1、*USACE / NAVFAC / AFCESA / NASA UFGS-33 34 13 (April 2008)-Preparing Activity: USACE SupersedingUFGS-33 34 13 (April 2006)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated March 2008*SECTION TABLE OF CONTENTSDIVISION 33 - UTILITIESSECTION 33 34 13SIPHONS, DOSING04/08

2、PART 1 GENERAL1.1 REFERENCES1.2 SYSTEM DESCRIPTION1.3 SUBMITTALSPART 2 PRODUCTS2.1 MATERIAL AND EQUIPMENT2.1.1 Pipe2.1.1.1 Ductile Iron Pipe2.1.1.2 Polyvinyl Chloride (PVC) Pipe2.1.1.3 Polyethylene Pipe2.1.2 Pipe Fittings2.1.2.1 Ductile Iron Fittings2.1.2.2 Polyvinyl Chloride (PVC) Fittings2.1.2.3 P

3、olyethylene Fittings2.1.2.4 Malleable-Iron Fittings2.1.2.5 Malleable-Iron Unions2.1.3 Siphon Bells, Inlet Castings, and Similar Equipment2.1.3.1 Cast Iron2.1.3.2 Polyvinyl Chloride (PVC)2.1.3.3 Polyethylene2.1.4 ValvesPART 3 EXECUTION3.1 INSTALLATION3.2 SIPHONS3.3 PIPING3.4 PAINTING- End of Section

4、Table of Contents -SECTION 33 34 13 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-33 34 13 (April 2008)-Preparing Activity: USACE SupersedingUFGS-33 34 13 (April 2006)UNIFIED FACILITIES GUIDE SPECIFICATION

5、SReferences are in agreement with UMRL dated March 2008*SECTION 33 34 13SIPHONS, DOSING04/08*NOTE: This guide specification covers the requirements for automatic dosing siphons for sewage.Edit this guide specification for project specific requirements by adding, deleting, or revising text. For brack

6、eted items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brackets are present.Comments and suggestions on this guide specification are welcome and should be directed to the technical proponent of t

7、he specification. A listing of technical proponents, including their organization designation and telephone number, is on the Internet.Recommended changes to a UFGS should be submitted as a Criteria Change Request (CCR).*PART 1 GENERAL1.1 REFERENCES*NOTE: This paragraph is used to list the publicati

8、ons cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Sections Reference A

9、rticle to automatically place the reference in the Reference Article. Also use the Reference Wizards Check Reference feature to update the issue dates.SECTION 33 34 13 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-References not used in the t

10、ext will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.*The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the bas

11、ic designation only.AMERICAN WATER WORKS ASSOCIATION (AWWA)AWWA C110/A21.10 (2003) Ductile-Iron and Gray-Iron Fittings for WaterAWWA C111/A21.11 (2000) Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and FittingsAWWA C151/A21.51 (2002; Errata 2002) Ductile-Iron Pipe, Centrifugally Cast, for Wate

12、rASME INTERNATIONAL (ASME)ASME B16.3 (2006) Malleable Iron Threaded Fittings, Classes 150 and 300ASME B16.39 (1998; R 2006) Standard for Malleable Iron Threaded Pipe Unions; Classes 150, 250, and 300ASTM INTERNATIONAL (ASTM)ASTM A 48/A 48M (2003) Standard Specification for Gray Iron CastingsASTM D 3

13、034 (2006) Standard Specification for Type PSM Poly(Vinyl Chloride) (PVC) Sewer Pipe and FittingsASTM D 3350 (2006) Polyethylene Plastics Pipe and Fittings MaterialsMANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS INDUSTRY (MSS)MSS SP-80 (2003) Bronze Gate, Globe, Angle and Check Valv

14、es1.2 SYSTEM DESCRIPTIONThe dosing siphon shall be a deep seal trapless type suitable for the service required, completely automatic in operation, starting promptly when the sewage has reached the predetermined high water level, and shutting off positively at the low water level. Accomplish the star

15、ting, stopping, and alternating operations without the use of electrical or mechanical devices having moving parts. Capacities of equipment and materials shall be not less than those specified or indicated. Each siphon bell shall have the manufacturers name, address, and catalog or model number on a

16、 plate SECTION 33 34 13 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-securely in a conspicuous place. In lieu of nameplate, the manufacturers name or trademark may be cast integrally with the equipment, or standard, or otherwise permanently

17、marked.1.3 SUBMITTALS*NOTE: Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list to reflect only the submittals required for the project. Submittals should be kept to the minimum required for adequate quality control.A “G” following a sub

18、mittal item indicates that the submittal requires Government approval. Some submittals are already marked with a “G”. Only delete an existing “G” if the submittal item is not complex and can be reviewed through the Contractors Quality Control system. Only add a “G” if the submittal is sufficiently i

19、mportant or complex in context of the project.For submittals requiring Government approval on Army projects, a code of up to three characters within the submittal tags may be used following the “G“ designation to indicate the approving authority. Codes for Army projects using the Resident Management

20、 System (RMS) are: “AE“ for Architect-Engineer; “DO“ for District Office (Engineering Division or other organization in the District Office); “AO“ for Area Office; “RO“ for Resident Office; and “PO“ for Project Office. Codes following the “G“ typically are not used for Navy, Air Force, and NASA proj

21、ects.Choose the first bracketed item for Navy, Air Force and NASA projects, or choose the second bracketed item for Army projects.*Government approval is required for submittals with a “G“ designation; submittals not having a “G“ designation are for Contractor Quality Control approval.information on

22、ly. When used, a designation following the “G“ designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:SD-02 Shop DrawingsApproved Detail Drawings; G; G, _Complete drawings and other descriptiv

23、e data as the Contracting Officer may require to demonstrate compliance with the contract documents, not less than _ days before starting installation of any material or equipment. Drawings shall be submitted at one time. If departure from the contract drawings is deemed necessary, details of such d

24、eparture, including changes in related portions of the project and the reasons therefor, shall be submitted with the drawings. Approved departures shall be made at SECTION 33 34 13 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-no additional c

25、ost to the Government.SD-03 Product DataDosing Siphon SystemData including catalog numbers, cuts, and other descriptive data required to assure compliance with the specifications. A complete list in triplicate of material and equipment to be incorporated in the work, within _ working days of receipt

26、 of notice to proceed, and before starting installation of any material or equipment. A complete list in triplicate of parts and supplies for each different item of equipment listed, with current unit prices and sources of supply, a list of parts and supplies that are either normally furnished at no

27、 extra cost with the purchase of the equipment or are specified to be furnished as a part of the contract, and a list of additional items recommended by the manufacturer to assure efficient operation for a period of 120 days, not later than four months prior to the date of beneficial use.PART 2 PROD

28、UCTS2.1 MATERIAL AND EQUIPMENTProvide materials and equipment conforming to the publications and other requirements specified below. Other material and equipment shall be as specified and as shown on the approved detail drawings, and shall be the products of manufacturers regularly engaged in the ma

29、nufacture of such products. Material and equipment shall essentially duplicate items that have been in satisfactory use at least 2 years prior to bid opening.2.1.1 Pipe2.1.1.1 Ductile Iron PipeAWWA C151/A21.51, _ kPa psi working pressure.2.1.1.2 Polyvinyl Chloride (PVC) PipeASTM D 3034.2.1.1.3 Polye

30、thylene PipeASTM D 3350.2.1.2 Pipe Fittings2.1.2.1 Ductile Iron FittingsAWWA C110/A21.10 and AWWA C111/A21.11 _ kPa psi working pressure.2.1.2.2 Polyvinyl Chloride (PVC) FittingsASTM D 3034.2.1.2.3 Polyethylene FittingsASTM D 3350.SECTION 33 34 13 Page 5Provided by IHSNot for ResaleNo reproduction o

31、r networking permitted without license from IHS-,-,-2.1.2.4 Malleable-Iron FittingsASME B16.3.2.1.2.5 Malleable-Iron UnionsASME B16.39.2.1.3 Siphon Bells, Inlet Castings, and Similar Equipment2.1.3.1 Cast IronASTM A 48/A 48M, Class _.2.1.3.2 Polyvinyl Chloride (PVC)ASTM D 3034.2.1.3.3 PolyethyleneAS

32、TM D 3350.2.1.4 ValvesBronze, MSS SP-80, Type _.PART 3 EXECUTION3.1 INSTALLATIONInstall the Dosing Siphon System in accordance with the recommendations of the manufacturer as approved. The installation shall be made by workers experienced in the installation of this type of equipment.3.2 SIPHONSSiph

33、on bells, air bells, inlet castings, and similar equipment shall be cast iron, polyvinyl chloride (PVC) or polyethylene. Siphon bells shall be provided with suitable connections for the air-control piping and the sniff pipe shall be mounted over the _ mm inch diameter feed pipe. Each siphon shall be

34、 capable of discharging at a maximum rate of flow of _ L/second gpm while operating under a drawing depth of _ mm inches, and under the head conditions as indicated on the drawings. The average rate of inflow shall be _ L/second gpm and the minimum 4-hour average rate shall be _ L/second gpm. Each s

35、iphon shall be provided with a seal trap in the discharge pipe of such depth that an effective seal against blowing shall be maintained at all times. Each siphon shall discharge into an airtight piping system having a discharge point about the lowest point in the connecting pipe to form an effective

36、 seal. Siphons for alternating operation from a common chamber shall be provided with auxiliary equipment necessary for alteration in a predetermined sequence. The air piping shall be arranged and valved to permit removal of any number of the siphons from service without disturbing the alternating o

37、peration of the remaining siphons. Equipment for twin dosing tanks shall include air bells, air-locking inflow connection, and all similar equipment that may be necessary to alternate the inflow from one tank to the other and to prevent flow into the tank while the siphon in the tank is discharging.

38、SECTION 33 34 13 Page 6Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-3.3 PIPINGThe overflow pipe, feed pipe, air control and sniff pipe may be cast iron, polyvinyl chloride (PVC), or polyethylene. Cast iron pipes shall be installed with malleable-i

39、ron fittings and bronze valves. Cast iron pipe shall be installed with sufficient malleable-iron unions to facilitate maintenance or removal, and shall be assembled using a stiff mixture of graphite and oil, or an inert filler and oil, or an approved graphite compound, applied with a brush to the ma

40、le threads only.3.4 PAINTINGThe equipment shall be thoroughly cleaned, primed, and given finish painting at the factory in accordance with the recommendations of the manufacturer. Field painting is specified in Section 09 90 00 PAINTS AND COATINGS.- End of Section -SECTION 33 34 13 Page 7Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-