1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationLive working Insulating ropesBS EN 62192:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 31/08/2010 07:11, Uncontrolled Copy, (c) BSINational forewordThis British Stan

2、dard is the UK implementation of EN 62192:2009. It is identical to IEC 62192:2009.The UK participation in its preparation was entrusted to Technical CommitteePEL/78, Tools for live working.A list of organizations represented on this committee can be obtained onrequest to its secretary.This publicati

3、on does not purport to include all the necessary provisions of acontract. Users are responsible for its correct application. BSI 2010ISBN 978 0 580 57283 8ICS 13.260; 29.240.20; 29.260.99Compliance with a British Standard cannot confer immunity fromlegal obligations.This British Standard was publish

4、ed under the authority of the StandardsPolicy and Strategy Committee on 31 May 2010.Amendments issued since publicationAmd. No. Date Text affectedBRITISH STANDARDBS EN 62192:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 31/08/2010 07:11, Uncontrolled Copy, (c) BSIEUROPEAN STANDARD EN 62

5、192 NORME EUROPENNE EUROPISCHE NORM June 2009 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: Avenue Marnix 17, B - 1000 Brussels 2009 CENELEC - All rights of exploit

6、ation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 62192:2009 E ICS 13.260; 29.240.20; 29.260.99 English version Live working - Insulating ropes (IEC 62192:2009) Travaux sous tension - Cordes isolantes (CEI 62192:2009) Arbeiten unter Spannung - Isolierende Seile (

7、IEC 62192:2009) This European Standard was approved by CENELEC on 2009-05-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and

8、bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsi

9、bility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, G

10、reece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. BS EN 62192:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 31/08/2010 07:11, Uncontrol

11、led Copy, (c) BSIEN 62192:2009 2 Foreword The text of document 78/773/FDIS, future edition 1 of IEC 62192, prepared by IEC TC 78, Live working, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as EN 62192 on 2009-05-01. The following dates were fixed: latest date by which t

12、he EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2010-02-01 latest date by which the national standards conflicting with the EN have to be withdrawn (dow) 2012-05-01 Annex ZA has been added by CENELEC. _ Endorsement notice The tex

13、t of the International Standard IEC 62192:2009 was approved by CENELEC as a European Standard without any modification. In the official version, for Bibliography, the following note has to be added for the standard indicated: IEC 60743 + A1 NOTE Harmonized as EN 60743:2001 + A1:2008 (not modified).

14、_ BS EN 62192:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 31/08/2010 07:11, Uncontrolled Copy, (c) BSI 3 EN 62192:2009 Annex ZA (normative) Normative references to international publications with their corresponding European publications The following referenced documents are indispen

15、sable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. NOTE When an international publication has been modified by common modifications, indicated by (

16、mod), the relevant EN/HD applies. Publication Year Title EN/HD Year IEC 60060-1 - 1)High-voltage test techniques - Part 1: General definitions and test requirements HD 588.1 S1 1991 2)IEC 60212 1971 Standard conditions for use prior to and during the testing of solid electrical insulating materials

17、HD 437 S1 1984 IEC 60417 Data- base Graphical symbols for use on equipment - - IEC 61318 2007 Live working - Conformity assessment applicable to tools, devices and equipment EN 61318 2008 IEC 61477 - 1)Live working - Minimum requirements for the utilization of tools, devices and equipment EN 61477 2

18、009 2)ISO 2307 - 1)Fibre ropes - Determination of certain physical and mechanical properties EN ISO 2307 2005 2)1)Undated reference. 2)Valid edition at date of issue. BS EN 62192:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 31/08/2010 07:11, Uncontrolled Copy, (c) BSI 2 62192 IEC:2009

19、CONTENTS INTRODUCTION.5 1 Scope.6 2 Normative references .6 3 Terms and definitions .6 4 Requirements .7 4.1 Physical and dimensional 7 4.1.1 Physical.7 4.1.2 Dimensional 7 4.2 Electrical .7 4.3 Mechanical7 4.4 Marking .8 4.5 Instructions for use and care .8 5 Tests 9 5.1 General .9 5.2 Atmospheric

20、conditions .9 5.3 Visual verification and dimensional checking .9 5.3.1 Visual verification 9 5.3.2 Dimensional check 9 5.4 Electrical tests.9 5.4.1 Leakage current under dry conditions 9 5.4.2 Tests after water conditioning13 5.5 Mechanical tests .14 5.5.1 Water absorption .14 5.5.2 Capillary14 5.5

21、.3 Elongation and creep.14 5.6 Durability of marking .15 5.7 Verification of the required instructions for use15 6 Conformity assessment of insulating ropes having completed the production phase .15 7 Modifications 15 Annex A (normative) Suitable for live working; double triangle (IEC 60417-5216 (20

22、02-10).16 Annex B (normative) Chronology of type tests .17 Annex C (normative) Classification of defects 18 Annex D (informative) Recommendations for in-service care and periodic testing 19 Bibliography21 Figure 1 Example of test set up to measure leakage current 10 Figure 2 Electrode arrangement on

23、 rope test piece 12 Table B.1 Chronology of type tests 17 Table C.1 Classification of defects and associated requirements and tests 18 BS EN 62192:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 31/08/2010 07:11, Uncontrolled Copy, (c) BSI62192 IEC:2009 5 INTRODUCTION Insulating ropes des

24、igned and manufactured according to this standard contribute to the safety of the users, provided they are used by skilled persons, in accordance with safe methods of work and the instructions for use. This International Standard defines the required electrical properties of insulating ropes which a

25、lready meet other specifications relating to mechanical strength, physical and construction properties, for use in live working at the power frequency system voltages up to and including 800 kV r.m.s. This standard does not propose to address all the safety factors associated with the use of the ins

26、ulating rope. It is the responsibility of the user to establish appropriate safety practices. Ropes which meet this standard can bridge two or more live phase conductors, or one phase conductor and earth as required during live working. Effects of the use of insulating ropes on the dielectric streng

27、th of the installation have to be evaluated. Depending on the configuration of an installation, the use of insulating ropes will have different effects on its dielectric strength. Cotton, sisal and hemp ropes are unsuitable for this application, as are any other ropes that exhibit electrical conduct

28、ivity. Examples of ropes which are able to meet the requirements of this standard are formed from fibres that have been treated with a wax or other chemical which causes the surface of the rope to become hydrophobic. This document has been prepared according to the requirements of IEC 61477 where ap

29、plicable. The product covered by this standard may have an impact on the environment during some or all stages of its life cycle. These impacts can range from slight to significant, be of short-term or long-term, and occur at the global, regional or local level. Except for a requirement for the sele

30、ction of a testing dye and the disposal statement in the instructions for use, this standard does not include requirements and test provisions for the manufacturers of the product, or recommendations to the users of the product for environmental improvement. However, all parties intervening in its d

31、esign, manufacture, packaging, distribution, use, maintenance, repair, reuse, recovery and disposal are invited to take account of environmental considerations. BS EN 62192:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 31/08/2010 07:11, Uncontrolled Copy, (c) BSI 6 62192 IEC:2009 LIVE W

32、ORKING INSULATING ROPES 1 Scope This International Standard covers insulating ropes that are utilized during live working procedures in contact with parts of installations operating at voltages up to and including 800 kV r.m.s. Insulating ropes for live working procedure under rain and/or d.c. condi

33、tions are not covered by this standard. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendme

34、nts) applies. IEC 60060-1, High-voltage test techniques Part 1: General definitions and test requirements IEC 60212:1971, Standard conditions for use prior to and during the testing of solid electrical insulating materials IEC 60417, Graphical symbols for use on equipment IEC 61318:2007, Live workin

35、g Conformity assessment applicable to tools, devices and equipment IEC 61477, Live working Minimum requirements for the utilization of tools, devices and equipment ISO 2307, Ropes Determination of certain physical and mechanical properties 3 Terms and definitions For the purposes of this document, t

36、he terms and definitions given in IEC 61318 and the following apply. 3.1 creep dimensional change with time in a test section of the rope when subjected to continued working load 3.2 elongation initial dimensional change in a test section of the rope subjected to rated working load for a short perio

37、d of time BS EN 62192:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 31/08/2010 07:11, Uncontrolled Copy, (c) BSI62192 IEC:2009 7 3.3 insulating rope rope with electrical insulating properties suitable for use in contact with live parts IEV 651-09-01, modified 3.4 rope stout cord made fr

38、om woven or twisted insulating or non-insulating material used for various handling operations NOTE Ropes, which may come into contact with live conductors, should be insulating. Ropes used to move tools and other equipment into place, which are clear of live parts, may be non-insulating. IEC 60743,

39、 definition 10.1.1, modified 4 Requirements 4.1 Physical and dimensional 4.1.1 Physical Ropes shall be free of visual manufacturing defects such as incorrect impregnation or faulty stranding or cabling. Ropes covered by this standard shall demonstrate low water absorption and capillary action. 4.1.2

40、 Dimensional Diameter and circumference of ropes shall comply with the manufacturer specifications with a tolerance of 10 %. NOTE National or regional standards could specify dimensioning where needed. 4.2 Electrical Ropes covered by this standard shall have appropriate dielectric properties under d

41、ry conditions and when exposed to humid conditions. Splicing of insulating ropes shall be possible, whilst keeping the ropes appropriate dielectric properties and in accordance with the manufacturers instructions. Insulating ropes to be used under rain condition, or d.c. stress are not covered by th

42、is standard. 4.3 Mechanical In addition to other specifications related to mechanical strength and construction properties, ropes covered by this standard shall demonstrate limit elongation under normal loading conditions. BS EN 62192:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 31/08/

43、2010 07:11, Uncontrolled Copy, (c) BSI 8 62192 IEC:2009 4.4 Marking The insulating ropes shall be properly identified. Ropes covered by this standard shall be marked with the following permanent items of marking: name of the manufacturer, or trade mark, year of manufacture, coded with a colour trace

44、r or other means. The following information shall also be supplied, either by a marking or other means on the rope or on each reel of rope or each smallest shipping container: symbol IEC 60417-5216 (2002-10) Suitable for live working; double triangle (see Annex A), NOTE The exact ratio of the height

45、 of the figure to the base of the triangle is 1,43. For the purpose of convenience, this ratio can be between the values of 1,4 and 1,5. number of the relevant IEC standard immediately adjacent to the symbol with year of publication (four digits) (IEC 62192:2009), batch number, details of diameter,

46、type of lay, fibre material, minimum breaking force, creep, recommended working load. The marking shall be durable, clearly visible and legible to a person with normal or corrected vision without additional magnification. 4.5 Instructions for use and care Each reel of rope or each smallest shipping

47、length shall be supplied with the manufacturers written information and instructions for use and care. These instructions shall be prepared in accordance with the general provisions given in IEC 61477. The information and instructions shall include as a minimum: any special treatment of the fibres w

48、hich makes them specially suitable for this application, instructions for splicing, instructions for handling, cleaning, storage and transportation, instructions for periodic testing, repair, and disposal of the rope, period of years from the moment of production in which the mechanical characterist

49、ics can be guaranteed (storage life). BS EN 62192:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 31/08/2010 07:11, Uncontrolled Copy, (c) BSI62192 IEC:2009 9 5 Tests 5.1 General The present standard provides testing provisions to demonstrate compliance of the product to the requirements of Clause 4. These testing provisions are primarily intended to be used as type tests for validation of the design input. Where relevant, altern