapproved in 2002. Last previous edition approved in 2015 as D6756 10 (2015).DOI: 10.1520/D6756-17.2For referenced A
13、STM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.*A Summary of Changes section appears at the end of this standardCopyright AST
14、M International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for theDevelopment of International Stan
15、dards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.1color based on a scale of 0.5 (lightest) to 8 Dil (darkest) anddetermined by Test Method D1500.3.1.2 surrogate calibration, na multivariate calibrationthat is developed using a calib
16、ration set which consists ofmixtures with pre-specified and reproducible compositions thatcontain substantially fewer chemical components than thesamples which will ultimately be analyzed. E20563.1.3 surrogate method, na standard test method that isbased on a surrogate calibration. E20563.2 Definiti
17、ons of Terms Specific to This Standard:3.2.1 red dye, nsubstance that, when added to fuel,absorbs green light and imparts a red color to the product. Forthis test method, red dyes are:3.2.1.1 product dyes, nalkyl derivatives of azobenzene-4-azo-2-naphthol (methyl derivatives of Color Index No. 26105
18、)which are more soluble in diesel fuel.3.2.1.2 solvent red 26, nan azobenzene-4-azo-2-naphtholdye of a specific chemical structure that is used to gage theamount of red dye present in a given sample.4. Summary of Test Method4.1 A sample is introduced into the liquid specimen cell.The cell is placed
19、into the light path of the apparatus. A beamof visible light is imaged through the sample onto a detector,and the detector response is determined. Wavelengths of thespectrum, which correlate highly with the red dye concentra-tion and the ASTM color, are selected for analysis usingselective bandpass
20、filters. A multivariate mathematical modelconverts the absorption values from the filters to the red dyeconcentration and the estimated ASTM color.5. Significance and Use5.1 In the United States, high sulfur content (defined by theUnited States Environmental Protection Agency (USEPA)middle distillat
21、e products and diesel fuel used for off-roadpurposes, other than aviation turbine fuel, are required bygovernment agencies to contain red dye. The dye concentrationrequired to be present in high-sulfur and off-road dieselproducts is regulated by the United States EnvironmentalProtection Agency and t
22、he United States Internal RevenueService, respectively.5.2 Some fuels that are readily exchanged in the markethave a color specification. The color of the base fuel is maskedby the presence of the red dye. This test method provides ameans of estimating the base color of Number 1 and Number2 diesel f
23、uel and heating oil in the presence of red dye.5.3 The test method provides a means to indicate confor-mance to contractual and legal requirements.6. Interferences6.1 The presence of colorants other than the hydrocarbonstypical of Number 1 and 2 diesel fuel and heating oils, or thepresence of red dy
24、e other than the specified types, can interferewith the accurate determination of the red dye concentrationreported as Solvent Red 26 equivalent or the base fuel ASTMcolor.7. Apparatus7.1 Filter Spectrophotometer, is equipped with specimenchamber, visible wavelength source, four 10 nm 6 2 nm (fullwi
25、dth at half transmission maximum) bandpass wavelengthdiscriminating filters having center wavelengths at 450 nm 62 nm, 520 nm 6 2 nm, 650 nm 6 2 nm, and 700 nm 6 2 nm.The bandpass filters are used in conjunction with the visiblewavelength source to produce light in the blue, green, red, andfar-red r
26、egions of the electromagnetic spectrum. A detectorconverts the transmitted light to an electronic signal that isprocessed by an A-D converter and a microprocessor.3,47.2 Specimen Cell, constructed of polymethacrylate or clearoptical glass having a path length of approximately 1 cm. Ifmore than one c
27、ell is used for calibration, qualification, andsample measurement, the path length of the cells must bematched to 60.001 cm.8. Sampling8.1 Samples shall be taken in accordance with PracticeD4057 or D4177.8.2 Precautions must be taken to shield the samples fromlight prior to analysis.9. Calibration a
28、nd Standardization of the Apparatus9.1 The instrument is calibrated according to the proceduredescribed in Annex A2.NOTE 1The DT100C3instruments are calibrated at the factory by thevendor.9.2 The instrument is qualified according to the proceduredescribed in Annex A3.NOTE 2The DT100C instruments are
29、 qualified at the factory by thevendor.9.2.1 If the qualification procedure is performed by thevendor, then the user shall perform a quality control checkaccording to the procedure described in Section 10.10. Quality Control Check10.1 To confirm the performance of the instrument, periodi-cally measu
30、re the red dye concentration and theASTM color ofthree control samples using the procedure outlined in Section11. The quality control check standards should be analyzed atleast once a week or before the sample analysis if theinstrument is used less frequently than weekly or if theinstrument is moved
31、 to a different laboratory or field location.NOTE 3Quality control samples are available from DT100C.310.1.1 A standard of known dye concentration and ASTMcolor is made according to the information in A1.4. The set ofquality control samples shall have a low, medium, and high red3DT100C instruments u
32、sed to develop this precision statement are availablefrom PetroSpec, Inc., 530 Main St., Acton, MA 01720.4The sole source of supply of the apparatus known to the committee at this timeis PetroSpec, Inc. If you are aware of alternative suppliers, please provide thisinformation to ASTM International H
33、eadquarters. Your comments will receivecareful consideration at a meeting of the responsible technical committee,1whichyou may attend.D6756 172dye concentration (0 mgL to 14 mgL 6 2 mgL) and a low,medium, and high ASTM color (0 to 5 ASTM color units).10.1.2 The standards are stable for at least one
34、year whenstored in the dark in tightly sealed bottles.10.2 If the red dye concentration determined for one of thequality control samples differs from the known value by morethan 1.0 mgL or if the estimated ASTM color for one of thequality control samples differs from the known value by morethan 0.5
35、units, then the measurement system is out-of-controland cannot be used to determine the red dye concentration orused to estimate the ASTM color until the cause of theout-of-control behavior is corrected.10.3 If correction of out-of-control behavior requires repairto the instrument or recalibration o
36、f the instrument, thequalification of instrument performance described in AnnexA3shall be performed before the system is used to measure reddye concentration or used to estimate ASTM color.11. Procedure11.1 Prepare the filter spectrophotometer for operation inaccordance with the manufacturers instru
37、ctions.11.2 Equilibrate the sample to between 20 C and 25 C.11.3 Without filtering the sample (see 13.6), fill a clean, dryspecimen cell. The external optical surfaces shall be clean. Ifnot, wipe clean and dry with a piece of lint-free paper (forexample, lens paper).11.4 Insert the specimen cell int
38、o the cell chamber of theinstrument.11.5 Record the Solvent Red 26 equivalent concentrationand the estimated ASTM color.12. Report12.1 Report the red dye concentration to the nearest0.1 mgL as Solvent Red 26 equivalent dye.NOTE 4The number of milligrams per litre of Solvent Red 26equivalents measure
39、d by the DT100C instrument is labeled as ppm on thedisplay. The ppm unit reported by the DT100C instrument is equivalent tomg/L.12.2 Report the estimated ASTM color value as: estimatedASTM color using ASTM D6756. Report the result to thenearest 0.1 color value.12.2.1 The reported estimated ASTM colo
40、r value can beconverted to a value that mimics the reporting convention ofTest Method D1500. For estimatedASTM color values that arex.0 or x.5, the estimated value is reported unchanged. Forestimated color values between x.1 and x.4, round up the valueto the nearest x.5 and place an L before the res
41、ult. Forestimated color values between x.6 and x.9, round up the valueto the nearest whole number and place an L before the result.If the estimated color value is greater than 8.0, report theestimated result as 8.13. Precision and Bias513.1 Interlaboratory tests of the procedure were carried outusin
42、g sixteen samples covering the red dye concentration rangeequivalent to 0 mgLto 16 mgLof Solvent Red 26 equivalentsand covering the range of ASTM color from 0.5 to 3.0. Sevenlaboratories participated in the interlaboratory tests. The pre-cision of this procedure as determined by the statisticalexami
43、nation of the interlaboratory test results is as follows:513.1.1 RepeatabilityThe difference between successivetest results obtained with the same apparatus under constantoperating conditions on identical samples would in the longrun, in normal and correct operation of the test method, exceedthe fol
44、lowing value in only one case in twenty:r 5 0.22 mg/Lfor Solvent Red 26 equivalent dye concentrations between0.1 mgL and 20.0 mgL, andr 5 0.085 ASTM color unitsfor samples in the ASTM color range of 0 to 5.13.1.2 ReproducibilityThe difference between two singleand independent results obtained from d
45、ifferent instruments onidentical samples, would in the long run, in normal and correctoperation of the test method, exceed the following value inonly one case in twenty:R 5 0.86 mg/Lfor Solvent Red 26 equivalent dye concentrations between0.1 mgL and 20.0 mgL, andR 5 0.20 ASTM color unitsfor samples
46、in the ASTM color range of 0 to 5.13.2 BiasSince there is no accepted reference materialsuitable for determining the bias for the procedure in this testmethod, bias has not been determined.13.3 Relative Bias (Dye Concentration)Some relativebias,5among certain samples, was observed when the SolventRe
47、d 26 concentration results were compared to the expectedSolvent Red 26 concentrations. The bias between the theoreti-cal and measured Solvent Red 26 concentration is observedwith the test samples that were made using Solvent Red 164,the chemical used to commercially dye diesel fuel. Theobserved bias
48、 does appear to be of a systematic nature and isnot known to be related to the accuracy of this test method,since the Solvent Red 26 equivalency of the Solvent Red 164used in sample preparation has not been determined, onlyestimated.13.4 Relative Bias (ASTM Color)Relative bias,5for onesample, was ob
49、served when the color results were compared tothe Test Method D1500 results; however, this bias is near the5Supporting data have been filed at ASTM International Headquarters and maybe obtained by requesting Research Report RR:D02-1521. ContactASTM CustomerService at serviceastm.org.D6756 173reproducibility of the test methods and is inconclusive. Theoverall relative bias to Test Method D1500 is not significant.NOTE 5The average bias of the estimatedASTM color relative to TestMethod D1500 was 0.17. The largest average biases, 0