1、 AMERICAN NATIONAL STANDARD FOR TELECOMMUNICATIONS ATIS-0600010.03.2011 HEAT DISSIPATION REQUIREMENTS FOR NETWORK TELECOMMUNICATIONS EQUIPMENT ATIS is the leading technical planning and standards development organization committed to the rapid development of global, market-driven standards for the i

2、nformation, entertainment and communications industry. More than 200 companies actively formulate standards in ATIS Committees, covering issues including: IPTV, Cloud Services, Energy Efficiency, IP-Based and Wireless Technologies, Quality of Service, Billing and Operational Support, Emergency Servi

3、ces, Architectural Platforms and Emerging Networks. In addition, numerous Incubators, Focus and Exploratory Groups address evolving industry priorities including Smart Grid, Machine-to-Machine, Networked Car, IP Downloadable Security, Policy Management and Network Optimization. ATIS is the North Ame

4、rican Organizational Partner for the 3rd Generation Partnership Project (3GPP), a member and major U.S. contributor to the International Telecommunication Union (ITU) Radio and Telecommunications Sectors, and a member of the Inter-American Telecommunication Commission (CITEL). ATIS is accredited by

5、the American National Standards Institute (ANSI). For more information, please visit . AMERICAN NATIONAL STANDARD Approval of an American National Standard requires review by ANSI that the requirements for due process, consensus, and other criteria for approval have been met by the standards develop

6、er. Consensus is established when, in the judgment of the ANSI Board of Standards Review, substantial agreement has been reached by directly and materially affected interests. Substantial agreement means much more than a simple majority, but not necessarily unanimity. Consensus requires that all vie

7、ws and objections be considered, and that a concerted effort be made towards their resolution. The use of American National Standards is completely voluntary; their existence does not in any respect preclude anyone, whether he has approved the standards or not, from manufacturing, marketing, purchas

8、ing, or using products, processes, or procedures not conforming to the standards. The American National Standards Institute does not develop standards and will in no circumstances give an interpretation of any American National Standard. Moreover, no person shall have the right or authority to issue

9、 an interpretation of an American National Standard in the name of the American National Standards Institute. Requests for interpretations should be addressed to the secretariat or sponsor whose name appears on the title page of this standard. CAUTION NOTICE: This American National Standard may be r

10、evised or withdrawn at any time. The procedures of the American National Standards Institute require that action be taken periodically to reaffirm, revise, or withdraw this standard. Purchasers of American National Standards may receive current information on all standards by calling or writing the

11、American National Standards Institute. Notice of Disclaimer data centers typically contain high-end servers and storage products with mission-critical functions. 3.9 Deflector: Any device that directs - changes the direction(s) of - the air in some manner. 3.10 Diffuser: Any device that diffuses or

12、spreads out or scatters air in some manner, to give a soft flow. 3.11 Equipment under Test (EUT): The equipment being reviewed for conformance to the requirements specified in this standard, which include but are not limited to circuit packs, individual or multiple shelves, and single or multiple fr

13、ameworks. 3.12 Field Replaceable Unit (FRU): Network telecommunications equipment that is capable of being replaced in the field. 3.13 Frame Level: An equipment frame consists of structural framework that occupies floor space and all the equipment mounted in it. 3.14 Framework: Generically considere

14、d to include frames, housings, cabinets, racks, bays, enclosures, or other structures for supporting electronic equipment. 3.15 Full Configuration: Maximum equipage for a given application. 3.16 Heat Dissipation: Excess energy expelled from the equipment as heat. 3.17 Hut: A small (e.g., 10ft. x 20f

15、t. 3.048m x 6.096m), environmentally controlled aboveground structure used to house telecommunications equipment. 3.18 Reevaluation: An engineering analysis which may include testing to determine the effects of product changes on reported results. ATIS-0600010.03.2011 3 3.19 Shelf Level: A single ch

16、assis of equipment that mounts inside a framework. 3.20 Uncontrolled Environment: A space housing telecommunications equipment that provides no ambient temperature and humidity conditions. 4 GENERAL CONDITIONS FOR TESTS 4.1 Test Configuration The equipment under test is to be populated and configure

17、d as described in this Section with any equipment and circuit packs intended for the specific model or simulated heat loads that will be equivalent to the worst case heat load for the series of models. All feeder and support interfaces servicing the equipment shall be connected and active, or approp

18、riately terminated, if they contribute to the heat dissipation. ATIS energy efficiency for telecommunications equipment standard (ATIS-0600015, Methodology for Measurement and Reporting-General Requirements) and its supplemental standards shall be used for test configuration. For equipment types not

19、 covered by the ATIS energy efficiency telecommunications equipment standard (ATIS-0600015 documents), the equipment shall be tested based on the manufacturers defined normal operating state. If it can be demonstrated that a particular interface(s) does not contribute to the heat dissipation of the

20、equipment, these interfaces are not required to be terminated or exercised (alarm interfaces, RS232, etc.). 4.2 Test Conditions 4.2.1 Temperature Measurements shall be made at an effective temperature of 27C (80.6F). The data reported for the EUT shall represent input power expected when the EUT is

21、operating in a simulated environment of 27C (80.6F). To capture this potential higher energy consumption and/or different airflow characteristics, one of the following methods shall be used: Test in a thermally controlled environment at 27C, -0C +3C (80.6F, -0F + 5.4F). Or, test in a thermally contr

22、olled environment that is between 23C (73.4F) and 27C (80.6F). If this method is to be used, perform the following: o If fans are configurable, the speed setting of the fans should be representative of 27C (80.6F) at sea level. o If fans are not configurable, a fan speed power adjustment shall be ad

23、ded to the measured system power to compensate for the difference in power consumption of the fans operating at less than 27C (80.6F) compared to the fans operating at 27C (80.6F). With a modular system, the power from the fans may be evaluated once and incorporated in the data matrix. NOTE - Non-Co

24、nfigurable adjustments shall be identified within the test report. o If cooling is provided by other than fans (e.g., thermo-electric cooling), or if component efficiency or other operating parameters are affected by the test temperature other than 27C (80.6F), then the manufacturer shall provide pr

25、ocedures on how to compensate for any differences in heat dissipation. The testing lab shall incorporate these procedures into the test plan. If these procedures are not feasible, then the test shall be performed in a thermally controlled environment of 27C (80.6F). ATIS-0600010.03.2011 4 o Measured

26、 exhaust temperature data shall be adjusted to compensate for the delta between the controlled environment temperature and 27C (80.6F). This assumes an effective linear temperature compensation. 4.2.2 Humidity The equipment shall be evaluated at a relative humidity of 30% to 75%. 4.2.3 Barometric Pr

27、essure The equipment shall be evaluated at a barometric pressure between 102 and 80kPa. This corresponds to typical barometric pressure between altitudes of 60m (197ft) below sea level to 1829m (6000ft) above sea level. 4.2.4 DC Powered Equipment Voltage The equipment shall be evaluated at a DC volt

28、age of 53V 1V. (This level is consistent with the voltage defined in ATIS-0600315.2007 for a -48Vdc powering system.) Unless otherwise specified in a supplemental standard to this General Requirement Standard, equipment using nominal DC voltages other than -48Vdc shall be evaluated at 2% of the spec

29、ified voltage. Where applicable, the typical steady state voltage as defined in ATIS-0600315.2007 shall be used. 4.2.5 AC Powered Equipment Voltage The equipment shall be evaluated with a source providing the conditions found in Table 1 of ANSI C84.1, Voltage Range A. 4.3 Test Data Points Five data

30、points shall be provided at a normalized 27C (80.6F) level with the following varying traffic loads: 0% (sleep) (measured load) 25% (idle) (measured load) 50% (nominal) (measured load) 75% (typical maximum) (measured or calculated load) 100% (maximum) (measured or calculated load) For other than 100

31、%, load shall be evenly spread throughout the system. Optionally, a sixth measurement may be added by the manufacturer if the nominal operating range is not included above. 5 HEAT DISSIPATION MEASUREMENT 5.1 General Heat dissipation data (in Watts) of the equipment shall be provided for those end-us

32、ers managing cooling requirements in telecommunications facilities. Heat dissipation data (in Watts) shall be provided ATIS-0600010.03.2011 5 for the equipment under operation at the five steady state continuous duty conditions. See Section 4.1, Test Configuration. 5.2 Power Measurement Equipment Ac

33、curate measurement of power consumption by a given piece of equipment is critical in determining the overall heat dissipation for that product. In cases where the current measurement will be less than 100 mA, the meter resolution shall be 1 mA or better. Regarding AC inputs, insufficient sample inte

34、rvals and measurement durations can lead to power measurement errors. Use of a power analyzer (or equipment with equivalent capability and accuracy) is required for measuring the input power of a given piece of equipment. DC power equipment should meet the electromagnetic noise requirements of ATIS

35、0600315.2007, therefore the AC noise on the input power port(s) is not considered significant. For fluctuating loads, the reported data shall be the average of logged data over a 15 minute period. 5.3 Power Measurements - Input When multiple power sources are used, the power input from all lines sha

36、ll be considered. All redundant power supplies and rectifiers shall be active in the system. EUT with multiple power connections (including redundant connections) shall have all feeds connected and the power flow from all feeds summed to obtain total system power. If the power is coming from a remot

37、e source, such as a span power line or other remote power source, these need to be added to the power number used to calculate overall heat dissipation. For frame level: All frame level power measurements shall be taken at the main system power input (incorporating all operational modules). For shel

38、f level: Shelf level power measurements shall be taken at the main shelf power input (incorporating all operational modules). For circuit packs: Circuit pack power measurements shall be taken at each of the five load levels by tapping into the circuit pack input current line(s) (e.g., at the jumper,

39、 fuse, or current protection device) or by removing the circuit pack from the shelf and monitoring the change in power at the shelf or frame power input. For base configuration: Base configuration power measurements shall be calculated by subtracting the power of all non-base configuration circuit p

40、acks from the total main shelf level power. A linear efficiency for power supplies is assumed and considered acceptable for the purposes of this standard. 5.4 Power Measurements - Output The power dissipated in external loads for some EUT can be a significant portion of the Powerin. In this case, th

41、e power dissipated externally shall be subtracted from the Powerinfor the EUT. Examples of external loads to be considered: Span powered (xDSL, Traditional, such as repeated T1 spans, CATV span, DC span powering units) Sealing Current - shall be measured with an appropriate loading device for the te

42、chnology used ATIS-0600010.03.2011 6 Conditioned voltages (e.g., Rectifiers, power supplies, providing power to external loads) PoE POTs External load terminations shall be actual terminating devices like those used in actual service, or simulation devices that cause the equipment to dissipate the s

43、ame equivalent heat. For the following interfaces, output power is not considered significant for purposes of this standard: Non-span powered xDSL Wireline traffic (e.g., T1/DS3) Equipment with radio frequency (RF) output35.5 EUT Stabilization The average input power shall be allowed to stabilize fo

44、r a minimum of 15 minutes. Stabilization occurs when the average input power does not deviate more than 1% in those 15 minutes. 5.6 Calculations Powerinminus PoweroutOutput DC= VDCx Amps Output AC = VRMSx AmpsRMSx PF 3See informative Annex B. ATIS-0600010.03.2011 7 Table 1 - Heat Dissipation Summary

45、 (Watts)45Device6(Sleep), 0% (Idle 0, 25% (Nominal), 50% (Full Load), 75% (Max), 100% Optional 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 400,000 for wattage 100; 00.0 for wattage 100 5Full configuration; wattages can be either measured or calculated (source shall be reported) 6Examples: EUT, frame, she

46、lf, circuit pack ATIS-0600010.03.2011 8 6 AIRFLOW MEASUREMENTS 6.1 Location of Measurement Airflow measurements shall be 6 inches (0.1524 meter) from the surface exhaust plane taken between 23C (73.4F) and 27C (80.6F). The measurement angle of the velocity measurement device should be parallel to th

47、e surface exhaust plane as shown in Figure 1. Airflow measurement shall be obtained using methods described in 6.3. 6.2 EUT Stabilization The average temperature shall be allowed to stabilize for a minimum of 15 minutes. Stabilization occurs when the average temperature does not deviate more than 2C

48、 (3.6F) over a one hour period. 6.3 Measurement Methods The following methods should be used to obtain consistent reporting results. 6.3.1 Device Dimensions Measurements will be provided in the following order: width, height, and depth. This includes the primary shelf/frame only, not cable managemen

49、ts, attachments, mounting ears, or any other protrusions. 6.3.2 Intake Location & Dimensions For each intake location, measurements shall be provided. Measurements will be provided in the following order: width and height. ATIS-0600010.03.2011 9 Figure 1 - F1-R3 Airflow 6.3.3 Exhaust Location & Dimensions For each exhaust location, measurements shall be provided. Measurements will be provided in the following order: width, then height. Figure 2 - F1-T/R3 Airflow ATIS-0

展开阅读全文
相关资源
  • ANSI Z97 1-2009 American National Standard for Safety Glazing Materials used in Buildings - Safety Performance Specifications and Methods of Test《建筑物中窗用玻璃材料安全性用.pdfANSI Z97 1-2009 American National Standard for Safety Glazing Materials used in Buildings - Safety Performance Specifications and Methods of Test《建筑物中窗用玻璃材料安全性用.pdf
  • ANSI Z97 1 ERTA-2010 Re ANSI Z97 1 - 2009 Errata《修订版 美国国家标准学会Z97 1-2009标准的勘误表》.pdfANSI Z97 1 ERTA-2010 Re ANSI Z97 1 - 2009 Errata《修订版 美国国家标准学会Z97 1-2009标准的勘误表》.pdf
  • ANSI Z21 40 2a-1997 Gas-Fired Work Activated Air-Conditioning and Heat Pump Appliances (Same as CGA 2 92a)《燃气、工作激活空气调节和热泵器具(同 CGA 2 92a)》.pdfANSI Z21 40 2a-1997 Gas-Fired Work Activated Air-Conditioning and Heat Pump Appliances (Same as CGA 2 92a)《燃气、工作激活空气调节和热泵器具(同 CGA 2 92a)》.pdf
  • ANSI Z124 9-2004 American National Standard for Plastic Urinal Fixtures《塑料小便器用美国国家标准》.pdfANSI Z124 9-2004 American National Standard for Plastic Urinal Fixtures《塑料小便器用美国国家标准》.pdf
  • ANSI Z124 4-2006 American National Standard for Plastic Water Closet Bowls and Tanks《塑料抽水马桶和水箱用美国国家标准》.pdfANSI Z124 4-2006 American National Standard for Plastic Water Closet Bowls and Tanks《塑料抽水马桶和水箱用美国国家标准》.pdf
  • ANSI Z124 3-2005 American National Standard for Plastic Lavatories《塑料洗脸盆用美国国家标准》.pdfANSI Z124 3-2005 American National Standard for Plastic Lavatories《塑料洗脸盆用美国国家标准》.pdf
  • ANSI T1 659-1996 Telecommunications - Mobility Management Application Protocol (MMAP) RCF-RACF Operations《电信 可移动管理应用协议(MMAP) RCF-RACF操作》.pdfANSI T1 659-1996 Telecommunications - Mobility Management Application Protocol (MMAP) RCF-RACF Operations《电信 可移动管理应用协议(MMAP) RCF-RACF操作》.pdf
  • ANSI T1 651-1996 Telecommunications – Mobility Management Application Protocol (MMAP)《电信 可移动性管理应用协议》.pdfANSI T1 651-1996 Telecommunications – Mobility Management Application Protocol (MMAP)《电信 可移动性管理应用协议》.pdf
  • ANSI T1 609-1999 Interworking between the ISDN User-Network Interface Protocol and the Signalling System Number 7 ISDN User Part《电信 ISDN用户间网络接口协议和7号信令系统ISDN用户部分.pdfANSI T1 609-1999 Interworking between the ISDN User-Network Interface Protocol and the Signalling System Number 7 ISDN User Part《电信 ISDN用户间网络接口协议和7号信令系统ISDN用户部分.pdf
  • ANSI T1 605-1991 Integrated Services Digital Network (ISDN) - Basic Access Interface for S and T Reference Points (Layer 1 Specification)《综合服务数字网络(ISDN) S和T基准点的.pdfANSI T1 605-1991 Integrated Services Digital Network (ISDN) - Basic Access Interface for S and T Reference Points (Layer 1 Specification)《综合服务数字网络(ISDN) S和T基准点的.pdf
  • 猜你喜欢
    相关搜索

    当前位置:首页 > 标准规范 > 国际标准 > ANSI

    copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
    备案/许可证编号:苏ICP备17064731号-1