1、Designation: F2487 06 (Reapproved 2012)F2487 13 An American National StandardStandard Practice forInfiltration and Exfiltration Acceptance Testing of InstalledCorrugated High Density Polyethylene and PolypropylenePipelines1,2This standard is issued under the fixed designation F2487; the number immed
2、iately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has
3、 been approved for use by agencies of the U.S. Department of Defense.1. Scope Scope*1.1 This practice covers procedures for testing installed non-perforated, gasketed corrugated high-density polyethylene (HDPE)and corrugated polypropylene (PP) pipelines using either water infiltration or exfiltratio
4、n acceptance limits to demonstrate theintegrity via the level of leakage of the installed materials, construction procedures and installation qualityvia the level of leakage.Pipe to be tested under this practice shall include corrugated HDPE and PP drainage pipe meeting the requirements of AASHTOM 2
5、52, AASHTO M 294 and SpecificationSpecifications F2306/F2306M., F2736, F2762, F2763, F2764, and F2947.NOTE 1The performance criteria specified in this standard may be used for other plastic pipe products. The engineer, however, must assess if thetesting procedures are adequate for the particular mat
6、erial and installation being considered.NOTE 2The user of this practice is advised that test criteria presented in this practice are similar to those in general use. Pipe, 600-mm (24-in.)diameter or larger, may be accepted by visual inspection when testing for infiltration.1.2 The values stated in S
7、I units are to be regarded as the standard. The values in parentheses are mathematical conversions toinch-pounds, which are provided for informational purposes only and are not considered standard.1.3 This test method shall be performed on lines after all connections and service laterals have been p
8、lugged and bracedadequately to withstand the test pressures. The time between completion of the backfill operations and testing shall be specifiedby the approving authority.1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibi
9、lityof the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatorylimitations prior to use. The testing required under this standard necessitates operating in confined spaces. The user must insurethat all OSHA and local safety codes ar
10、e duly observed.2. Referenced Documents2.1 ASTM Standards:3D3212 Specification for Joints for Drain and Sewer Plastic Pipes Using Flexible Elastomeric SealsF412 Terminology Relating to Plastic Piping SystemsF2306/F2306M Specification for 12 to 60 in. 300 to 1500 mm Annular Corrugated Profile-Wall Po
11、lyethylene (PE) Pipe andFittings for Gravity-Flow Storm Sewer and Subsurface Drainage ApplicationsF2736 Specification for 6 to 30 in. (152 To 762 mm) Polypropylene (PP) Corrugated Single Wall Pipe And Double Wall PipeF2762 Specification for 12 to 30 in. (300 to 750 mm) Annular Corrugated Profile-Wal
12、l Polyethylene (PE) Pipe and Fittings forSanitary Sewer ApplicationsF2763 Specification for 30 to 60 in. 750 to 1500 mm Triple Profile-Wall Polyethylene (PE) Pipe and Fittings for SanitarySewer ApplicationsF2764 Specification for 30 to 60 in. 750 to 1500 mm Polypropylene (PP) Triple Wall Pipe and Fi
13、ttings for Non-PressureSanitary Sewer Applications1 This practice is under the jurisdiction of ASTM Committee F17 on Plastic Piping Systems and is the direct responsibility of Subcommittee F17.20 on Joining.Current edition approved Aug. 1, 2012Nov. 1, 2013. Published October 2012December 2013. Origi
14、nally approved in 2006. Last previous edition approved in 20062012as F2487F248706(2012).06. DOI: 10.1520/F2487-06R12.10.1520/F2487-13.2 Available from American Association of State Highway and Transportation Officials (AASHTO), 444 N. Capitol St., NW, Suite 249, Washington, DC 20001,http:/www.transp
15、ortation.org.3 For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standards Document Summary page on the ASTM website.This document is not an ASTM standard and is int
16、ended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the curr
17、ent versionof the standard as published by ASTM is to be considered the official document.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1F2947 Specification for 150 to
18、1500 mm 6 to 60 in. Annular Corrugated Profile-Wall Polyethylene (PE) Pipe and Fittings forSanitary Sewer Applications2.2 AASHTO Standards2M 252 Standard Specification for Corrugated Polyethylene Drainage Pipe 75 to 250-mm (3 to 10-inch) DiameterM 294 Standard Specification for Corrugated Polyethyle
19、ne Drainage Pipe 300 to 1500-mm (12 to 60-inch) Diameter3. Terminology3.1 DefinitionsFor definitions of terms relating to plastic pipe, see Terminology F412.4. Summary of Practice4.1 Determine the groundwater conditions surrounding the section of pipeline to be tested and select the type of test to
20、beconducted.4.2 For the infiltration test, the amount of water leaking into the pipeline is measured, and the rate of infiltration is determined.If the rate is less than or equal to the allowable limit, the section of pipe tested is acceptable.4.3 For the exfiltration test, the pipeline is filled wi
21、th water to the specified test head and the rate of water loss is determined.If the rate is less than or equal to the allowable limit, the section of pipe tested is acceptable.5. Significance and Use5.1 This is not a routine test. The values recorded are applicable only to the pipe being tested and
22、at the time of testing.6. Preparation of the Pipeline6.1 The pipe shall be free of debris prior to testing.6.2 The manholes, the ends of the branches, laterals, wyes and stubs to be included in the test shall be plugged. All plugs shallbe secured to prevent leakage blowout due to testing pressure.Wa
23、rningThe test places extremely high forces on plugs used forsealing the pipeline for pressure testing. Plugs must be properly blocked and braced against movement before the test begins. Allconfined space procedures shall be observed during preparation and conducting of this test. Under no circumstan
24、ces shall anypersons be permitted inside the manhole during pressure testing.7. Procedure7.1 Infiltration Testing:7.1.1 Conduct testing from manhole to manhole. The length of pipeline tested shall not exceed 213 m (700 ft).7.1.2 Stop all dewatering operations and allow the groundwater to return to i
25、ts normal level. Infiltration testing shall not be usedunless the groundwater level is at least 0.6 m (2 ft) above the crown of the pipe for the entire length of the test section.7.1.3 Plug all pipe outlets discharging into the upstream manhole.7.1.4 Measure the groundwater elevation and determine t
26、he average head over the test section.7.1.5 Measure infiltration leakage at the outlet of the test section. Because leakage allowances are small, measurements are bestmade by either timing the filling of a small container of known volume, or by directing flow into a container for a specified timeand
27、 measuring the content, or by using small weirs.7.1.6 If the measured rate of leakage is less than or equal to the allowable leakage in accordance with 8.1, the section of pipelinetested is acceptable.7.1.7 If the test section fails, the line shall be repaired and retested in accordance with this pr
28、actice.7.2 Exfiltration Testing:7.2.1 Conduct testing from manhole to manhole. The length of pipeline tested shall not exceed 213 m (700 ft).7.2.2 Determine the groundwater elevation at both ends of the test section. If the groundwater level is less than 0.6 m (2 ft)above the crown of the pipe measu
29、red from the highest elevation of the pipeline, the exfiltration test shall be used.7.2.3 Plug all pipe outlets discharging into the upstream manhole and the test section outlet. Fill the pipeline with water.7.2.4 At the upstream manhole the test head shall be established as minimum of 0.6 m (2 ft)
30、above the crown of the pipe, orat least 0.6 m (2 ft) above existing groundwater, whichever is higher.7.2.5 Measure the leakage loss over a timed test period. The minimum test period shall be 15 min and the maximum shall notexceed 24 h.7.2.6 If the measured rate of leakage is less than or equal to th
31、e allowable leakage, in accordance with 8.1, the section of pipelinetested is acceptable.7.2.7 If the test section fails, the line shall be repaired and retested in accordance with this practice. The groundwater elevationshall be redetermined prior to a second test and the test head adjusted, if nec
32、essary, in accordance with 7.2.4.8. Leakage Criteria8.1 Leakage criteria for infiltration and exfiltration testing shall be determined by the owner based on their application anddesign requirements.F2487 132NOTE 3If the hydrostatic head is expected to exceed the maximum pressure capacity of the join
33、t, as specified in Specification D3212, the designengineer should review field conditions to determine if a special joint design is required to maintain the long-term integrity of the system.NOTE 4The current Environmental Protection Agencys (EPA) maximum leakage allowance specified for infiltration
34、 and exfiltration acceptance forsanitary pipelines is 18.5 L/(mm of internal diameter) (km of pipeline) (24 h) 200 gal/in/mi/day.9. Keywords9.1 corrugated HDPE pipe; exfiltration; infiltration; leakage testingSUMMARY OF CHANGESCommittee F17 has identified the location of selected changes to this sta
35、ndard since the last issue (F248706(2012) that may impact the use of this standard.(1) Addition of applicable corrugated HDPE and PP standards that have been developed since the original publication of PracticeF2487.ASTM International takes no position respecting the validity of any patent rights as
36、serted in connection with any item mentionedin this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the riskof infringement of such rights, are entirely their own responsibility.This standard is subject to revision at any time
37、by the responsible technical committee and must be reviewed every five years andif not revised, either reapproved or withdrawn.Your comments are invited either for revision of this standard or for additional standardsand should be addressed to ASTM International Headquarters. Your comments will rece
38、ive careful consideration at a meeting of theresponsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you shouldmake your views known to the ASTM Committee on Standards, at the address shown below.This standard is copyrighted by ASTM Inte
39、rnational, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the aboveaddress or at 610-832-9585 (phone), 610-832-9555 (fax), or serviceastm.org (e-mail); or through the ASTM website(www.astm.org). Permission rights to photocopy the standard may also be secured from the ASTM website (www.astm.org/COPYRIGHT/).F2487 133