1、Designation: B1 13 (Reapproved 2018)Standard Specification forHard-Drawn Copper Wire1This standard is issued under the fixed designation B1; the number immediately following the designation indicates the year of originaladoption or, in the case of revision, the year of last revision. A number in par

2、entheses indicates the year of last reapproval. A superscriptepsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.1. Scope1.1 This specification covers hard-drawn round copper wirefor elec

3、trical purposes.1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.2.1 ExceptionFor density, resistivity and temperature,the values st

4、ated in SI units are to be regarded as standard.1.3 This international standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by t

5、he World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Documents2.1 The following documents of the issue in effect at thetime of reference form a part of this specification to the extentreferenced herein:2.2 ASTM Standards:2B49 Specification for Copper Rod for Electrica

6、l PurposesB193 Test Method for Resistivity of Electrical ConductorMaterialsB258 Specification for Standard Nominal Diameters andCross-Sectional Areas of AWG Sizes of Solid RoundWires Used as Electrical Conductors2.3 Other Documents:NBS Handbook 100 Copper Wire Tables33. Ordering Information3.1 Order

7、s for material under this specification shall includethe following information:3.1.1 Quantity of each size,3.1.2 Wire size: diameter in inches (5.3 and Table 1),3.1.3 Type of copper, if special (Section 4),3.1.4 Package size (10.1),3.1.5 Special package marking, if required, and3.1.6 Place of inspec

8、tion (7.1).4. Materials4.1 The material shall be copper of such quality and puritythat the finished product shall have the properties and charac-teristics prescribed in this specification.NOTE 1Specification B49 defines the materials suitable for use.5. General Requirements (see Section 8)5.1 Tensil

9、e Strength and ElongationThe wire shall con-form to the requirements as to tensile strength and elongationprescribed in Table 1 (see Explanatory Note 1 and Note 2). Forwire whose nominal diameter is more than 0.001 in. (0.025mm) greater than a size listed in Table 1 and less than that ofthe next lar

10、ger size, the requirements of the next larger sizeshall apply.5.1.1 Tests on a specimen containing a joint shall show atleast 95 % of the tensile strength give in Table 1. Elongationtests shall not be made on a specimen containing a joint.5.2 ResistivityThe electrical resistivity at 20C shall notexc

11、eed the following values:Nominal Diameter, in.Resistivity at 20C,lb/mile2g/m20.460 to 0.325 (11.684 to 8.255 mm), incl 900.77 0.15775Under 0.325 to 0.0403 (8.255 to 1.024 mm), incl 910.15 0.159405.3 Dimensions and Permissible VariationsWithin therange of diameters given in Table 1, the wire shall no

12、t varyfrom the specified diameter by more than plus and minus 1 %,expressed to the nearest 0.0001 in. (or 0.001 mm) (seeExplanatory Note 4).5.4 JointsNo joints shall be made in the completed wire(Explanatory Note 3). Joints in the wire and rods made prior to1This specification is under the jurisdict

13、ion of ASTM Committee B01 onElectrical Conductors and is the direct responsibility of Subcommittee B01.04 onConductors of Copper and Copper Alloys.Current edition approved Oct. 1, 2018. Published October 2018. Originallyapproved in 1909. Last previous edition approved in 2013 as B1 13. DOI:10.1520/B

14、0001-13R18.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from National Technical Information Ser

15、vice (NTIS), 5301 ShawneeRd., Alexandria, VA 22312, http:/www.ntis.gov.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accordance with internationally recognized principles on standardizatio

16、n established in the Decision on Principles for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.1final drawing shall be in accordance with the best commercialpractice and shall conform to the req

17、uirements prescribed in5.1.5.5 FinishThe wire shall be free of all imperfections notconsistent with the best commercial practice.6. Test Methods6.1 Tensile Strength and Elongation:6.1.1 Obtain the tensile strength, expressed in pounds persquare inch, by dividing the maximum load carried by thespecim

18、en during the tension test, by the original cross-sectionalarea of the specimen. Tensile strength and elongation may bedetermined simultaneously on the same specimen.6.1.2 Determine the elongation of the wire as the permanentincrease in length due to the breaking of the wire in tension,measured betw

19、een gage marks placed originally 10 in. (250mm) apart upon the test specimen (see Explanatory Note 5).6.1.3 If any part of the fracture takes place outside the gagemarks or in the jaws of the testing machine, or if an examina-tion of the specimen indicates a flaw, the value obtained maynot be repres

20、entative of the material. In such cases the test maybe discarded and a new test made.6.2 ResistivityDetermine the electrical resistivity of thematerial in accordance with Test Method B193 (see Explana-tory Note 6). The purchaser may accept certification that thewire was drawn from rod stock meeting

21、the InternationalStandard forAnnealed Copper instead of resistivity tests on thefinished wire.6.3 Dimensional MeasurementsDimensional measure-ments shall be made with equipment capable of measuring toa graduation of 0.0001 in. (or 0.001 mm). Take measurementson at least three places on each unit sel

22、ected for this test. Ifaccessible, take one measurement on each end and one near themiddle. The average of the three measurements shall determinecompliance with the requirements.6.4 Surface FinishMake a surface-finish inspection withthe unaided eye (normal spectacles accepted).7. Inspection7.1 Gener

23、al (see Explanatory Note 7)Unless otherwisespecified in the contract or purchaser order, the manufacturershall be responsible for the performance of all inspection andtest requirements specified.7.1.1 All inspections and tests shall be made at the place ofmanufacture unless otherwise specifically ag

24、reed to betweenthe manufacturer and the purchaser at the time of the purchase.7.1.2 The manufacturer shall afford the inspector represent-ing the purchaser all reasonable manufacturers facilities tosatisfy him that the material is being furnished in accordancewith this specification.TABLE 1 Tensile

25、PropertiesDiameterAArea at 20CNominal TensileStrengthB(see ExplanatoryNote 2)NominalElongation,%Bin. mm cmil in.2mm2psi MPa in 10 in. (250 mm)0.4600 11.684 211 600 0.1662 107.0 49 000 340 3.80.4096 10.464 167 800 0.1318 85.0 51 000 350 3.30.3648 9.266 133 100 0.1045 67.4 52 800 365 2.80.3249 8.252 1

26、05 600 0.08291 53.5 54 500 375 2.40.2893 7.348 83 690 0.06573 42.4 56 100 385 2.20.2576 6.543 66 360 0.05213 33.6 57 600 395 2.00.2294 5.827 52 620 0.04133 26.7 59 000 405 1.80.2043 5.189 41 740 0.03278 21.2 60 100 415 1.70.1819 4.620 33 090 0.02599 16.8 61 200 420 1.60.1650* 4.191 27 220 0.02138 13

27、.8 62 000 425 1.50.1620 4.115 26 240 0.02061 13.3 62 100 430 1.40.1443 3.665 20 820 0.01635 10.5 63 000 435 1.30.1340* 3.404 17 960 0.01410 9.10 63 400 435 1.30.1285 3.264 16 510 0.01297 8.37 63 700 440 1.30.1144 2.906 13 090 0.01028 6.63 64 300 445 1.20.1040* 2.642 10 820 0.008495 5.48 64 800 445 1

28、.20.1019 2.588 10 380 0.008155 5.26 64 900 445 1.20.0920* 2.387 8 460 0.00665 4.29 65 400 450 1.10.0907 2.304 8 230 0.00646 4.17 65 400 450 1.10.0808 2.052 6 530 0.00513 3.31 65 700 455 1.10.0800* 2.032 6 400 0.00503 3.24 65 700 455 1.10.0720 1.829 5 180 0.00407 2.63 65 900 455 1.10.0650* 1.651 4 22

29、0 0.00332 2.14 66 200 455 1.00.0641 1.628 4 110 0.00323 2.08 66 200 455 1.00.0571 1.450 3 260 0.00256 1.65 66 400 460 1.00.0508 1.290 2 580 0.00203 1.31 66 600 460 1.00.0453 1.151 2 050 0.00161 1.04 66 800 460 1.00.0403 1.024 1 620 0.00128 0.823 67 000 460 1.0AThe diameters marked by asterisks (*) a

30、re often employed by purchasers for communication lines, but are not in the American Wire Gage (B however, any individual production unit, thespecimen from which has a tensile strength less than theappropriate tensile strength value in Table 1 minus 1700 psi (12MPa) shall be rejected.8.1.1.1 The lot

31、 shall be considered to have failed to meet thetensile conformance criterion if the average of the fourspecimens is less than the tensile strength in Table 1 minus 400psi (3 MPa) and the tensile strength of any of the individualspecimens is less than the value in Table 1 minus 1700 psi (12MPa).8.1.1

32、.2 If the average of the four specimens is less than thetensile strength in Table 1 minus 400 psi (3 MPa) and thetensile strength of each of the individual specimens is equal toor more than the value in Table 1 minus 1700 psi (12 MPa), sixadditional specimens from six production units other than the

33、four originally sampled shall be tested. The lot shall beconsidered conforming if the tensile strength of each of the tenspecimens is not less than the appropriate tensile strength valuein Table 1 minus 1700 psi and the average of the ten specimensis not less than the value in Table 1 minus 400 psi.

34、 The lot shallbe considered to have failed to meet the tensile strengthrequirement if the tensile strength of any of the individualspecimens is less than the value in Table 1 minus 1700 psi orif the average of the ten specimens is less than the value inTable 1 minus 400 psi.8.1.2 ElongationThe lot s

35、hall be considered conforming ifthe average elongation of the four specimens is not less thanthe appropriate elongation value in Table 1 minus 0.1 percent-age points; however, any individual production unit, thespecimen from which has an elongation less than the appro-priate elongation value in Tabl

36、e 1 minus 0.2 percentage pointsshall be rejected.TABLE 2 Sampling for Dimensional MeasurementsNumber of Units in LotFirst Sample Second SampleNumber ofUnits in Sample,n1Allowable Numberof Defects inFirst Sample, c1Number of Unitsin Sample, n2n, plus n2AllowableNumber ofDefects in BothSamples, c21 to

37、 14, incl all 0 . . .15 to 50, incl 14 0 . . .51 to 100, incl 19 0 23 42 1101 to 200, incl 24 0 46 70 2210 to 400, incl 29 0 76 105 3401 to 800, incl 33 0 112 145 4Over 800 34 0 116 150 4TABLE 3 Sampling for Surface Finish and Packaging InspectionNumber of Unitsin LotNumber of Units inSample, nAllow

38、able Numberof DefectiveUnits, c1 to 30, incl all 031 to 50, incl 30 051 to 100, incl 37 0101 to 200, incl 40 0201 to 300, incl 70 1301 to 500, incl 100 2501 to 800, incl 130 3Over 800 155 4B1 13 (2018)38.1.2.1 The lot shall be considered to have failed to meet theelongation conformance criterion if

39、the average of the fourspecimens is less than the appropriate elongation value in Table1 minus 0.1 percentage points the elongation of any of theindividual specimens is less than the elongation value in Table1 minus 0.2 percentage points.8.1.2.2 If the average of the four specimens is less than thea

40、ppropriate elongation value in Table 1 minus 0.1 percentagepoints and the elongation of each of the individual specimensis equal to or more than the elongation value in Table 1 minus0.2 percentage points, six additional specimens from sixproduction units other than the four originally sampled shall

41、betested. The lot shall be considered conforming if the elongationof each of the ten specimens is not less than the appropriateelongation value in Table 1 minus 0.2 percentage points andthe average of the ten specimens is not less than the value inTable 1 minus 0.1 percentage points. The lot shall b

42、e consid-ered to have failed to meet the elongation requirement if any ofthe ten specimens is less than the appropriate elongation valuein Table 1 minus 0.2 percentage points or if the average of theten specimens is less than the elongation value in Table 1minus 0.1 percentage points.8.1.3 Resistivi

43、tyThe electrical resistivity of each of thefour specimens shall conform to the requirements of 5.2.Failure to meet this requirement shall constitute failure to meetthe resistivity conformance criterion.8.1.4 DimensionsThe dimensions of the first sample(Table 2) shall conform to the requirements of 5

44、.3. If there areno failures, the lot conforms to this requirement. If there arefailures but the number of these does not exceed the allowabledefect number, c2(Table 2), for the respective number of unitsin the sample, a second sample equal to n2shall be taken andthe total defects of the n1plus n2uni

45、ts shall not exceed theallowable defect number, c2. Failure to meet this requirementshall constitute failure to meet the dimensional conformancecriterion.8.1.5 Surface FinishThe surface finish of the samplestaken in accordance with Table 3 shall conform to the require-ments of 5.5. The number of uni

46、ts in the sample showingsurface defects not consistent with commercial practice shallnot exceed the allowable defect number, c,inTable 3. Failureto meet this requirement shall constitute failure to meet thesurface-finish conformance criterion.8.1.6 PackagingConformance to the packaging require-ments

47、 specified by the purchaser shall be determined inaccordance with Table 3. The number of units in the sampleshowing nonconformance to the requirement shall not exceedthe allowable defect number, c,inTable 3. Failure to meet thisrequirement shall constitute failure to meet the packagingconformance cr

48、iterion.9. Density9.1 For the purpose of calculating mass per unit length,cross sections, etc., the density of the copper shall be taken as8.89 g/cm3(0.32117 lb/in.3) at 20C (see Explanatory Note 9).10. Packaging and Package Marking10.1 Package sizes shall be agreed upon between the manu-facturer an

49、d the purchaser in the placing of individual orders.10.2 The wire shall be protected against damage in ordinaryhandling and shipping.11. Keywords11.1 copper electrical conductor; copper wire; electricalconductor; electrical conductorcopper; hard-drawn copperwireEXPLANATORY NOTESNOTE 1Other tests than those provided in this specification have beenconsidered at various times, such as twist tests, wrap tests, tests for elasticlimit, etc. It is the opinion of the committee that twist and wrap tests onhard-drawn wire do not serve a useful purpose and should b