1、Designation: E 2307 04e1An American National StandardStandard Test Method forDetermining Fire Resistance of Perimeter Fire BarriersUsing Intermediate-Scale, Multi-story Test Apparatus1This standard is issued under the fixed designation E 2307; the number immediately following the designation indicat
2、es the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.e1NOTEThe word “system” was deleted from the phrase “per
3、imeter fire barrier system” throughout in September 2004.INTRODUCTIONA perimeter fire barrier is the perimeter joint protection that provides fire resistance to preventpassage of fire from floor to floor within the building at the opening between the exterior wallassembly and the floor assembly. A p
4、erimeter fire barrier is a unique building construction detail notaddressed by other fire test methods.Among its other functions, a perimeter fire barrier impedes the vertical spread of fire from the floorof origin to the floor(s) above, at the buildings exterior perimeter and accommodates variousmo
5、vements such as those induced by thermal differentials, seismicity, and wind loads.This test method describes criteria and test methods used to determine the fire resistance ofperimeter fire barriers when subjected to standard fire exposure conditions using the intermediate-scale, multistory test ap
6、paratus (ISMA). The use of the multi-story test apparatus and this test methodare intended to simulate a possible fire exposure on a perimeter fire barrier.1. Scope1.1 This test method measures the performance of theperimeter fire barrier and its ability to maintain a seal toprevent fire spread duri
7、ng the deflection and deformation of theexterior wall assembly and floor assembly during the fire test,while resisting fire exposure from an interior compartment fireas well as from the flame plume emitted from the windowburner below. The end point of the fire resistance test is theperiod of time el
8、apsing before the first condition of complianceis reached as the perimeter fire barrier is subjected to atime-temperature fire exposure.1.2 The fire exposure conditions used are those specified bythis test method for the first 30 min of exposure and thenconform to the Test Methods E119time-temperatu
9、re curve forthe remainder of the test in the test room.1.3 This test method specifies the heating conditions, meth-ods of test, and criteria for evaluation of the ability of aperimeter fire barrier to maintain the fire resistance where afloor and exterior wall assembly are juxtaposed to a perimeterj
10、oint.1.4 Test results establish the performance of perimeter firebarriers during the fire-exposure period and shall not beconstrued as having determined the suitability of perimeter firebarriers for use after that exposure.1.5 This test method does not provide quantitative informa-tion about the per
11、imeter fire barrier relative to the rate ofleakage of smoke or gases or both. While it requires that suchphenomena be noted and reported when describing the generalbehavior of perimeter fire barrier during the fire resistance test,such phenomena are not part of the conditions of compliance.1.6 Poten
12、tially important factors and fire characteristics notaddressed by this test method include, but are not limited to:1.6.1 The performance of the perimeter fire barrier con-structed with components other than those tested, and1.6.2 The cyclic movement capabilities of perimeter firebarriers other than
13、the cycling conditions tested.1.7 This test method is used to measure and describe theresponse of materials, products or assemblies to heat and flameunder controlled conditions but does not by itself incorporateall factors required for the fire-hazard or fire-risk assessment ofthe materials, product
14、s, or assemblies under actual fire condi-tions.1.8 The values stated in inch-pound units are to be regardedas the standard. The SI values given in parentheses are forinformation only.1.9 The text of this test method references notes andfootnotes which provide explanatory material. These notes andfoo
15、tnotes (excluding those in tables and figures) shall not beconsidered as requirements of the standard.1This test method is under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsibility of Subcommittee E05.11 on FireResistance.Current edition approved March 1, 2004. P
16、ublished April 2004.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.1.10 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to es
17、tablish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2E84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE 108 Test Methods for Fire Tests of Roof CoveringsE119 Test Met
18、hods for Fire Tests of Building Constructionand MaterialsE 176 Terminology of Fire StandardsE511 Test Method for Measuring Heat Flux Using aCopper-Constantan Circular Foil, Heat-Flux GageE 631 Terminology of Building ConstructionsE 1529 Test Methods for Determining Effects of LargeHydrocarbon Pool F
19、ires on Structural Members and As-sembliesE 1966 Test Method for Fire-Resistive Joint Systems2.2 Other Documents:Uniform Building Code Standard No. 26-9 Method of Testfor the Evaluation of Flammability Characteristics ofExterior, Non-Loadbearing Wall Assemblies ContainingCombustible Components Using
20、 the Intermediate-ScaleMultistory Test Apparatus3NFPA 285 Standard Method of Test for the Evaluation ofFlammability Characteristics of Exterior Non-Load-Bearing Wall Assemblies Containing Combustible Com-ponents Using the Intermediate-Scale, Multistory TestApparatus4The 14th Edition of the Gypsum As
21、sociations Fire Resis-tance Design Manual (GA 600 94)53. Terminology3.1 Terms defined in Terminology E 176 and E 631 shallprevail for fire standard and building terms not defined in thisdocument.3.1.1 blockout, na recess formed in the floor assembly toaccommodate the installation of the perimeter jo
22、int protection,flush with the wearing surface of the floor assembly.3.1.2 curtain wall assembly, neither a rated or non-rated,nonbearing exterior wall assembly secured to and supported bythe structural members of the building.3.1.3 exterior wall assembly, na curtain wall or a load-bearing exterior w
23、all that is either fire resistance rated or onethat is not.3.1.4 floor assembly, na fire resistance rated loadbearinghorizontal separating element adjacent to and separate from thefloor of the observation room.3.1.4.1 DiscussionFloor assemblies tested in accordancewith Test Methods E119are required
24、to be loadbearing.3.1.5 integrity, nthe ability of a perimeter fire barrier,when exposed to fire from two sides, to prevent the passage offlame and hot gases through it and the occurrence of flames onits unexposed sides as determined by using a cotton pad.3.1.6 maximum joint width, nthe widest openi
25、ng of theperimeter joint as defined by the test sponsor.3.1.7 minimum joint width, nthe narrowest opening of theperimeter joint as defined by the test sponsor.3.1.8 movement cycle, nthe change between the minimumand the maximum joint widths.3.1.9 nominal joint width, nthe specified opening of theper
26、imeter joint as defined by the test sponsor that is selected fortest purposes.3.1.10 observation room, nthe second-story room of theISMA.3.1.11 perimeter fire barrier, nthe perimeter joint protec-tion that provides fire resistance to prevent the passage of firefrom floor to floor within the building
27、 at the opening betweenthe exterior wall assembly and the floor assembly. The bound-aries are the edge of the floor assembly and the interior face ofthe exterior wall assembly in contact with the perimeter jointprotection.3.1.11.1 DiscussionFor the purpose of this standard, aknee wall is not to be c
28、onsidered as part of the exterior wall.3.1.12 perimeter joint, nthe linear void located between ajuxtaposed exterior wall assembly and floor assembly toaccommodate various movements induced by thermal differ-entials, seismicity, wind loads, and misalignments of the floorand wall during construction.
29、3.1.13 perimeter joint protection, na fire-resistive jointsystem located between the exterior wall assembly and thefloor assembly that fills the perimeter joint.3.1.13.1 DiscussionFire-resistive joint system is definedin Test Method E 1966.3.1.14 separating element, na floor assembly or exteriorwall
30、 assembly.3.1.15 splice, nthe connection or junction within thelength of a perimeter joint protection.3.1.15.1 DiscussionA splice is a result of the device ormethod used to connect or join multiple lengths of theperimeter joint protection.3.1.16 supporting construction, nthe arrangement ofseparating
31、 elements forming the intersection into which theperimeter joint protection is installed.3.1.17 test assembly, nthe complete assembly of the testspecimen together with the test apparatus.3.1.18 test room, nthe first-story room of the ISMA.3.1.19 test specimen, nthe specific test details of theperime
32、ter fire barrier.4. Summary of Test Method4.1 This test method describes the following test sequenceand procedure:2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to th
33、e standards Document Summary page onthe ASTM website.3International Conference of Building Officials Inc., 5360 Workman Mill Rd.,Whittier, CA 90601.4National Fire Protection Association, 1 Batterymarch Park, Quincy, MA02269-9101.5Gypsum Association, 810 First Street NE #510, Washington, DC 20002.E23
34、0704e124.1.1 When the maximum joint width does not equal theminimum joint width, the perimeter fire barrier is movementcycled before being fire tested.4.1.2 A perimeter joint protection and its supporting con-struction are conditioned and fire tested.4.1.3 During the fire test, the integrity of the
35、perimeter jointprotection and its supporting construction is determined by useof a cotton pad.5. Significance and Use5.1 This test method provides for the following measure-ments and evaluations:5.1.1 Movement capacity of the perimeter fire barrier.5.1.2 Loadbearing capacity of the perimeter joint p
36、rotectionis optional.5.1.3 Ability of the perimeter fire barrier to resist thepassage of flames and hot gases.5.1.4 Transmission of heat through the perimeter fire barrier.5.2 This test method does not provide the following:5.2.1 Evaluation of the degree to which the perimeter firebarrier contribute
37、s to the fire hazard by generation of smoke,toxic gases, or other products of combustion,5.2.2 Measurement of the degree of control or limitation ofthe passage of smoke or products of combustion through theperimeter fire barrier,NOTE 1This test method does not measure the quantity of smoke orhot gas
38、es through the floor assembly, the wall assembly, or the perimeterjoint protection.5.2.3 Measurement of flame spread over the surface of theperimeter fire barrier,NOTE 2The information in 5.2.1 through 5.2.3 are determined byother suitable fire test methods. For example, Test Method E84is used todet
39、ermine 5.2.3.5.2.4 Durability of the test specimen under actual serviceconditions, including the effects of cycled temperature,5.2.5 Effects of a load on the movement cycling of theperimeter fire barrier established by this test method,5.2.6 Rotational, vertical, and horizontal shear capabilitiesof
40、the test specimen,5.2.7 Any other attributes of the test specimen, such as wearresistance, chemical resistance, air infiltration, water-tightness,and so forth, and5.2.8 A measurement of the capability of the test specimento resist:5.2.8.1 Flame propagation over the exterior faces of the testspecimen
41、,5.2.8.2 Spread of flame within the combustible core com-ponent of the exterior wall assembly from one story to the next,NOTE 3Some exterior wall assemblies are made from sandwichFIG. 1 Plan View of Test Room Burner Positioned in Test Room (See 6.3.2 for Dimensions)E230704e13panels, which use EPS fo
42、am or other similar materials that are combus-tible.5.2.8.3 Spread of flame over the interior surface (room side)of the test specimen from one story to the next, andNOTE 4While it is a failure to have fire on the interior surface of theobservation room, this test method does not provide a measuremen
43、t of thatflame spread.5.2.8.4 Lateral spread of flame from the compartment of fireorigin to adjacent spaces.NOTE 5The exterior wall assembly, floor assembly, and perimeterjoint protection are individual components. The capabilities of individualcomponents are not part of this specific test methods C
44、onditions ofCompliance.5.3 In this test method, the test specimens are subjected toone or more specific test conditions. When different testconditions are substituted or the end-use conditions arechanged, it is not always possible by, or from, this test methodto predict changes to the characteristic
45、s measured.5.4 This test method is not intended to be used as the onlytest method in the selection of a perimeter fire barrier. It is notintended as a specification for all attributes required by aperimeter fire barrier, or any of its individual components, inorder for a perimeter fire barrier to be
46、 used in a particularapplication.6. Apparatus6.1 The test apparatus described in 6.2 shall be locatedinside a test facility. The facility shall have provisions forsupplying fresh combustion make-up air during the test. Thefacility shall be constructed to allow for the exhaust of thecombustion by-pro
47、ducts during the test, while not inducingairflow on the exterior face of the test specimen. The testfacility shall protect the test apparatus and test specimen fromweather conditions such as wind and rain.6.2 Test Apparatus:6.2.1 The ISMA consists of a two-story test structureconsisting of a test ro
48、om and observation room (See Fig. 2.).Each room in the test apparatus is square having inside lengthand width dimensions (unfinished and unprotected by any fireresistive materials) of 120 6 0.5 in. (3048 6 13 mm) and aheight (unfinished and unprotected by any fire resistive mate-rials) of 84 6 0.5 i
49、n. (2134 6 13 mm).NOTE 6The test apparatus is similar to the one used in U.B.C.FIG. 2 Plan View of Window Burner and Elevation View of Window Burner LocationE230704e14FIG. 3 Example of an Exterior Wall Assembly with Window Opening in a Test Frame (See 7.3.1)E230704e15Standard No. 26-9 and NFPA 285.6.2.2 The floors and roof of the test apparatus shall besupported by columns and beams of a size that will support theload of the floor and roof. These supports shall be locatedoutside of both the test room and the observation room. Thefloor of the observati