1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationCable trunking systems and cable ducting systems for electrical installationsPart 2-3: Particular requirements for slotted cable trunking systems intended for installation in cab
2、inetsBS EN 50085-2-3:2010Incorporating corrigendum July 2010National forewordThis British Standard is the UK implementation of EN 50085-2-3:2010. Itsupersedes BS EN 50085-2-3:2001 which is withdrawn.The UK participation in its preparation was entrusted to Technical CommitteePEL/213, Cable management
3、.A list of organizations represented on this committee can be obtained onrequest to its secretary.This publication does not purport to include all the necessary provisions of acontract. Users are responsible for its correct application. BSI 2010 ISBN 978 0 580 71812 0 ICS 29.120.10Compliance with a
4、British Standard cannot confer immunity from legal obligations.This British Standard was published under the authority of the Standards Policy and Strategy Committee on 30 June 2010.Date Text affectedBRITISH STANDARDBS EN 50085-2-3:2010Amendments/corrigenda issued since publication31 July 2010 Corre
5、ction to supersession textEUROPEAN STANDARD EN 50085-2-3 NORME EUROPENNE EUROPISCHE NORM March 2010 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: Avenue Marnix 17,
6、B - 1000 Brussels 2010 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 50085-2-3:2010 E ICS 29.120.10 Supersedes EN 50085-2-3:1999English version Cable trunking systems and cable ducting systems for electrical installations - Part
7、 2-3: Particular requirements for slotted cable trunking systems intended for installation in cabinets Systmes de goulottes et systmes de conduits-profils pour installations lectriques - Partie 2-3: Rgles particulires pour les systmes de goulottes de cblage pour installation dans les armoires Elektr
8、oinstallationskanalsysteme fr elektrische Installationen - Teil 2-3: Besondere Anforderungen an Verdrahtungskanle zum Einbau in Schaltschrnke This European Standard was approved by CENELEC on 2010-03-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate th
9、e conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Standard exist
10、s in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the national electr
11、otechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden,
12、 Switzerland and the United Kingdom. EN 50085-2-3:2010 2 Foreword This European Standard was prepared by the Technical Committee CENELEC TC 213, Cable management systems. It was submitted to the formal vote and was approved by CENELEC as EN 50085-2-3 on 2010-03-01. This document supersedes EN 50085-
13、2-3:1999 and is aligned on EN 50085-1:2005. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and CENELEC shall not be held responsible for identifying any or all such patent rights. The following dates were fixed: latest date b
14、y which the EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2011-03-01 latest date by which the national standards conflicting with the EN have to be withdrawn (dow) 2013-03-01 This European Standard is a system standard for cable m
15、anagement products used for electro-technical purposes. It relates to the Council Directive on the approximation of laws, regulations and administrative provisions of the Member States relating to Low Voltage (Directive 2006/95/EC) through consideration of the essential requirements of this directiv
16、e. This European Standard is supported by separate standards to which references are made. This Part 2-3 is to be used in conjunction with EN 50085-1:2005, “Cable trunking systems and cable ducting systems for electrical installations Part 1: General requirements”. This Part 2-3 supplements or modif
17、ies the corresponding clauses of EN 50085-1:2005. Where a particular clause or subclause of Part 1 is not mentioned in this Part 2, that clause or subclause applies as far as it is reasonable. Where this Part 2 states “addition“, “modification“ or “replacement” the relevant text of Part 1 is to be a
18、dapted accordingly. NOTE The following numbering system is used: subclauses, tables and figures that are additional to those in Part 1 are numbered starting from 101; additional annexes are lettered AA, BB, etc. _ BS EN 50085-2-3:2010 3 EN 50085-2-3:2010 Contents 1 Scope 4 2 Normative references 4 3
19、 Definitions 4 4 General requirements 5 5 General conditions for tests .5 6 Classification .6 7 Marking and documentation 6 8 Dimensions 6 9 Construction 7 10 Mechanical properties .7 11 Electrical properties .8 12 Thermal properties 9 13 Fire hazard 9 14 External influences . 10 15 Electromagnetic
20、compatibility . 10 Annex A (informative) Types of cable trunking systems (CTS) and cable ducting systems (CDS) . 16 Annex B (informative) A-deviations . 16 Annex AA (normative) Compliance checks to be carried out for slotted cable trunking systems intended for installation in cabinets complying with
21、 EN 50085-2-3:1999 . 16 Bibliography . 17 Figures Figure 101 Examples of pattern of fixing holes in the base of the slotted trunking length 11 Figure 102 Examples of sizes for the fixing holes 12 Figure 103 Fixing distances for cable support test of 10.2 . 13 Figure 104 Arrangements for cable suppor
22、t test of 10.2 14 Figure 105 Arrangement for flame test of 13.1.3 . 15 BS EN 50085-2-3:2010EN 50085-2-3:2010 4 1 Scope Replacement: This European Standard specifies requirements and tests for cable trunking systems (CTS) and cable ducting systems (CDS) intended for the accommodation, and where neces
23、sary for the electrically protective separation, of insulated conductors, cables and possibly other electrical equipment in electrical and/or communication systems installations. The maximum voltage of these installations is 1 000 V a.c. and 1 500 V d.c. Slotted cable trunking systems are intended f
24、or mounting inside cabinets in electrical and/or communication system installations. This European Standard does not apply to conduit systems, cable tray systems, cable ladder systems, power track systems or equipment covered by other standards. This European Standard shall be used in conjunction wi
25、th EN 50085-1:2005 “Cable trunking systems and cable ducting systems for electrical installations Part 1: General requirements” which is referred to in this document as Part 1. Wherever reference is made in this European Standard to EN 50085-1:2005 this does not apply to cable ducting systems. 2 Nor
26、mative references Replacement: EN 50085-1 2005 Cable trunking systems and cable ducting systems for electrical installations Part 1: General requirements EN 50085-2-3 1999 Cable trunking systems and cable ducting systems for electrical installations Part 2-3: Particular requirements for slotted cabl
27、e trunking systems intended for installation in cabinets EN 60695-11-5 2005 Fire hazard testing Part 11-5: Test flames Needle-flame test method Apparatus, confirmatory test arrangement and guidance (IEC 60695-11-5:2004) HD 383 S2 1986 1)Conductors of insulated cables First supplement: Guide to the d
28、imensional limits of circular conductors (IEC 60228:1978, mod. + IEC 60228A:1982, mod.) 3 Definitions For the purposes of this document, the terms and definitions of Part 1 apply except as follows. Addition: 3.101 slotted cable trunking system system comprising a slotted trunking length and possibly
29、 other slotted cable trunking system components for the accommodation and laying in of insulated conductors or cables intended for use in a cabinet or similar 1)Superseded by EN 60228:2005, Conductors of insulated cables (IEC 60228:2004). BS EN 50085-2-3:2010 5 EN 50085-2-3:2010 3.102 slotted cable
30、trunking system component part of the system which includes a) slotted trunking length, b) trunking fitting, c) fixing device, d) system accessory NOTE The above mentioned system components may not necessarily be included all together in a system. Different combinations of system components may be u
31、sed. 3.103 slotted trunking length trunking length with slotted walls and with cover(s) which may be integral part of the base and/or may be slotted 3.104 slotted wall wall with openings allowing cables to pass through NOTE The openings can be with open or closed boundary and may have different shap
32、es, normally designed to maintain wiring in position. 3.105 wall finger part of a slotted wall between two consecutive slots with open boundary 3.106 break-out line line which may be available on the walls of a trunking length to facilitate the breaking of walls or parts thereof, such as a wall fing
33、er 4 General requirements Replacement: Slotted cable trunking systems shall be so designed and constructed that where required they ensure reliable support, accommodation and segregation of the insulated conductors and/or cables contained therein. Equipment associated with or incorporated in a syste
34、m component but which is not a system component, shall and need only comply with the relevant standard of this equipment, if any. However it may be necessary to include such equipment in a test arrangement for the purpose of testing its interface with the slotted cable trunking system. Compliance is
35、 checked by carrying out all the tests specified. 5 General conditions for tests This clause of Part 1 is applicable. BS EN 50085-2-3:2010EN 50085-2-3:2010 6 6 Classification This clause of Part 1 is applicable except as follows. 6.2 Not applicable 6.3 Table 2 is not applicable. 6.5 Not applicable 6
36、.6 Not applicable 6.7 Not applicable 6.9 Not applicable 6.10 Not applicable Addition: 6.101 According to the intended installation positions 6.101.1 Mounted on vertical or horizontal surface 6.101.2 Mounted on vertical or horizontal surface except in a cover down position 7 Marking and documentation
37、 This clause of Part 1 is applicable. 8 Dimensions This clause of Part 1 is applicable except as follows. Addition: 8.101 Preferred solution for fixing holes, if any, in the base of the slotted trunking lengths according to the different trunking widths as shown in Figure 101 is as follows: - trunki
38、ng lengths with a nominal width less or equal to 12,5 mm should preferably have one row of small holes only, as shown in Figure 102 b); - trunking lengths with a nominal width greater than 12,5 mm and less or equal to 62,5 mm, should preferably have one row of holes only, alternately as shown in Fig
39、ure 102 a) and in Figure 102 b); - trunking lengths with a nominal width greater than 62,5 mm should preferably have two or more rows of holes alternately as shown in Figure 102 a) and in Figure 102 b), positioned at a distance of 25 mm or 50 mm apart, symmetrically located from the trunking centre
40、line. BS EN 50085-2-3:2010 7 EN 50085-2-3:2010 9 Construction This clause of Part 1 is applicable except as follows. 9.2 Not applicable 9.5 Not applicable 9.6 Not applicable 9.7 Not applicable 9.8 Not applicable 9.9 Not applicable 9.10 Not applicable 9.11 Not applicable 9.12 Not applicable 10 Mechan
41、ical properties This clause of Part 1 is applicable except as follows. 10.2 Cable support test Replacement: 10.2.1 General test conditions Each test is made on one new sample of slotted trunking length having a length of (250 5) mm. Before the test non metallic and composite slotted trunking lengths
42、 are aged at a temperature declared according to Table 3 for (168 4) h continuously. The sample is securely fixed, using 10 mm external diameter flat metallic washers and appropriate metallic screws to a rigid smooth support such as a plywood board 16 mm thick. When 10 mm external diameter is too la
43、rge, suitable smaller washer and appropriate screw are used. Fixing(s) are positioned as shown in Figure 103 at (200 5) mm centres along the length of the sample. Within the width of the sample: for trunking with a width less than 50 mm, one fixing is used as shown in Figure 103 a); for trunking wit
44、h a width equal or greater than 50 mm, two fixings are used as shown in Figure 103 b). If the manufacturers instructions require the use of cable retainers or dividers, these are fitted according to the manufacturers instructions. Cable retainers, if any, are symmetrically fixed along the length. Th
45、e sample is subjected to an evenly distributed load of 0,8 g per mm of the declared usable area for cables, per metre length. The load is distributed between the compartments proportionally to the declared usable area. The load consists of copper insulated conductors or cables complying with class 5
46、, Table 3 of HD 383 S2:1986, or flexible insulated conductors or cables of similar mass per meter. BS EN 50085-2-3:2010EN 50085-2-3:2010 8 To allow for settlement of the sample, a pre-load of 10 % of the load is applied and removed after (300 30) s. The measurement apparatus is then calibrated to ze
47、ro. Insulated conductors or cables of 25 mm nominal cross section are placed in the sample so that approximately 50 % of the load is achieved. Insulated conductors or cables of 2,5 mm nominal cross section are placed on top of the larger cables to achieve the total load within a tolerance of 5 g. If
48、 the dimensions of the compartment do not permit the accommodation of 25 mm insulated conductor or cable, 2,5 mm nominal cross section insulated conductors or cables are used. Non metallic and composite slotted trunking lengths are tested at the maximum application temperature declared by the manufa
49、cturer according to Table 3. 10.2.2 Slotted trunking lengths are mounted according to Figure 104 a). After (120 + 5/0) min with the load still applied the vertical deflection F is measured at approximately the middle of the length. F shall not exceed 10 % of the height H with a maximum of 10 mm (see Figure 104 a). 10.2.3 Slotted trunking lengths classified according to 6.101.1 are mounted according to Figure 104 b). After (120 + 5/0) min with the load still applied