ASTM C1321-2015 Standard Practice for Installation and Use of Interior Radiation Control Coating Systems (IRCCS) in Building Construction《建筑物内部辐射控制涂层系统 (IRCCS) 的安装和使用的标准实施规程》.pdf

上传人:sofeeling205 文档编号:464221 上传时间:2018-11-27 格式:PDF 页数:3 大小:86.75KB
下载 相关 举报
ASTM C1321-2015 Standard Practice for Installation and Use of Interior Radiation Control Coating Systems (IRCCS) in Building Construction《建筑物内部辐射控制涂层系统 (IRCCS) 的安装和使用的标准实施规程》.pdf_第1页
第1页 / 共3页
ASTM C1321-2015 Standard Practice for Installation and Use of Interior Radiation Control Coating Systems (IRCCS) in Building Construction《建筑物内部辐射控制涂层系统 (IRCCS) 的安装和使用的标准实施规程》.pdf_第2页
第2页 / 共3页
ASTM C1321-2015 Standard Practice for Installation and Use of Interior Radiation Control Coating Systems (IRCCS) in Building Construction《建筑物内部辐射控制涂层系统 (IRCCS) 的安装和使用的标准实施规程》.pdf_第3页
第3页 / 共3页
亲,该文档总共3页,全部预览完了,如果喜欢就下载吧!
资源描述

1、Designation: C1321 15Standard Practice forInstallation and Use of Interior Radiation Control CoatingSystems (IRCCS) in Building Construction1This standard is issued under the fixed designation C1321; the number immediately following the designation indicates the year oforiginal adoption or, in the c

2、ase of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice has been prepared for use by the designer,specifier, and applicator of Inte

3、rior Radiation Control CoatingSystems (IRCCS) for use in building construction. The scopecontains instructions related to the use and installation ofIRCCS that are sprayed, rolled, or brush applied. Examplesthat this practice is intended to address include: (1) lowemittance surfaces in vented buildi

4、ng envelope cavities in-tended to retard radiant transfer across the vented airspace; (2)low emittance surfaces at interior building surfaces intended toretard radiant transfer to or from building inhabitants; and (3)low emittance surfaces at interior building surfaces intended toreduce radiant tran

5、sfer to or from heating or cooling systems.1.2 This practice covers the installation process from pre-installation inspection through post-installation. It does notcover the production of the Interior Radiation Control CoatingMaterials.1.3 This practice is not intended to replace the manufactur-ers

6、installation instructions, but it shall be used in conjunctionwith such instructions. This practice is not intended to super-sede local, state, or federal codes.1.4 This practice assumes that the installer possesses a goodworking knowledge of the application codes and regulations,safety practices, t

7、ools, equipment, and methods necessary forthe installation of Interior Coating Materials. It also assumesthat the installer understands the fundamentals of buildingconstruction that affect the installation of an IRCCS.1.5 When the installation or use of Interior RadiationControl Coating Materials, a

8、ccessories, and systems posesafety or health problems, the manufacturer shall provide theuser appropriate current information regarding any knownproblems associated with the intended use of the products andshall also provide direction on protective measures to beemployed for safe utilization. The us

9、er shall establish appro-priate safety and health practices and determine the applicabil-ity of regulatory requirements prior to use.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to estab

10、lish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. Specific precau-tionary statements are contained in Sections 5 and 7.2. Referenced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationC1371 Test Method for

11、Determination of Emittance ofMaterials Near Room Temperature Using Portable Emis-sometersE84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE96/E96M Test Methods for Water Vapor Transmission ofMaterials2.2 NFPA Standards:3NFPA 54 National Fuel Gas CodeNFPA 211 Standard for Chimn

12、eys, Fireplaces, Vents, andSolid Fuel-Burning Appliances2.3 Other Documents:CPSC Guide to Home Wiring Hazards43. Terminology3.1 DefinitionsFor definitions of terms used in thispractice, refer to Terminology C168.3.2 Definitions of Terms Specific to This Standard:3.2.1 applicatorthe person or persons

13、 who apply interiorreflective coating materials in buildings.3.2.2 conditioned spaceany space in a building that isserved by a heating or cooling system.1This practice is under the jurisdiction of ASTM Committee C16 on ThermalInsulationand is the direct responsibility of Subcommittee C16.21 on Refle

14、ctiveInsulation.Current edition approved Nov. 15, 2015. Published December 2015. Originallyapproved 1996. Last previous edition approved in 2014 as C132114. DOI:10.1520/C1321-15.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org.

15、For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from National Fire Protection Association (NFPA), 1 BatterymarchPark, Quincy, MA 02169-7471, http:/www.nfpa.org.4Available from Consumer Product Safety Commission, https:/w

16、ww.cpsc.gov.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States13.2.3 Interior Radiation Control Coating Systems(IRCCS)a building construction consisting of a low emit-tance (0.25 or less) surface bounded by an open air space. AnIRCCS is

17、used for the sole purpose of limiting heat transfer byradiation and is not specifically intended to reduce heat transferby convection or conduction.3.2.4 open air spacea vented building cavity (forexample, a vented attic) or a large conditioned or uncondi-tioned building space.3.2.5 DiscussionA larg

18、e building space is defined as onewhose minimum dimension exceeds two feet.3.2.6 ownerthe person, partnership, corporation, agency,or other entity who owns the building in which the IRCCS isto be applied whether such ownership is by virtue of deed,contract, or any other instrument for acquiring lega

19、l title underthe laws of the state in which the building is located.4. Significance and Use4.1 This practice recognizes that effectiveness, safety, anddurability of an IRCCS depends not only on the quality of thematerials, but also on the proper installation.4.2 Improper installation of an IRCCS wil

20、l reduce itsthermal effectiveness, cause fire risks and other unsafeconditions, and promote deterioration of the structure in whichit is installed. Improper installation has the potential to createspecific hazards that include: heat buildup in recessed lightingfixtures, deterioration of failure of e

21、lectrical wiringcomponents, and deterioration of wood structures and paintfailure due to moisture accumulation.4.3 This practice provides directions for the installation ofIRCCS materials in a safe and effective manner. Actualconditions in existing buildings will vary greatly.4.4 The user shall cons

22、ult the manufacturer for applicationand installation methods.5. Safety Precautions5.1 The applicator shall meet all of the requirements of themanufacturer, code, and their contract for safety.5.2 Ventilation shall be provided to ensure that mist andoverspray are immediately dispersed from the applic

23、ation area.When natural ventilation is not adequate, place OSHA ap-proved fans in windows or doors adjacent to the applicationarea to improve ventilation. Warnings shall be provided forareas where ventilation is exhausted. Ventilation of the areas ofapplication shall meet all of the requirements of

24、themanufacturer, code, and the installation contract.5.3 The instructions provided by the manufacturer shall beconsulted for all applicable handling and safety requirements.6. Pre-Installation Inspection and Preparation6.1 Inspections:6.1.1 Inspect the roof, walls, ceilings, and floors to identifyar

25、eas where previous or existing moisture problems havecaused paint peeling, warpage, stain, visible fungus growth,rotting, or other structural damage. Do not apply IRCCS insuch areas until the owner has been informed and has certifiedthese conditions have been corrected and the source(s) elimi-nated.

26、6.1.2 In areas where the IRCCS is to be applied, compo-nents of the electrical system shall be in good condition. Whenthere is reason to believe the electrical system is faulty, do notapply the IRCCS in such areas until the owner has beeninformed and qualified inspection and repair have been per-for

27、med.NOTE 1The CPSC Guide to Home Wiring Hazards has identified thefollowing signs of potential electrical deficiencies: lights dimming, fusesblowing, circuit breakers tripping frequently, electrical sparks and glowingfrom receptacles, light flickering, and cover plates on switches and outletsthat ar

28、e warm or hot to the touch. Useful safety information is alsocontained in the NFPA 54 and NFPA 211.6.1.3 In areas where an IRCCS is to be applied, theapplicator shall locate and plan the application around venti-lation openings. The applicator shall not apply the IRCCS in away that will plug or othe

29、rwise obstruct existing ventilationopenings.6.1.4 All inspections for wood grade stamps must be com-plete before application of the product.6.2 Preparations:6.2.1 All electrical wiring at or near the IRCCS applicationsurfaces shall be protected to ensure that the IRCCS materialcannot contact the ele

30、ctrical wiring system.6.2.2 Where attic ventilation is compromised by the instal-lation of an IRCCS or the subsequent application of fibrousinsulation, vent baffles shall be installed at the soffits of theattic such that attic ventilation airflows are maintained inaccordance with applicable building

31、 codes.NOTE 1Apply IRCCS to cover the exposed roof deck area includingsupport structure directly connected to the roof deck (such as purlins,rafters, and top chord of the trusses). The low-emittance surface of theIRCCS must face the interior of the attic.FIG. 1 Typical Residential UseNOTE 1Apply the

32、 IRCCS to cover the entire interior surface area. Thelow-emittance surface of the IRCCS must face the interior of the building.FIG. 2 Typical Industrial, Commercial, and Agricultural UseC1321 1526.2.3 All materials shall be mixed for at least 2 minimmediately before spraying. The instructions provid

33、ed by themanufacturer shall be consulted for type of mixing equipmentand mixing methods to be employed. When material is to besprayed from a pressure pot, the pot shall be equipped with anair driven agitator.7. Installation Guidelines7.1 Material Handling:7.1.1 The IRCCS materials shall be applied,

34、handled, andstored in accordance with manufacturers instructions.7.1.2 The IRCCS materials shall not be applied in directcontact with corrosive building materials.7.2 Performance Considerations:7.2.1 The performance of the IRCCS depends on adherenceto the installation instructions provided by the ma

35、nufacturer.The installation instructions and local building codes shall befollowed. The manufacturer shall provide product sheet(s) thatspecify the products intended use(s), application method(s),health and safety considerations, and material properties toinclude: (1) the IRCCS surface emittance det

36、ermined inaccordance with Test Method C1371;(2) the applied materialwater vapor transmission rate, in accordance with Test Meth-ods E96/E96M and; (3) the applied material surface burningcharacteristics in accordance with Test Method E84.7.2.2 The performance of the IRCCS is dependent on themaintenan

37、ce of an open airspace facing the low emittancesurface.7.2.3 The performance of the IRCCS are affected by foreignmaterials on the low emittance surface. After application,foreign materials shall be removed using manufacturersinstructions, taking care not to damage the IRCCS surface.7.2.3.1 Some IRCC

38、S will provide a high resistance to watervapor transmission. An IRCCS shall not be applied so as tolead to moisture accumulation and deterioration in the struc-ture.7.2.4 All roof support structure directly connected to theroof deck (such as purlins, rafters, and top chord of trusses)shall be coated

39、 on any exposed surface.7.3 Post-installationThe applicator shall provide a signedand dated statement describing the IRCCS applicator, installedin accordance with Practice C1321 and the area covered.8. Keywords8.1 low emittance; painthigh reflectance; painthightemperature; paintlow emittance; paints

40、pray-applied; ra-diation; radiation control coating; radiation control coatinginteriorASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentionedin this standard. Users of this standard are expressly advised that determination of t

41、he validity of any such patent rights, and the riskof infringement of such rights, are entirely their own responsibility.This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years andif not revised, either reapproved or withdrawn. Yo

42、ur comments are invited either for revision of this standard or for additional standardsand should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of theresponsible technical committee, which you may attend. If you feel that your comment

43、s have not received a fair hearing you shouldmake your views known to the ASTM Committee on Standards, at the address shown below.This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,United States. Individual reprints (single or mul

44、tiple copies) of this standard may be obtained by contacting ASTM at the aboveaddress or at 610-832-9585 (phone), 610-832-9555 (fax), or serviceastm.org (e-mail); or through the ASTM website(www.astm.org). Permission rights to photocopy the standard may also be secured from the Copyright Clearance Center, 222Rosewood Drive, Danvers, MA 01923, Tel: (978) 646-2600; http:/ 153

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 标准规范 > 国际标准 > ASTM

copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1