1、BSI Standards Publication Fire detection and alarm systems Part 28: Fire protection control equipment BS ISO 7240-28:2014National foreword This British Standard is the UK implementation of ISO 7240-28:2014. There is currently no legal requirement for fire protection equipment to be controlled by the
2、 equipment described in ISO 7240-28 in the UK, although such equipment could contribute to an effective fire safety strategy in certain installations. Also, there is currently no equivalent EN 54 series standard for such equipment, which is why this standard has been adopted in the UK. It should be
3、noted, however, that there are inconsistencies with the requirements of BS EN 54-2:1997+A1:2006 and BS EN 54-16:2008 and ISO 7240-28. Compliance with EN 54 series standards is a requirement of meeting the legal requirements of the Construction Products Regulation for fire detection and fire alarm eq
4、uipment, therefore the requirements of EN 54 series standards should always take precedence over those of ISO 7240-28 in the UK. The UK participation in its preparation was entrusted by Technical Com- mittee FSH/12, Fire detection and alarm systems, to Subcommittee FSH/ 12/3, Control and indicating
5、equipment. A list of organizations represented on this committee can be obtained on request to its secretary. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. The British Standards Institution 2014. Published
6、by BSI Standards Limited 2014 ISBN 978 0 580 82459 3 ICS 13.220.20 Compliance with a British Standard cannot confer immunity from legal obligations. This British Standard was published under the authority of the Standards Policy and Strategy Committee on 30 September 2014. Amendments/corrigenda issu
7、ed since publication Date Text affected BRITISH STANDARD BS ISO 7240-28:2014 ISO 2014 Fire detection and alarm systems Part 28: Fire protection control equipment Systmes de dtection et dalarme dincendie Partie 28: quipement de commande des systmes de lutte contre lincendie INTERNATIONAL STANDARD ISO
8、 7240-28 Second edition 2014-08-15 Reference number ISO 7240-28:2014(E) ISO 7240-28:2014(E)ii ISO 2014 All rights reserved COPYRIGHT PROTECTED DOCUMENT ISO 2014 All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized otherwise in any form or by any
9、means, electronic or mechanical, including photocopying, or posting on the internet or an intranet, without prior written permission. Permission can be requested from either ISO at the address below or ISOs member body in the country of the requester. ISO copyright office Case postale 56 CH-1211 Gen
10、eva 20 Tel. + 41 22 749 01 11 Fax + 41 22 749 09 47 E-mail copyrightiso.org Web www.iso.org Published in Switzerland BS ISO 7240-28:2014 ISO 7240-28:2014(E) ISO 2014 All rights reserved iii Contents Page Foreword iv Introduction vi 1 Scope . 1 2 Normative references 2 3 T erms, abbr e viat ed t erms
11、, and definitions . 2 3.1 Definitions . 2 3.2 Abbreviated terms . 3 4 Requirements 3 4.1 General . 3 4.2 Quiescent condition 3 4.3 Fire protection condition . 4 4.4 Fault warning condition 6 4.5 Disabled condition Optional function 8 4.6 Test condition Optional function 9 4.7 Functional condition re
12、corder Optional function 9 4.8 Accessibility of indications and controls .10 4.9 Visual indications.10 4.10 Audible indications.11 4.11 Additional indications12 4.12 Power supply .12 4.13 Mechanical .12 4.14 Integrity of transmission paths .12 4.15 Software .13 4.16 Data 14 5 Tests 15 5.1 General 15
13、 5.2 Functional test 16 5.3 Environmental tests 17 5.4 Cold (operational) .18 5.5 Damp heat, steady-state (operational)19 5.6 Impact (operational) .20 5.7 Vibration, sinusoidal (operational) 21 5.8 Electromagnetic compatibility (EMC), immunity tests (operational) 22 5.9 Supply voltage variation (ope
14、rational) .23 5.10 Damp heat, steady-state (endurance) 24 5.11 Vibration, sinusoidal (endurance) 24 6 Test report 25 7 Marking .25 Annex A (informative) Explanation of access levels 27 Annex B (informative) Design r equir ements for softw ar e-c ontr olled fir e pr ot ection control equipment .29 BS
15、 ISO 7240-28:2014 ISO 7240-28:2014(E) Foreword ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies (ISO member bodies). The work of preparing International Standards is normally carried out through ISO technical committees. Each member body
16、 interested in a subject for which a technical committee has been established has the right to be represented on that committee. International organizations, governmental and non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the International Electrotec
17、hnical Commission (IEC) on all matters of electrotechnical standardization. The procedures used to develop this document and those intended for its further maintenance are described in the ISO/IEC Directives, Part 1. In particular the different approval criteria needed for the different types of ISO
18、 documents should be noted. This document was drafted in accordance with the editorial rules of the ISO/IEC Directives, Part 2 (see www.iso.org/directives). Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. ISO shall not be held res
19、ponsible for identifying any or all such patent rights. Details of any patent rights identified during the development of the document will be in the Introduction and/or on the ISO list of patent declarations received (see www.iso.org/patents). Any trade name used in this document is information giv
20、en for the convenience of users and does not constitute an endorsement. For an explanation on the meaning of ISO specific terms and expressions related to conformity assessment, as well as information about ISOs adherence to the WTO principles in the Technical Barriers to Trade (TBT) see the followi
21、ng URL: Foreword - Supplementary information The committee responsible for this document is ISO/TC 21, Equipment for fire protection and fire fighting, Subcommittee SC 3, Fire detection and alarm systems. This second edition cancels and replaces the first edition (ISO 7240-28:2008), which has been t
22、echnically revised. ISO 7240 consists of the following parts, under the general title Fire detection and alarm systems: Part 1: General and definitions Part 2: Control and indicating equipment Part 3: Audible alarm devices Part 4: Power supply equipment Part 5: Point-type heat detectors Part 6: Carb
23、on monoxide fire detectors using electro-chemical cells Part 7: Point-type smoke detectors using scattered light, transmitted light or ionization Part 8: Carbon monoxide fire detectors using an electro-chemical cell in combination with a heat sensor Part 9: Test fires for fire detectors Technical Sp
24、ecification Part 10: Point-type flame detectors Part 11: Manual call points Part 12: Line type smoke detectors using a transmitted optical beam Part 13: Compatibility assessment of system componentsiv ISO 2014 All rights reserved BS ISO 7240-28:2014 ISO 7240-28:2014(E) Part 14: Design, installation,
25、 commissioning and service of fire detection and fire alarm systems in and around buildings Part 15: Point type fire detectors using scattered light, transmitted light or ionization sensors in combination with a heat sensor Part 16: Sound system control and indicating equipment Part 17: Short-circui
26、t isolators Part 18: Input/output devices Part 19: Design, installation, commissioning and service of sound systems for emergency purposes Part 20: Aspirating smoke detectors Part 21: Routing equipment Part 22: Smoke-detection equipment for ducts Part 23: Visual alarm devices Part 24: Sound-system l
27、oudspeakers Part 25: Components using radio transmission paths Part 27: Point-type fire detectors using a scattered-light, transmitted-light or ionization smoke sensor, an electrochemical-cell carbon-monoxide sensor and a heat sensor Part 28: Fire protection control equipment ISO 2014 All rights res
28、erved v BS ISO 7240-28:2014 ISO 7240-28:2014(E) Introduction This part of the ISO 7240 has been prepared by ISO/TC 21, Subcommittee SC 3, the secretariat of which is held by SA and is based on ISO 7240-28:2008. Fire protection control equipment (FPCE) (ISO 7240-1:2014, Figure 1, item G) receives sig
29、nals from control and indicating equipment (ISO 7240-1:2014, Figure 1, item B) and sends initiating signals to automatic fire protection equipment (AFPE) (ISO 7240-1:2014, Figure 1, item H). The initiating signals are used to operate AFPE, such as pumps associated with fire suppression systems, cont
30、rol doors, dampers, fans, and other equipment. This part of ISO 7240 describes the mandatory functions that it is required on all FPCE covered by this part of ISO 7240, and optional functions with their associated requirements. It is intended that the options be used for specific applications, as re
31、commended in application guidelines. Each optional function is included as a separate entity, with its own set of associated requirements, in order to permit the FPCE covered by this part of ISO 7240, with different combinations of functions, to conform to the specified requirements. It is necessary
32、 that FPCE complying with this part of ISO 7240 fulfil the requirements of all of the mandatory functions, together with the requirements of those optional functions that are provided. Other functions associated with the fire detection and alarm system can also be provided, even if not specified in
33、this part of ISO 7240.vi ISO 2014 All rights reserved BS ISO 7240-28:2014 INTERNATIONAL ST ANDARD ISO 7240-28:2014(E) Fire detection and alarm systems Part 28: Fire protection control equipment 1 Scope This part of ISO 7240 specifies requirements, methods of test, and performance criteria for fire p
34、rotection control equipment (FPCE) (ISO 7240-1:2014, Figure 1, item G) connected to automatic fire protection equipment (AFPE) (ISO 7240-1:2014, Figure 1, item H) installed in buildings. The FPCE receives signals from fire detection control and indicating equipment (ISO 7240-1:2014, Figure 1, item B
35、), sends control signals to, and indicates the condition of, the AFPE (see Figure 1). The control signals are used to initiate automatic fire protection equipment, such as pumps associated with fire suppression systems, control doors, dampers, fans, and the like.Pump start G 1 Smoke control C 1 Fire
36、 doors C 1 C C C C H C G Smoke control Pump start Fire doors C a) FPCE with discrete transmission paths b) FPCE with serial transmission path Key G fire protection control equipment H automatic fire protection equipment 1 automatic control indicator manual control F i g u r e 1 T y p i c a l f i r e
37、 p r o t e c t i o n c o n t r o l e q u i p m e n t c o n f i g u r a t i o n ISO 2014 All rights reserved 1 BS ISO 7240-28:2014 ISO 7240-28:2014(E) 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its applica
38、tion. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ISO 7240-1:2014, Fire detection and alarm systems Part 1: General and definitions ISO 7240-2, Fire detection and alarm systems Part 2:
39、 Control and indicating equipment ISO 7240-4, Fire detection and alarm systems Part 4: Power supply equipment ISO 7240-13, Fire detection and alarm systems Part 13: Compatibility assessment of system components IEC 60068-1, Environmental testing Part 1: General and guidance IEC 60068-2-1, Environmen
40、tal testing Part 2-1: Tests Tests A: Cold IEC 60068-2-6, Environmental testing Part 2-6: Tests Test Fc: Vibration (sinusoidal) IEC 60068-2-47, Environmental testing Part 2-47: Tests Mounting of specimens for vibration, impact and similar dynamic tests IEC 60068-2-75, Environmental testing Part 2-75:
41、 Tests Test Eh: Hammer tests IEC 60068-2-78, Environmental testing Part 2-78: Tests Test Cab: Damp heat, steady state IEC 60529, Degrees of protection provided by enclosures (IP Code) IEC 60721-3-3, Classification of environmental conditions Part 3-3: Classification of groups of environmental parame
42、ters and their severities Stationary use at weatherprotected locations EN 50130-4, Alarm systems Part 4: Electromagnetic compatibility Product family standard: Immunity requirements for components of fire, intruder, hold up, CCTV, access control and social alarm systems 3 T erms, a bbr e viat ed t e
43、rms, and definition s 3.1 Definitions For the purposes of this document, the terms and definitions given in ISO 7240-1 and the following apply. 3.1.1 functional condition condition of the FPCE characterized by its indication at the FPCE Note 1 to entry: The functional conditions recognized in this p
44、art of ISO 7240 are the following: quiescent condition, specified in 4.2; fire protection condition, specified 4.3; fault warning condition, specified in 4.4; disabled condition, specified in 4.5; test condition, specified 4.6.2 ISO 2014 All rights reserved BS ISO 7240-28:2014 ISO 7240-28:2014(E) 3.
45、2 Abbreviated termsAFPE automatic fire protection equipmentFPCE fire protection control equipment 4 Requirements 4.1 General 4.1.1 The FPCE shall be capable of unambiguously controlling and indicating the following functional conditions, as described in 4.2 to 4.6: quiescent condition; fire protecti
46、on condition; fault warning condition; disabled condition; test condition. 4.1.2 The FPCE shall be capable of functioning simultaneously in any combination of the following functional conditions: fire protection condition; fault warning condition; disabled condition; test condition. 4.1.3 If functio
47、ns other than those specified in this part of ISO 7240 are provided, they shall not jeopardize compliance with any requirements of this part of ISO 7240. 4.1.4 If an optional function is included in the FPCE, then all the corresponding requirements shall be met. 4.1.5 Functions required in this part
48、 of ISO 7240 can be performed within fire detection control and indicating equipment complying with ISO 7240-2. 4.2 Quiescent condition The FPCE shall be in the quiescent condition when the FPCE is powered, and no other functional condition is indicated. Any kind of system information can be display
49、ed during the quiescent condition. However, no indications shall be given that can be confused with the fire protection condition, fault warning condition, disabled condition, or test condition. ISO 2014 All rights reserved 3 BS ISO 7240-28:2014 ISO 7240-28:2014(E) 4.3 Fire protection condition 4.3.1 R ec eption and pr oc essing of fir e pr ot ection c ondition signals 4.3.1.1 The FPCE shall receive fire al